Control Wiring Schematics

NOTE: 

The simplified schematics below show only the relevant 

portions of the low-voltage control circuit in the ERV unit and 

representational external control approaches.  See the complete 

unit schematics elsewhere in this manual.

OBSERVE THESE LIMITS TO WIRE LENGTH AND GAUGE, 

in order to ensure reliable operation of the control system.

Wire Gauge

#22

#20

#18

#16

#14

#12

Circuit Length

100’

150’

250’

400’

700’

1000’

“Circuit Length” is distance from ERV to Control Device.

How to Reset the 24VAC Circuit Breaker

If the transformer is subjected to an excessive load or a short 

circuit, the circuit breaker will trip to prevent the failure of the 

transformer. When it trips the circuit breaker’s button pops up. 

Shut off the primary-side power to the unit, and remove the 

excessive load or the short. The circuit breaker can be reset 

about fifteen seconds after it trips by pressing in the button.

NOTE: 

INSTALLING CONTRACTOR:

If primary-side voltage is 230VAC, move black primary-side lead 

from transformer’s “208V” terminal to the transformer’s terminal 

marked “240V” (“230V” in some units).
Do not move the black primary-side lead that is connected to the 

transformer’s “COM” terminal.

Limits of Power Output

If limits on wire gauge and length are observed, you may connect 

control devices that draw up to 8VA to the blue and red wires. 

More than one device can be connected as long as total steady-

state load does not exceed 8VA.

Control Options

PN 165840_000 HE1XIN P1

C

GND

L1 L2

Contactor

Motor

 (FA)

Motor

 (EA)

Class 2 

Transformer with 

Circuit Breaker

POWER SUPPLY

SINGLE-PHASE 60hz

See Unit Nameplate for VOLTAGE

Fuse Block 

(factory option)

RED

Isolation Relay

BLUE

YEL

YEL

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Connect Blue & First Yellow Leads

Connect Switch between Red & 

Second Yellow Leads

Connect Blue & First Yellow Leads

Connect Control's N.O. Output to 2nd Yellow Lead

External Control is 

powered by 24VAC 

available between the Red 

and Blue leads.

8VA Maximum Load.

UNIT INTERNAL CONTROL WIRING

C

Isolation 

Relay Coil

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Cap Blue and Red Leads when using 

24VAC from external source.

C

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

C

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT CONTROL WIRING SHOWN

SHOWN IN CONTROL OPTIONS AT LEFT

UNIT WIRING

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

AN EXTERNAL CONTROL DEVICE USING 

UNIT'S 24VAC POWER SUPPLY

24VAC FROM AN EXTERNAL SOURCE

Isolation 

Relay Coil

Isolation 

Relay Coil

MPU

B. 

Control Sending 24VAC “On” Signal (from an external 

power source) to ERV: 

Make sure jumper is NOT installed 

between Terminals 2 & 3. Now you safely can apply 24VAC to 

the Terminals 3 & 4 to operate the ERV’s isolation relay.

C. 

Control operating on Unit’s 24VAC Power Supply: 

24VAC 

power is available at the Terminals 1 & 2. CAUTION: external 

control system should not draw more than 8VA. Install jumper 

(provided) between terminals 2 & 3. Connect the switched 

output of the Control to Terminal 4 to operate the ERV’s 

isolation relay.

Control Options

PN 165840_000 HE1XIN P1

C

GND

L1 L2

Contactor

Motor

 (FA)

Motor

 (EA)

Class 2 

Transformer with 

Circuit Breaker

POWER SUPPLY

SINGLE-PHASE 60hz

See Unit Nameplate for VOLTAGE

Fuse Block 

(factory option)

RED

Isolation Relay

BLUE

YEL

YEL

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Connect Blue & First Yellow Leads

Connect Switch between Red & 

Second Yellow Leads

Connect Blue & First Yellow Leads

Connect Control's N.O. Output to 2nd Yellow Lead

External Control is 

powered by 24VAC 

available between the Red 

and Blue leads.

8VA Maximum Load.

UNIT INTERNAL CONTROL WIRING

C

Isolation 

Relay Coil

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Cap Blue and Red Leads when using 

24VAC from external source.

C

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

C

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT CONTROL WIRING SHOWN

SHOWN IN CONTROL OPTIONS AT LEFT

UNIT WIRING

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

AN EXTERNAL CONTROL DEVICE USING 

UNIT'S 24VAC POWER SUPPLY

24VAC FROM AN EXTERNAL SOURCE

Isolation 

Relay Coil

Isolation 

Relay Coil

MPU

Control Options

PN 165840_000 HE1XIN P1

C

GND

L1 L2

Contactor

Motor

 (FA)

Motor

 (EA)

Class 2 

Transformer with 

Circuit Breaker

POWER SUPPLY

SINGLE-PHASE 60hz

See Unit Nameplate for VOLTAGE

Fuse Block 

(factory option)

RED

Isolation Relay

BLUE

YEL

YEL

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Connect Blue & First Yellow Leads

Connect Switch between Red & 

Second Yellow Leads

Connect Blue & First Yellow Leads

Connect Control's N.O. Output to 2nd Yellow Lead

External Control is 

powered by 24VAC 

available between the Red 

and Blue leads.

8VA Maximum Load.

UNIT INTERNAL CONTROL WIRING

C

Isolation 

Relay Coil

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

Cap Blue and Red Leads when using 

24VAC from external source.

C

RED

BLUE

YEL

YEL

Unit 24VAC 

Power Supply

C

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

UNIT CONTROL WIRING SHOWN

SHOWN IN CONTROL OPTIONS AT LEFT

UNIT WIRING

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

AN EXTERNAL CONTROL DEVICE USING 

UNIT'S 24VAC POWER SUPPLY

24VAC FROM AN EXTERNAL SOURCE

Isolation 

Relay Coil

Isolation 

Relay Coil

MPU

This ERV is provided with a Class II 24VAC power supply system that 

operates the unit’s contactor(s) for EV450 and HE1X. The ERV’s 

24VAC Power Supply can also be used to power the externally-

installed controls system: up to 8VA of power is available.

The unit’s power supply system includes isolation relay(s) so you 

can use external controls whose contact ratings are as low as 50mA 

(1.2VA). Also, it is possible to operate the isolation relays with 24VAC 

power from an external source (with proper wiring connections).

A built-in circuit-breaker prevents damage to the transformer and other 

low-voltage components in the event of a short-circuit or overload. In 

extreme cases, the transformer itself is designed to fail safely.

24VAC Power Supply 

Provided with this ERV Unit

1.  Connect only to components intended for use with 24VAC 

power.

2.  Do not undersize the low-voltage wires connected to 

this device. Observe the wire length and gauge limits 

indicated in this manual.

3.  Do not overload this unit’s 24VAC power supply system. 

Confirm that the power requirements of devices you connect 

to this power supply system do not exceed 8VA in total.

4.  If an external source of 24VAC power is used to control 

the unit, consult the wiring schematics and connect the 

external power only to the specified terminals in order 

to avoid damaging the unit or external controls. Connect 

only CLASS II power to the control terminals of this unit.

5.  Unit is not equipped to receive analog signals (such as 

1-10vdc or 4-20mA).

6.  Unit is not equipped to communicate directly with 

Building Management Systems (such as BACNET, 

LONWORKS, etc.). However, the unit can be controlled 

by powered or non-powered contacts operated by any 

kind of control system.

Specifications 

• 

Nominal Output Voltage under load:     24VAC

• 

Typical Output Voltage at no load: 

29-31V

• 

Minimum contact rating

       for connected control device:   

(50mA (1.2VA)

• 

Circuit Breaker Trip Point: 

 

3A

Make sure the control provides no voltage or current at its 

output terminals.

Supply only 24VAC (not VDC) from a Class II Power Source.

Be careful if the external control system provides 24VAC 

power at its control output: make sure blue and red leads are 

separately capped and not connected to any other wires.

A. 

Single 2-wire Control:

 Use schematic below if the control 

requires no power to operate and acts like a simple on/

off switch. 

The control must not supply any power to the 

ERV unit. 

Install jumper (provided) between terminals 2 & 3. 

Connect the control’s contacts to terminals 1 & 4 to operate 

the ERV’s isolation Relay. 

 

Control on separate Power Supply, no power present at 

Control Output:

 Wire as shown for the Single 2-wire control.

Summary of Contents for EV450-RT ECM

Page 1: ...tallation must comply with all applicable building health and safety code requirements 5 This unit must be grounded 6 Danger of severe injury to bystanders and damage to unit or property if high winds...

Page 2: ...e optional roof adapter at least one of the ducts is outside and must be weatherized Any weatherized duct must be thermally insulated to prevent condensation on the inside or outside of the duct The d...

Page 3: ...lation are the Responsibility of the Electrical Contractor Before bringing power to the unit check unit nameplate to confirm it matches the voltage and phase of the power you are supplying Remember th...

Page 4: ...ire com Page 4 EV450RT Dimensions 12 1 8 2 5 8 11 3 4 5 1 2 2 3 4 8 3 4 4 1 2 10 Single Phase 8 1 4 Three Phase TOP VIEW Door Removed EA OA Electrical Box FA FILTERS RA 37 1 2 1 5 3 4 3 1 8 6 12 3 8 4...

Page 5: ...n_Feb14 indd Revised 02 2014 www renewaire com Page 5 EV450RT Replacement Parts A CORE B FILTERS C DOOR ASSEMBLY D DRAW LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H CIRCUIT BREAKER J CO...

Page 6: ...Units openings must be cut into RTU Duct openings to be field cut into adapter Opening location and size is flexible For horizontal connection of either the Fresh Air duct or the Return Air duct stack...

Page 7: ...uired by code to secure the field wiring Electrical Options are identified on the Unit Label located near electrical box on the outside of the unit Find the complete Unit Model Number in the lower lef...

Page 8: ...UNIT INTERNAL CONTROL WIRING SIMPLIFIED UNIT INTERNAL CONTROL WIRING SIMPLIFIED SH A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY AN EXTERNAL CONTROL DEVICE USING UNIT S 24VAC POWER...

Page 9: ...o continuing product development specifications are subject to change without notice 2014 RenewAire LLC 138060_009 EV450RTMan_Feb14 indd Revised 02 2014 www renewaire com Page 9 THIS PAGE LEFT INTENTI...

Page 10: ...o continuing product development specifications are subject to change without notice 2014 RenewAire LLC 138060_009 EV450RTMan_Feb14 indd Revised 02 2014 www renewaire com Page 10 THIS PAGE LEFT INTENT...

Page 11: ...o continuing product development specifications are subject to change without notice 2014 RenewAire LLC 138060_009 EV450RTMan_Feb14 indd Revised 02 2014 www renewaire com Page 11 THIS PAGE LEFT INTENT...

Page 12: ...ANING AND INSPECTION Perform general cleaning and inspection when changing filters Remove dust from blower wheels periodically Remove paper leaves etc from inlet and outlet screens Inspect for insect...

Reviews: