Setting the air throttle 

 

 
The air throttle is opened or shut until the soot has an oil 
free colour, soot „0-1“ and CO

2

-value is 12-14%. When 

setting, note that if there is a considerable excess of air, 
the soot value can increase and oil can also appear in 
the soot. If the flame becomes sooty or burns away 
from the nozzle when the air throttle is fully open, re-
duce the pressure behind the device by means of the 
setting screw. 

Adjustment lever „

blue“

 stage 1 

Adjustment lever „

orange“

 stage 2 

Adjustment lever „

black“

 

solenoid valve stage 2 

Opening scale 

Opening indicator 

1. Closed air throttle

 

If the burner is not in operation 
the servomotor is in position 
„closed air throttle“ (scale: 0). 
This position is fixed by the 
manufacturer and may not be 
changed. 
 

2. Air volume „stage 1“

 

For preheating, start and opera-
tion with „low“ output the servo-
motor rotates to the switch con-
tact of the 

blue

 cam. 

By means of this you get a fixed 
opening angle for the air throttle 
and a constant air volume for the 
first stage. 
For a different air volume you 
can regulate with this lever the 
air volume „stage 1“;  
standard value: approx. 30°. 
 

3. Tripping point „solenoid 2“ 

Place the black lever (solenoid 2) 
approx. 

1/3 of way

 between the 

blue 

and the 

orange

 lever. 

 

4. Air volume „stage 2“ 

When the burner gets the clear-
ance for the second stage, the 
servo motor rotates up to the trip-
ping point  of the 

orange

 cam. 

During its rotation the black lever 
releases the oil-quantity for the 
second stage;  
standard value: approx. 50°. 

1) 

2) 

3) 

4) 

Setting „air volume stage 1“ 

(adjustment lever 

blue

 
Disconnect the 4-pole multi-plug-connector (thermostat 
stage 2 ). Move the adjustment lever „air volume stage 2“ 

orange

 and the adjustment lever „solenoid valve 2“ 

black

 

clockwise until the two control cams are not pressed in or-
der not to impede the setting of the control cam „air vol-
ume 1 

 
Less air „stage 1“:  

 
Set the 

blue

 adjustment lever by moving it anticlockwise to 

decrease the opening angle. If the burner is operating, the 
servomotor turns automatically. 

 
More air - „stage 1“:          

 
Set the 

blue

 adjustment lever by moving it anticlockwise to 

decrease the opening angle. If the burner is operating, the 
servomotor turns automatically. 
 

Switch point „solenoid valve 2“ 

(lever 

black

 
Now move back the adjustment lever for „solenoid valve 2” 
anticlockwise and the switch point „air volume stage 2“ is 
set just behind the switch point „air volume stage 1“ This 
switch point will operate between the settings „air volume 
stage 1“ and „air volume stage 2“  . 

 
Please check that under no circumstances the control 
cam of „solenoid valve 2“ is activated before the con-
trol cam „air volume stage 1“, because this would 
mean that „solenoid valve 2“ opens in the range of „air 
volume 1“ and the burner would operate with exces-
sive deficiency of air.

 

 

Setting air volume „stage 2“ 

(adjustment lever 

orange) 

 
The  adjustment lever for „air volume stage 2“ is now 
turned back anticlockwise and the switch point for „air vol-
ume stage 2“ is determined according to the burner output 
behind the switch point „solenoid valve 2“. Reconnect the 
4-pole multi- plug-connector „thermostat stage 2“. The ser-
vomotor moves via „solenoid valve stage 2“ to position „air 
volume stage 2“. 

 
Less air „stage 2“:  

 
Move the 

orange

 adjustment lever anticlockwise to a 

smaller opening angle. Switch the burner briefly back to 
stage 1. When stage 2 is switched on again, the servo mo-
tor turns to the adjusted volume of air. 

 
More air „stage 2“:

             

 
Move the orange adjustment lever clockwise to a larger 
opening angle. In stage 2 operation the servomotor turns 
automatically.

 

Servomotor LKS 130-2  

 
The servomotor has three switch-functions as well as a 
switch contact for the solenoid valve stage 2. 

G

 

Check that neither the servomotor nor the air throt-
tle make mechanical contact to any point, because 
this could damage the motor! 

Summary of Contents for HTL 150-FB

Page 1: ...REMKO as strong as an ox REMKO HTL 150 250 FB 2 step Automatic Oil Heater Edition GB M02 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...rams 12 Wiring Diagram 13 Oil Burner 14 Operating instructions Make sure to read these instructions carefully before starting using the unit Our guarantee will become void when the unit supplied by us...

Page 4: ...ld resistant down to 20 C below 20 C the de vice switches off when the temperature rises above this temperature it switches on again When the sensor or the capillary tube is damaged or when an overtem...

Page 5: ...d Please use exclusively those hot air hoses accessories which have been approved by our company The inside overlappings on the seams of the hot air hoses must run with the air current direction Make...

Page 6: ...STB If the STB has been released make sure to find the reasons why e g unit could not cool down as the electric power has been cut off temperature of blown out air is too high because of inadequate ai...

Page 7: ...Have the waste gas values of the burner checked regularly by authorised experts For safety reasons we recommend that you con clude a maintenance contract Make sure to store the unit in a dust free an...

Page 8: ...s sale and com missioning Burner maintenance Make sure that the burner is exclusively maintained by authorized experts Make sure to observe the limit values for waste gas losses according to the relev...

Page 9: ...0 3N 50 400 3N 50 power take up max entirely unit W 2 640 4 580 4 810 rated current max entirely unit A 6 1 9 3 9 8 power take up min max fan W 960 1 950 2 700 3 900 2 850 4 100 rated current max fan...

Page 10: ...6 17 18 20 19 21 22 23 11 9 8 46 7 30 29 28 27 26 31 32 33 34 35 36 39 38 40 41 42 43 44 45 25 24 Unit design comb chamber heat exchanger We reserve the right to make modifications in dimensions and c...

Page 11: ...ttom rear 1105389 1105389 1105389 26 bracket fan 1105390 1105391 1105391 27 fan 1105375 1105377 1105380 28 inlet nozzle 1105376 1105378 1105378 29 suction plate 1105392 1105393 1105393 30 plate rear w...

Page 12: ...tactor phase sequence relay K7 Auxiliary relay KX5 6 phase sequence relay KB combined regulator M1 fan motor P1 hour counter RT room thermostat socket S1 operating switch S2 burner reset S3 change ove...

Page 13: ...double socket close to burner S2 burner reset S3 change over switch 1 2 Step SK switch box TW burner temperature monitor WS4 4 pole plug to burner WS7 7 pole plug to burner X3 terminal strip close to...

Page 14: ...ng cross section Loosen socket screw and turn air inlet device into desired posi tion pay attention to the arrows Turn to min reduced burner pressure Turn to max increased burner pressure Secondary ai...

Page 15: ...he setting of the control cam air vol ume 1 Less air stage 1 Set the blue adjustment lever by moving it anticlockwise to decrease the opening angle If the burner is operating the servomotor turns auto...

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: