8
REMKO HTL 400
■
With increased induction
temperature or resistance at
the device outlet, it is possible
that the forced air oil burner is
switched off briefly by the tem-
perature monitor (TW).
After reduction of the tempera-
ture the burner will fire up
again automatically!
■
In the case of cycle intervals
that are too short , the length
of the hot air ducting should be
checked.
■
To prevent heat
accumulation, sharp edged
bends should be avoided in the
hose guidance. Film hoses
must not be twisted
Air Induction
Using appropriate accessories and/
or connections, the device can be
operated in fresh air, blended air or
recycled air mode.
Induction may only be performed
using stable pipes or similar
suitable air ducting.
After being checked for
fulfilment of the local regula-
tions as well as
a check by
authorised, expert personnel,
the forced air burner must be
checked and where appropri-
ate reset in terms of its exhaust
pollution standards.
NOTE
Air Diffusion
The device is fitted with a special
high performance radial fan which
is designed to selectively and
effectively transport the heated air
across long distances.
The diffusion of the air is best per-
formed using pipes or special hot
air or film tubes
■
Use exclusively the hot air
tubes approved by us
(accessories)
■
Attention should be paid to the
flow direction of the tubes!
The internal overlaps on the
seams of the hot air tubes must
point in the direction of the air
flow
■
Secure fastening of the tubes
and pipes at the exhaust and
any connection points used
must be observed
■
Only suitable air diffusers or
those approved by us may be
used
■
When heating closed rooms
using hoses, back pressure must
not be allowed to build up
Before commissioning, the device
should be checked for noticeable
defects of the operating and safety
devices, as well as for proper set-
up and correct electrical
connection.
The following points must be
taken into consideration:
■
It must be assured that the
chimneys can be properly
expelled
■
The device must be
set up stably
■
An adequate supply of inlet air
for combustion must be assured
■
Check that there is no
physical restriction on air intake
and air emission
■
Avoid excessively high or low
pressure in the operation
location
■
Assure and adequate supply
of fuel which also complies to
local requirements
■
Only use clean EL heating oil or
diesel fuel
Do not use biodiesel!
■
It is essential that the suction
pipe at the base of the
tank is fitted with a foot-
operated valve
■
A safety zone of 1.5 m around
the device must be observed,
also for non-flammable objects
Prior to Operation
The hot air tubes may only be
used fully extended and with-
out kinks.
IMPORTANT
Cycle operation of the forced
air burner of less than 5 mins.
should be avoided at all costs.
NOTE
The maximum air intake
temperature may not exceed
30 °C
NOTE
CAUTION
In the event of accumulated
heat, heating operation will
be continuously interrupted by
the STB!