Technical data
Series
MD 261
MD 351
Operating mode
Inverter-wall room air conditioner combination for cooling and heating
Nominal cooling output
1)
kW
2.68 (0.82 to 3.41)
3.56 (1.05 to 4.53)
Nominal heating output
2)
kW
2.96 (0.98 to 3.64)
3.86 (1.14 to 4.78)
Energy efficiency class, cooling
1)
A
A
Energy efficiency ratio EER
1)
4,25
3,75
Energy efficiency class, heating
2)
A
A
Coefficient of performance COP
2)
4,42
4,02
Operating range (room volume), approx.
m³
80
110
Refrigerant
R 410A
Voltage supply
V/Hz
230 / 1~ / 50
Nom. electrical power consumption, cooling
1)
kW
0,63 (0,32-1,10)
0,91 (0,41-1,48)
Nom. electrical power consumption, heating
2)
kW
0,67 (0,35-1,15)
0,96 (0,43-1,56)
Electr. nominal power consumption cooling
1)
A
3,00 (1,42-4,87)
4,25 (1,84-6,52)
Electr. nominal power consumption heating
2)
A
3,09 (1,55-5,10)
4,34 (1,92-6,93)
Electr. starting current, max.
A
17
20
Refrigerant connection, injection pipe
Inches
(mm)
1/4 (6,35)
1/4 (6,35)
Refrigerant connection, suction pipe
Inches
(mm)
3/8 (9,52)
1/2 (12,70)
Max. operating pressure
kPa
4200 / 4200
Data specific to
indoor unit
MD 261 IT
MD 351 IT
Adjustment range, room temperature
°C
+17 to +30
Working range
°C
+17 to +32
Air flow rate per stage
m³/h
375/515/650
375/500/675
Noise output per stage
3)
dB(A)
30/35/39
30/37/40
Protection degree
IP
X0
Condensation connection
mm
16
Dimensions Height
mm
280
280
Width
mm
815
815
Depth
mm
215
215
Weight
kg
10,0
10,0
Data specific to
outdoor component
MD 261 AT
MD 351 AT
Working range, cooling
°C
-15 to +50
Working range, heating
°C
-15 to +34
Air flow rate, max.
m³/h
1900
Protection degree
IP
24
Noise output max.
3)
dB(A)
49
50
Refrigerant, basic quantity
kg
1,23
1,23
Refrigerant, additional quantity > 5 m
g/m
30
30
Refrigerant pipe, max. length
m
15
15
Refrigerant pipe, max. length
m
10
10
Dimensions Height
mm
590
590
Width
mm
820
820
Depth
mm
290
290
Weight
kg
41,0
41,0
Serial number
757...
758...
Computerised part no.
1631260
1631350
1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air volume, 5m pipe length
2) Air inlet temperature TK 20°C, outdoor temperature TK 7°C, FK 6°C, max. air volume, 5m pipe length
3) Distance 1 m free air
REMKO MD
30
Summary of Contents for MD 261
Page 2: ......
Page 31: ...Notes 31...