background image

HE3XRT               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134773_005                      HE3XRTMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 11

Measuring Airflow

Equipment Required

•  A magnehelic gauge or other device capable of measuring 0 

to 1.5 in. water of differential pressure.

•  2 pieces of natural rubber latex tubing, 1/8” ID, 1/16” Wall 

works the best. NOTE: Be sure to remove cap from pressure 

port before inserting tubing. Insure tubing is well seated 

in pressure ports. NOTE: The tubing should extend in the 

pressure port approx. 1 inch.

Cross Core Static Pressure Measurement Instructions

•  The individual differential static pressures (DSP) can be 

measured using the installed pressure ports located in the 

front of the units core access doors. NOTE: These ports 

have been carefully located on the unit as to give you the 

most accurate airflow measurement. NOTE: Do not relocate 

pressure ports. 

•  To read SCFM of Fresh Air (FA) install the “high” pressure side 

(+) of your measuring device to the Outside Air (OA) port and 

the “low” pressure side (-) to the Fresh Air (FA) port.

•  To read SCFM of Room Air (RA) install the “high” pressure 

side (+) of your measuring device to the Room Air (RA) port 

and the “low” pressure side (-) to the Exhaust Air (EA) port.

•  Use the reading displayed on your measurement device to 

cross reference the CFM output using the conversion chart. 

NOTE: Be sure to replace cap into pressure port when air 

flow measuring is completed.

ONLY

RTH, RTF

RA

OA

FA

RTV, RTF

ONLY

RTV, RTR

ONLY

RA

RTH, RTR

FA

ONLY

FRONT

VIEW

E-box

Pressure Taps (4)

EA

Differential Static Across Core DSP vs. CFM

HE3XR

T

DSP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00

Fresh Air

 (FA)

CFM 830 1250 1670 2080 2500 2920 3330 3750 4160

Room Air

 (RA)

CFM 720 1080 1440 1800 2150 2510 2870 3230 3590

HE3XRT Airflow Performance

Motor 

HP

Blower 

RPM

Turns 

Open

External Static Pressure (in. w.g.)

0.00

0.25

0.50

0.75

1.00

1.25

1.50

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

2

1207

4

2130

1.0

1940

0.8

1695

0.6

1340

0.4

1347

2

2380

1.4

2210

1.2

2005

1.0

1725

0.8

1365

0.5

1488

0

2630

1.9

2470

1.6

2300

1.4

2100

1.2

1800

0.9

1435

0.7

820

0.4

(a)

1533

3

2790

2.5

2660

2.3

2500

2.1

2290

1.8

2040

1.6

1765

1.3

1265

1.0

1597

2

2905

2.8

2785

2.6

2630

2.4

2340

2.1

2200

1.9

1955

1.6

1640

1.3

1661

0.5

2810

3.0

2760

2.7

2585

2.5

2365

2.2

2140

1.9

1890

1.6

1692

0

2820

2.9

2665

2.7

2450

2.4

2220

2.1

1980

1.8

5

1686

3

3110

3.5

3000

3.2

2890

3.0

2730

2.7

2520

2.4

2295

2.1

2000

1.8

1764

1.5

3255

4.0

3150

3.7

3045

3.5

2905

3.2

2720

2.9

2520

2.5

2270

2.2

1843

0

3300

4.2

3200

4.0

3075

3.7

2910

3.4

2715

3.0

2500

2.7

(a) Sheaves for 3HP motors can be adjusted from 1688 RPMs at 0 turns to 1400 RPM at 4.5 turns. Operating range shown is best for motor efficiency.

(b) Sheaves for 5HP motors can be adjusted from 1843 RPMs at 0 turns to 1503 RPM at 6.5 turns. However, motor efficiency drops at lower loads.

Summary of Contents for HE3XRTF

Page 1: ...unit to the building 7 Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this e...

Page 2: ...should be at least 10 away from any exhaust such as dryer vents chimneys furnace and water heater exhausts or other sources of contamination or carbon monoxide Do not locate the fresh air inlet where...

Page 3: ...rformance of the HE3XRT Unit In most cases the job engineer will specify flow rates and ESP requirements The blower motors will also be specified to provide the required performance See unit specifica...

Page 4: ...irectly measure airflow in the unit Energy Exchange Precise determination of installed sensible energy exchange effectiveness requires careful measurement of temperatures and air flows in all four air...

Page 5: ...T CONTROL A STANDARD UNIT CONTROL WIRING V ONBOARD VFD BOTH AIRSTREAMS F ONBOARD VFD FA AIRSTREAM E ONBOARD VFD EA AIRSTREAM DAMPERS NO DAMPERS STANDARD D DAMPERS BOTH AIRSTREAMS E DAMPER EA AIRSTREAM...

Page 6: ...und from the unit itself The outlet ducts can be significant sources of radiated sound as well The FA duct should be insulated for sound control This insulation should start at the unit At a minimum t...

Page 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manua...

Page 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTORY...

Page 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as BA...

Page 10: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 11: ...put using the conversion chart NOTE Be sure to replace cap into pressure port when air flow measuring is completed ONLY RTH RTF RA OA FA RTV RTF ONLY RTV RTR ONLY RA RTH RTR FA ONLY FRONT VIEW E box P...

Page 12: ...unds 3 HP BLOWER 4 pounds 5 HP BLOWER 5 pounds GENERAL CLEANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper le...

Reviews: