background image

11 

Cleaning the Filter

 

 
The dehumidifier features an air intake filter to prevent 
damage to the unit and improve the room climate.  

The unit ETF 150 also has a charcoal filter that requires 
replacement when contaminated.  The charcoal filter is 
intended solely to improve the quality of the room air and 
is therefore not required for operation.

 

Check the air filters at least every two weeks and clean 
or replace them according to the instructions to prevent 
loss of performance or device malfunctions. 

8.  

Reinstall the filter frame carefully after cleaning or re-
placing the air intake filter. 

9.   Ensure that the frame is correctly seated and posi-

tioned. 

Maintenance and Service 

 
Regular care and the observation of a number of basic 
rules will ensure the dehumidifier’s long life and reliable 
operation. 

The unit should be inspected and cleaned thoroughly 
after each long period of operation, at a minimum once 
a year. 

All moving parts feature low-maintenance long-life lubri-
cation.  

The complete cooling system is hermetically sealed and 
contains no user-serviceable parts. 

It may only be 

serviced by authorised repair facilities. 

Ensure that the interior and exterior of the unit re-
mains free of dust and other deposits. Clean the unit 
only with a dry or dampened cloth.   

Do not use a water jet!

 

Do not use aggressive cleansers or cleaning prod-
ucts containing solvents. 

Be sure to use suitable cleaning products should the 
unit become extremely dirty. 

Regularly check the  air intake filter / charcoal filter 
(only ETF 150) and the exhaust grille for soiling.  

Clean or replace them as required.

 

4.   Unhook the filter holder at the 

rear (only ETF 150). 

5.   Remove (only ETF 150) the 

charcoal filter and replaced as 
required. 

The charcoal filter insert cannot 
be cleaned. 

Charcoal 
filter 

Filter holder 

Filter frame 
with filters 

6.   Clean the air intake filter in the 

filter frame. 

      - With lukewarm water. 

Dirty side down

 

     -   With a vacuum cleaner. 

Dirty side up. 

7.   Clean heavily contaminated fil-

ters in lukewarm, max. 40°C  
soapy water. 

Rinse with clean water after-
wards. 

The dehumidifier uses environmentally-friendly R134a 
refrigerant which is not hazardous to the ozone layer. 

The refrigerant / oil mixture in the unit must be dis-
posed of in accordance with your local regulations. 

3.   Pull the entire filter frame con-

taining the filters upwards out of 
the unit. 

1.   Shut the unit down by turning the 

knob to the “OFF” position. 

2.   Remove the plug from the plug 

socket. 

The air intake filter must be completely dry and in-
tact before it is replaced to prevent damage to the 
charcoal filter. 

Only ETF 150

 

G

 

The cooling and electrical systems may only be 
serviced by authorised service centres! 

G

 

Important recycling note

 

Cleaning the condenser and vaporizer 

These operations require opening the unit housing and 
should only be performed by authorised service person-
nel. 

Clean the condenser and vaporizer with an air jet, 
vacuum cleaner or a soft brush. Do not use a water 
jet. 

Caution: the blades bend easily! 

Carefully clean the interior surfaces of the unit, con-
densation trap, inner condensation tube with hose 
connector (do not forget plug) as well as the fan 
blades and housing and wipe dry. 

Reinstall all removed components.

 

Test the functions of the unit and perform an electri-
cal safety check! 

Always remove the power plug from the 

plug 

socket when working on the unit! 

G

 

Never operate the unit without the filter frame!  

G

 

Summary of Contents for ETF 100

Page 1: ...REMKO powerful like a bear REMKO ETF 100 150 Mobile Dehumidifier Edition GB M02 Operation Technology Spare Parts ...

Page 2: ......

Page 3: ...without our prior consent Subject to alterations Operating Instructions Contents page Air Dehumidification 4 Safety Instructions 6 Unit Description 7 Installation 8 Starting 8 Discard the Unit 10 Transport Instructions 10 Cleaning the Filter 11 Contents page Maintenance and Service 11 Exploded View 12 Spare Part List 13 In Case of Troubles 14 Technical Data 14 Wiring Diagram 14 Maintenance and Ser...

Page 4: ...r kg of dry air absolute water content 1 m of air weighs approx 1 2 kg at 20 C Depending on the temperature each kg of air can only absorb a defined quantity of water vapour When this quantity has been absorbed the air is saturated and has a relative humidity of 100 By relative air humidity we understand the relation be tween the percentage of water vapour contained in the air at the moment concer...

Page 5: ...On the other hand energy is re leased when gas is liquefied and this energy is called condensation heat The energy rate of evaporation and condensation heat is identical For water this is 2250 kJ kg 4 18 kJ 1kcal This shows that a relatively high energy rate is released through water vapour condensation If the humidity to be condensed is not generated by evaporation within the room but fed from th...

Page 6: ...condensation tank before moving the unit Do not set the unit up near curtains or drapes Maintain a safety distance of at least 50 cm min 50 cm Ensure that the unit is set up at a safe distance from flammable mate rials Ensure that the dehumidifier is sol idly set up on a level surface The unit may only be operated in an upright position Do not attempt to use the unit while lying on its side or in ...

Page 7: ...a tion of the room air through the unit will thus reduce the humidity in the room to the desired relative humidity Depending on the air temperature and relative humidity condensation either drips into the condensation trap continuously or during the periodic defrosting phases From there it passes through the integrated outlet into the condensation tank located below it Condensation can also be rel...

Page 8: ...tall the unit directly near radiators or other heat sources Make sure to keep the room to be dried and dehumidified closed so that air from outside cannot penetrate into it Entering into and going out of the room should be avoided if possible You can obtain better air circulation if you place the unit at a height of approx 1 m Important Hints Make sure that appropriate measures for mainte nance an...

Page 9: ...rol lamp OPERATION in dicates the correct function of the unit BETRIEB OPERATION To open the flap tap the corrugated surfaces The top side will tip downward per mitting you to adjust the air flow direc tion as required Ensure that the air outlet is unob structed and that sensitive objects such as plants are not directly in the path of the air stream Remove the small grille lid to fill the dispense...

Page 10: ...rform these steps in reverse order Remove the plug S from the connector on the rear of the unit S Attach a sufficiently long hose to the connector The condensa tion can now be allowed to flow into a drain for example during unattended continuous opera tion To prevent spillage ensure that the plug is cor rectly positioned G Remove the condensation tank and close the drain A below the condensation t...

Page 11: ...ook the filter holder at the rear only ETF 150 5 Remove only ETF 150 the charcoal filter and replaced as required The charcoal filter insert cannot be cleaned Charcoal filter Filter holder Filter frame with filters 6 Clean the air intake filter in the filter frame With lukewarm water Dirty side down With a vacuum cleaner Dirty side up 7 Clean heavily contaminated fil ters in lukewarm max 40 C soap...

Page 12: ...12 Exploded View We reserve the right to make changes to the design and dimensions in the interest of technical progress ...

Page 13: ...essor complete 1103548 38 Accumulator 1103547 39 Rear panel 1103555 40 Support brace 1103538 41 Solenoid 1103530 42 Fan cover 1103539 43 Dry filter 1103549 44 Control board 1103541 45 Display board 1103542 46 Power board 1103543 47 Transport handle 1103544 No Designation Ref No ETF 150 Ref No 1103502 1103503 1103504 1103505 1103506 1103507 1103508 1103509 1103545 1103501 1103510 1103511 1103512 11...

Page 14: ... than the humidity in the room Unit running no condensation formation Check room temperature The working range of the unit is between 6 C and 32 C Check relative humidity Min 40 Check hygrostat setting and choose a lower setting if required Check air intake filter charcoal filter for contamination Clean or replace as required Check exchanger blades for soiling Lei it clean as required Vaporizer is...

Page 15: ...e 7 Date 8 Date 9 Date 10 Date Signature Signature Signature Signature Signature 11 Date 12 Date 13 Date 14 Date 15 Date Signature Signature Signature Signature Signature 16 Date 17 Date 18 Date 19 Date 20 Date Signature Signature Signature Signature Signature Unit cleaned exterior Unit cleaned interior Condenser cleaned Vaporizer cleaned Fan blades cleaned Dust filter cleaned or replaced Protecti...

Page 16: ...REMKO GmbH Co KG Klima und Wärmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 ...

Reviews: