13
1.800.627.4499
EV-Series Premium
ERV
www.renewaire.com (800) 627- 4499
NOTE: For the
setup in Figure
2.4.3, the furnace
blower must be op-
erated any time the ERV is
operated. Use furnace fan
“on” continuous low speed
or optional FM control to
cycle furnace fan on ERV.
FIGURE 2.4.3 FURNACE RETURN AIR BACK INTO RETURN AIR
www.renewaire.com (800) 627- 4499
FIGURE 2.4.2 SEPARATE RETURN AIR AND FRESH AIR SUPPLY
NOTE: ERV blower
may be operated
independently from
furnace blower.
*Use caution to introduce
FA at low velocity and
where good mixing will oc-
cur to minimize discomfort
from drafts
www.renewaire.com (800) 627- 4499
NOTE: ERV blower
may be operated
separate from
furnace blower.
FIGURE 2.4.4 FURNACE RETURN AIR BACK INTO SUPPLY AIR
COMPONENT DESCRIPTION
2.5 ENTHALPIC CORE
Each EV Premium has a static-plate, cross-flow core separates the outgoing, polluted indoor
airstream from the incoming fresh airstream—while simultaneously transferring total energy
(heat and water vapor) between the two. Airstreams do not mix, and pollutants are not
transferred across partition plates.
NOTE: The cores
used in all ERVs
are static plate
enthalpic cores. They are
commonly referred to in
this manual as “cores.”