background image

Prior to each commissioning or as 
required, the air inlet and outlet 
grilles must be checked for clog-
ging.

The units operate via an integrated 
hygrostat set to 60% relative hu-
midity (standard value for swim-
ming baths and indoor swimming 
pools). The unit does not start at 
room air conditions below 60% 
relative humidity. If the relative 
humidity is above 60%, the unit 
automatically starts the dehumidi-
fication process.

The front housing panel can be 
removed to make any changes to 
the hygrostat setting. 
The hygrostat is located next to 
the evaporator below the com-
pressor housing.
Turning the control knob clockwise 

reduces the humidity

, turning an-

ticlockwise 

increases the humidity

.

An external hygrostat (accessory) 
can be fitted if required.
Connection option, see under 
“Electrical wiring diagram”.

In order to prevent compressor 
damage, the units are provided 
with reclosing protection, which 
prevents immediate reconnection 
of the compressor after disconnec-
tion

The compressor initially switches 
on again after a delay of about 30 
seconds!

Commissioning

NOTE

If the unit is switched on or 
off via a main switch, all LEDs 
successively show green and 
the triangle red. 

LED display

The units are provided with an 
electronic control. The following 
functions are controlled, monitored 
and displayed:

   Safety

   Monitoring

   On/off

The LED display is located on the 
side of the unit. 

The LED shows constant 
„green“ when the unit is 
connected to the supply. 
 
The LED shows constant 
„green“ when the com-
pressor is operating and the 
unit is dehumidifying.

This LED has no function 
for dehumidification.

Symbol legend

A „green“ flashing drop symbol 
and a constant „green“ lightning 
symbol indicate that the unit is 
functioning, but has been switched 
off by the condenser sensor (over-

nsor (over-

heating).

A constant „green“ lightning 
symbol indicates that the supply is 
connected to the unit. 
Alternating „green“ and „red“ 
flashing LEDs indicate a unit fault 
registered via the condenser sensor 
(overheating). 

If the condenser sensor registers 
an excessive temperature, the 
compressor is switched off and the 
unit remains inoperational for 45 
minutes. 
After lapse of this time, the unit is 
automatically switched on again. 
After switching on again, the 
„red“ triangle symbol no longer 
flashes, the drop symbol continues 
to flash. 

The lightning symbol shows con-
stant „green“.

+

+

+

NOTE

Interruption of unit operation 
for less than 6 minutes com-
pressor operating time will 
force a restart lockout of about 
4 minutes.

NOTE

If the relative humidity is 
below 60%, the unit will not 
start, even when the supply is 
connected.

NOTE

The flashing drop symbol is 

extinguished when the power 

is switched off and on again.

9

Summary of Contents for SLE 40

Page 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO SLE series SLE 40 SLE 60 SLE 80 Pool dehumidifiers Edition GB N11...

Page 2: ......

Page 3: ...Subject to changes errors and typographical errors excepted Dehumidification 4 6 Safety information 6 Unit description 7 Installation 8 Commissioning 9 Care and maintenance 10 Troubleshooting 11 Refri...

Page 4: ...ur es caping from buildings or materials is absorbed by the ambient air This increases their moisture content and ultimately results in corrosion mould rot peeling of paint coat ings and other unwante...

Page 5: ...ncrete 140 190 l m lime sand bricks 180 270 l m The drying out of moist materials e g masonry takes place as fol lows The contained moisture moves from the inside of the material to its surface Evapor...

Page 6: ...essed in a rise of temperature The time necessary for drying normally does not depend only on the unit capacity but is rather determined by the rate at which the material or parts of the build ing rel...

Page 7: ...the cold evaporator heat is extracted from the room air and cooled to below the dew point The water vapour contained in the room air deposits as condensate or frost on the evaporator gills At the con...

Page 8: ...n A solid or flexible drain con nection can be connected The drain hose must always be installed with a minimum gradi ent of 2 to enable the water to drain unhindered from the drip tray Alternatively...

Page 9: ...trol The following functions are controlled monitored and displayed Safety Monitoring On off The LED display is located on the side of the unit The LED shows constant green when the unit is connected...

Page 10: ...eaner whereby the condenser should be thorough ly cleaned If the evaporator gills are heavily fouled they should be cleaned carefully with soapy water Do not use a direct water jet e g high pressure c...

Page 11: ...filter suction If the unit does not start after 45 min utes the following must be checked Check that the fan fans is are op erating Check whether the suction filter is clogged Check that the suction a...

Page 12: ...alve 5 Dry filter 6 Solenoid valve 7 Fan 8 Non return valve Legend 1 Compressor 2 Evaporator 3 Condenser 4 Thermal expansion valve 5 Dry filter 6 Solenoid valve 7 Fan We reserve the right to make dime...

Page 13: ...mper can be connected between terminals 25 and 26 The fan or fans then operate with out any control and monitoring in a continuous mode External hygrostat accessories Remove the both jumper at the ter...

Page 14: ...the right to make dimensional and design changes in the interest of technical advances Diagram of unit SLE 40 80 4 8 25 1 3 12 28 27 20 16 38 2 9 11 15 24 30 35 18 22 7 6 5 Fig REMKO SLE 80 14 REMKO...

Page 15: ...ndensate tray complete 1109149 1109170 1109182 11 Suction filter 1109150 1109171 1109183 12 Front panel 1109151 1109172 1109184 15 Evaporator sensor metal 1109160 1109160 1109111 16 Condenser sensor 1...

Page 16: ...ture 17 Date Signature 18 Date Signature 19 Date Signature 20 Date Signature Remarks Model Serial No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned externally Unit cleaned internally...

Page 17: ...nly high quality materials are used the majority of which are recyclable Make your contribution towards environmental protection by disposing of your old unit in an environmentally friendly manner Onl...

Page 18: ...ktions nderungen die dem technischen Fortschritt dienen bleiben uns vorbehalten A 800 675 315 B 140 130 A A A A 50 90 35 22 30 52 14 Series Dimensions in mm A B SLE 40 950 890 SLE 60 1260 1190 SLE 80...

Page 19: ...ity kg 0 6 0 95 1 6 Max air capacity m3 h 250 500 750 Sound pressure level LpA 1m 2 dB A 47 49 51 Power supply V Hz 230 1 50 Enclosure class IP X4 Max power consumption kW 0 72 1 05 1 65 Max rated pow...

Page 20: ...40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 40 0 5 10 15 20 25 30 35 40 0 0 5 1 1 5 2 2 5 3 3 5 40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 60 Room temperature C Dehumidification...

Page 21: ...21 0 5 10 15 20 25 30 35 40 0 1 2 3 4 5 40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 80 Room temperature C Dehumidification capacity l h...

Page 22: ...22 REMKO SLE series...

Page 23: ...23...

Page 24: ...ct as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is...

Reviews: