background image

HE3XRT               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134773_005                      HE3XRTMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 4

HE3XRT Replacement Parts

M

N

P

L

R

S

A CORES

B FILTERS

C BLOWER DOOR

D TURN  LATCH

E DISCONNECT SWITCH

F TRANSFORMER

G ISOLATION RELAY

H OVERLOAD RELAY

J CONTACTOR

K CORE DOOR

L MOTOR

M MOTOR MOUNT

N BLOWER

P MOTOR SHEAVE

R BELT

S BLOWER SHEAVE
T INTAKE HOOD

U EXHAUST HOOD

A

B

C

G

D

H

E

J

F

K

T

U

Operation

Principal of Operation

The HE3XRT has one basic purpose: to exhaust air from a structure 

and bring in fresh air from outside, while transferring heating or 

cooling energy from the exhaust air to the fresh air.

The HE3XRT is a very simple device, and will accomplish this 

purpose as long as the blowers for both airstreams are able to 

move air through the energy-exchange core.

Checking that Unit is Operating

Air Flow

Airflow should be occurring in both airstreams. Sometimes the easiest 

place to confirm that air is moving is at the weatherhoods.  

If  exact  airflow  is  critical,  it  may  be  desirable  to  permanently 

install flow measuring stations and manometers in the ductwork 

connected to the unit. These also can be used to determine when 

filters should be cleaned or changed.

Use Static Taps in Doors to Measure Airflow Rates

See “Cross-Core Static Drop” in MEASURING AIRFLOW table. These 

may be used to directly measure airflow in the unit.

Energy Exchange

Precise determination of installed sensible energy exchange 

effectiveness requires careful measurement of temperatures and air 

flows in all four air streams, and in practice is somewhat difficult.

It is possible to confirm that energy is being exchanged simply by 

feeling the ducts. If the Fresh Air duct from the unit into the room 

is closer to room temperature than to the outside temperature, 

energy is being recovered.

Operating Controls

A wide variety of control schemes may be selected by the 

engineer, installer, or owner to meet the ventilation needs of 

the facility. These may include timer clocks, occupancy sensors, 

dehumidistats (for cool-weather operation), carbon dioxide 

sensors, and others. DDC systems may also control the unit. Most 

control schemes will operate the unit only when needed.

Continuous Operation

Continuous operation is acceptable in virtually all conditions.  

Unit will not be damaged by continuous operation as long as 

air  flow  occurs.  Blower  motors  may  overheat  if  filters  become 

completely blocked due to lack of maintenance. Motors are 

thermally protected. With continuous operation, some external 

frosting may occur in very cold weather (see below).

Operation in Extreme Cold Weather

Unit is capable of operating at outside temperatures down to 

-10°F, with indoor humidities below 40%, without any internal 

frosting. Unit can operate at more severe conditions occasionally 

with little or no impact on its performance. At lower humidities, 

it can operate at lower outside temperatures without freezing 

the energy-exchange core.

Summary of Contents for HE3XRTF

Page 1: ...unit to the building 7 Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this e...

Page 2: ...should be at least 10 away from any exhaust such as dryer vents chimneys furnace and water heater exhausts or other sources of contamination or carbon monoxide Do not locate the fresh air inlet where...

Page 3: ...rformance of the HE3XRT Unit In most cases the job engineer will specify flow rates and ESP requirements The blower motors will also be specified to provide the required performance See unit specifica...

Page 4: ...irectly measure airflow in the unit Energy Exchange Precise determination of installed sensible energy exchange effectiveness requires careful measurement of temperatures and air flows in all four air...

Page 5: ...T CONTROL A STANDARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM...

Page 6: ...und from the unit itself The outlet ducts can be significant sources of radiated sound as well The FA duct should be insulated for sound control This insulation should start at the unit At a minimum t...

Page 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 10: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 11: ...put using the conversion chart NOTE Be sure to replace cap into pressure port when air flow measuring is completed ONLY RTH RTF RA OA FA RTV RTF ONLY RTV RTR ONLY RA RTH RTR FA ONLY FRONT VIEW E box P...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: