2.4 Performance curves for heating and cooling
Heating capacity RVD 354 DC
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
-15
-10
-5
0
7
10
2
1
3
A
[°C]
Fig. 3: Performance curves, heating RVD 354 DC (data for room temperature FK 27 °C/TK 19°C)
A: Outside temperature / 1: COP
2: Heating capacity in kW
3: Power consumption in kW
Outside temperature in °C
-15
-10
-5
0
7
10
Heating capacity in kW
2.46
2.67
2.87
3.36
4.10
4.47
Power consumption in kW
0.80
0.85
0.90
0.95
1.00
1.02
COP
3.09
3.15
3.20
3.56
4.12
4.36
Cooling capacity RVD 354 DC
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
20
25
30
35
40
2
1
3
A
[°C]
Fig. 4: Performance curves, cooling RVD 354 DC (data for room temperature FK 27 °C/TK 19°C)
A: Outside temperature / 1: EER
2: Cooling capacity in kW
3: Power consumption in kW
Outside temperature in °C
20
25
30
35
40
Cooling capacity in kW
4.01
3.85
3.68
3.52
3.34
Power consumption in kW
0.75
0.82
0.88
0.96
1.03
EER
5.35
4.72
4.17
3.66
3.25
13