2
1
3
4
5
Fig. 13: Dismantling the connecting line
1: Connecting line
2: Cable strap
3: Plug connection
4: Condensate hose
5: Cable strap
9.
Unscrew the left-hand union nut with the size
24 open-ended spanner provided. In doing
so, use the second size 21 open-ended
spanner to hold the lower coupling section
NOTICE!
Never twist the the fixed lower section.
NOTICE!
It is possible that residual fluid can leak
out of the the condensate hose.
10.
Screw continuously until the connection is
disconnected.
11.
Unscrew the right-hand union nut with the
size 24 open-ended spanner provided. In
doing so, use the second size 21 open-
ended spanner to hold the upper coupling
NOTICE!
Never twist the the fixed upper section.
12.
Screw continuously until the connection is
disconnected.
NOTICE!
Do not stop screwing in the event that
refrigerant escapes and a slight hissing
sound is heard.
13.
Screw the protective caps provided onto the
14.
Ensure that there is a wall opening available
of Ø 60 mm in the event that the connecting
line is to be fed through a wall.
15.
After the placement or mounting of the indoor
unit and outdoor unit is complete, the con-
necting line can be hooked up to the indoor
unit in the opposite order.
16.
After making the connections, check the
quick-release couplings for leaks.
A
B
C
D
Fig. 14: Unscrew the left-hand union nut
A: Hold to prevent turning
B: Tighten
C: Loosen
D: Remove cable strap
15