120
1500
120
120
Installation inside buildings
■
Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(figure 4)
.
■
Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses
(figure 4)
■
Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each
other
(figure 4)
.
Minimum clearances
Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.
ML 226 DC AT
ML 352 DC AT
ML 522 DC AT
A
150 mm
B
700 mm
C
400 mm
D
150 mm
E
200 mm
■
Comply with any regulations
and conditions affecting the
structure of the building.
If necessary, fit acoustic
installation.
Minimum clearances
E
C
B
A
D
Air intake
Air outlet
Warm air
Cold
Fresh air
Light
well
Outdoor component
Warm air
Light
well
Additional
fan
4 Installation inside buildings
Air intake
Air outlet
All values in mm
1700
Mounting points for wall bracket
ML 226-352 DC IT
ML 522 DC IT
920
45
270
65
65
790
270
65
65
45
90
70
70
40
17