Page 5

HE3XINV Airflow Performance

Motor 

HP

Blower 

RPM

Turns 

Open

External Static Pressure (in. w.g.)

0.00

0.25

0.50

0.75

1.00

1.25

1.50

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

2

1195

4

2185

0.8

2000

0.7

1725

0.5

1210

0.4

1355

2

2440

1.1

2270

0.9

2060

0.8

1715

0.6

1210

0.5

1476

0

2700

1.5

2550

1.3

2380

1.2

2150

1.0

1750

0.8

1300

0.6

(a)

1536

2.5

2810

2.1

2700

2.1

2560

1.9

2370

1.8

2140

1.6

1840

1.5

1420

1.1

1632

1.5

2985

2.5

2880

2.4

2760

2.3

2590

2.2

2400

2.0

2145

1.8

1855

1.6

1696

0.5

3100

2.8

3000

2.7

2900

2.7

2735

2.5

2505

2.3

2335

2.1

2065

1.9

1728

0

3160

3.0

3055

2.9

2960

2.8

2800

2.6

2635

2.5

2425

2.3

2165

2.1

(b)

1749

2

3300

3.3

3200

3.1

3020

2.8

2860

2.6

2660

2.3

2440

2.1

2200

1.8

1801

1

3300

3.4

3140

3.1

2980

2.8

2800

2.6

2585

2.8

2350

2.1

1853

0

3245

3.4

2920

3.1

2920

2.9

2715

2.6

2500

2.4

(a) Sheaves for 3HP motors can be adjusted from 1728 RPMs at 0 turns to 1420 RPM at 4.5 turns. Operating range shown is best for motor efficiency. 

(b) Sheaves for 5HP motors can be adjusted from 1853 RPMs at 0 turns to 1515 RPM at 6.5 turns. However, motor efficiency drops at lower loads.

Operation

Principal of Operation

The HE3XINV has one basic purpose: to exhaust air from a 

structure and bring in fresh air from outside, while transferring 

heating or cooling energy from the exhaust air to the fresh air.

The HE3XINV is a very simple device, and will accomplish this 

purpose as long as the blowers for both airstreams are able to 

move air through the energy-exchange core.

Checking that Unit is Operating

Airflow

Airflow should be occurring in both airstreams. Sometimes the easiest 

place to confirm that air is moving is at the external wall caps.  

If  exact  airflow  is  critical,  it  may  be  desirable  to  permanently 

install flow measuring stations and manometers. These also can be 

used to determine when filters should be cleaned or changed.

Use Static Taps in Doors to Measure Airflow Rates

See “Cross-Core Static Drop” in MEASURING AIRFLOW table. These 

may be used to directly measure airflow in the unit.

Energy Exchange

Precise determination of installed sensible energy exchange 

effectiveness requires careful measurement of temperatures and 

airflows in all four airstreams, and in practice is somewhat difficult.

It is possible to confirm that energy is being exchanged simply by 

feeling the ducts. If the Fresh Air duct from the unit into the room 

is closer to room temperature than to the outside temperature, 

energy is being recovered.

Operating Controls

A wide variety of control schemes may be selected by the 

engineer, installer, or owner to meet the ventilation needs of 

the facility. These may include timer clocks, occupancy sensors, 

dehumidistats (for cool-weather operation), carbon dioxide 

sensors, and others. DDC systems may also control the unit with 

external control by other. Most control schemes will operate the 

unit only when needed.

Continuous Operation

Continuous operation is acceptable in virtually all conditions.  

Unit will not be damaged by continuous operation as long as 

air  flow  occurs.  Blower  motors  may  overheat  if  filters  become 

completely blocked due to lack of maintenance. Motors are 

thermally protected. With continuous operation, some external 

frosting may occur in very cold weather (see below).

Operation in Extreme Cold Weather

Unit is capable of operating at outside temperatures down to 

-10°F,  with  indoor  humidities  below  40%,  without  any  internal 

frosting. Unit can operate at more severe conditions occasionally 

with little or no impact on its performance. At lower humidities, 

it can operate at lower outside temperatures without freezing 

the energy-exchange core.

Some condensation or even frost may form on the outside or 

drip off of the case during very cold conditions, particularly if 

the unit runs continuously. Exterior condensation during extreme 

conditions can be reduced or prevented by periodically cycling 

the unit off for several minutes to allow the case to warm up.

Summary of Contents for HE3XINV

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...to inside EA Exhaust Air to outside NOTE Airstreams always cross in the energy exchange core Duct Connections as Labeled Alternate Duct Connections RA EA FA OA RA EA FA OA The fresh air inlet should...

Page 3: ...ive or negative pressure in the building is desired RenewAire heat recovery ventilators can generally operate with a flow imbalance of up to 20 without appreciable loss in heat recovery efficiency How...

Page 4: ...IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2 3 4 5 6 7 8...

Page 5: ...ns and manometers These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow Rates See Cross Core Static Drop in MEASURING AIRFLOW table...

Page 6: ...locate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port To read SCFM of...

Page 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manu...

Page 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTOR...

Page 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 10: ...Connect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFI...

Page 11: ...34772_006 HE3XINVMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 HE3XINV Replacement Parts A CORES B FILTERS C DOOR D DRAW LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...