09

10

RS-485  interfaces  are  used  for  EzConverter  and  EzMeter  communication.  The  cable  length  should  not  exceed  800m. For

 

the 

connection methods of RS-485 please refer to chapter 4.5, chapter 4.6. 

Please follow below steps to implement RS-485 connection of inverter side: 

● 

Remove RS-485 waterproof assembly from inverter.

● 

Disconnect screw cap from insulator.

● 

Disconnect waterproof ring from insulator.

● 

Put the cable through the components in this order: screw cap, waterproof ring, insulator, RS-485 cover. Refer to Figure 4.4-1.

● 

Put cable cores insert into the corresponding slots and compress the crystal head by professional tool, then screw down screw cap 

slight. Refer to Figure 4.4-1. 

● 

Put crystal head insert into the corresponding inner slots of inverter.

● 

Fasten RS-485 waterproof assembly to inverter.

● 

Screw down screw cap again.

 

4.4 RS-485 Connection

Figure

 

4

.

3

-

4

Figure

 

4

.

3

-

5

Cable

 

core

 

section

 

after

 

crimp

 

----

red

 

cable

 

----

black

 

cable

 

Positive
terminal

Negative
terminal

Figure

 

4

.

3

-

6

Figure

 

4

.

3

-

7

Hexagon

  

head

 

screw

Pan

 

head

 

screw

4.5 EzMeter Connection

EzMeter  can  detect  the  current  magnitude  and  direction,  to  control  the  working  condition  of  inverter.  Inverter  and  EzMeter 

communication via RS-485, The cable length should not exceed 800m.

For

 

the connection method of single phase EzMeter refer to Figure 4.5-1.

Cable

Waterproof

 

ring

RS-485

 

cover

Crystal

 

head

Screw

 

cap

Insulator

Figure

 

4

.

4

-

1

PIN

1

2

3

4

5

6

7

8

Color

Orange/white

Orange

Green white

/

Blue

Blue white

/

Green

Brown white

/

Brown

RS-485

 

waterproof

 

assembly

RESERVED

RX RS485B

_

RX_RS485A

TX RS485B

_

TX RS485A

_

Function

RESERVED

RESERVED

RESERVED

Load

PIN

1

2

3

4

5

6

7

8

RESERVED

RX RS485B

_

RX_RS485A

TX RS485B

_

TX RS485A

_

Function

Color

Orange white

/

Orange

Green white

/

Blue

Blue white

/

Green

Brown white

/

Brown

RESERVED

RESERVED

RESERVED

Breaker

 

Connection

 

Illustration

 

of

 

Single

 

Phase

 

System

 

T568B

Grid

Figure

 

4

.

5

-

1

EzMeter

If

 

the light is flashing, the connection is ok.

Breaker

RESERVED

Function

Color

Orange/white

Orange

Green white

/

Blue

Blue white

/

Green

Brown white

/

Brown

RESERVED

RESERVED

RESERVED

Summary of Contents for Replus 3648ME

Page 1: ...rned off and disconnected to ensure safety in any installation operation The package product should be handled carefully and never be tipped over or slung 2 2 Safety Installation maintenance and conne...

Page 2: ...n head screw 8 Flat head screw 5 Max 15 than the following value In consideration of heat dissipation and convenient dismantlement the minimum clearances around the inverter should be no less Upward 3...

Page 3: ...ver and AC terminal Refer to Figure 4 1 2 7 Compress the terminal head by professional tool and screw down screw cap slight Refer to Figure 4 1 3 Figure 4 1 4 8 Insert AC terminals into the correspond...

Page 4: ...breaker between inverter and battery 3 Disconnect screw cap from insulator 4 Disconnect waterproof ring from insulator 5 Put the cable through the components in this order screw cap waterproof ring i...

Page 5: ...e terminal Negative terminal Figure 4 3 6 Figure 4 3 7 Hexagon head screw Pan head screw 4 5 EzMeter Connection EzMeter can detect the current magnitude and direction to control the working condition...

Page 6: ...munication connects to EzConverter via CAN interface if lithium battery communication protocol is CAN Refer to Figure 4 6 2 Lithium battery communication connects to EzConverter via RS 232 interface i...

Page 7: ...8 1 Figure 4 8 1 Open USB cover Touch switch 5 LED Lights Illustration 6 EzManage Operation Illustration Hybrid Series inverter has no LCD screen it can be controlled via mobile device with the APP so...

Page 8: ...me charge is preferred Battery Selection Advanced Settings Feeding To Grid When the switch is yes excess energy of PV can feed to grid Shadow Scan When switch is on it can resolve the multiple wave pr...

Page 9: ...ssfully created Please enter the registered user name and password when you created the solar station 7 Work Modes Hybrid series inverters have the following main work modes based on different conditi...

Page 10: ...y Communication Fail Battery Output Short 8 Error Messages 9 Technical Parameters Model Category SUNCLIX MC4 Optional Replus 5048ME 5400 580 125 550 125 15 15 20 2 2 can parallel Lead acid or Li Ion 4...

Page 11: ...installation Examples are appliances portable tools and other plug connected equipment Category III applies to fixed equipment downstream of and including the main distribution board Examples are swi...

Reviews: