REMKO CLK 120 Operating And Installation Instructions Download Page 9

9

Exhaust gas ducting

Over 1 metre

Max. 1 metre

In order to avoid the combustion 
chamber being damaged due 
to condensation of moisture 
(condensate) in example 3, 
make sure that the exhaust gas 
ducting is correctly installed with 
a condensate trap as shown in 
example 1.

   Fault-free operation is 

guaranteed if the exhaust gas 
ducting is fitted in a rising 
arrangement and with a vertical 
end pipe

   The exhaust gas routing should 

end at least above the height of 
the eaves but ideally above the 
height of the ridge, in order to 
prevent any counter-pressure 
being caused by poor weather 
conditions (e.g. wind)

   The minimum distance of 0.6 m 

to combustible parts must be 
met

   Exhaust gas ducting parts and 

fastening materials are available 
as accessories

It is also possible to operate the 
units outdoors or in open spaces 
without exhaust ducting.  
However, we recommend fitting 
a 1m exhaust gas duct with a rain 
hood on top (example 2), in order 
to exclude the ingress of rainwater 
and dirt

.

If the units are used for room 
heating then the combustion 
gases must be routed away, to the 
outside if necessary. 

   The exhaust gas ducting must 

be designed so that the thermal 
lift of the exhaust gases is 
guaranteed at all times

 

  The exhaust gas ducting must 

be designed so that no counter-
pressure can be generated

   All parts of the exhaust gas 

ducting must be reliably 
fastened Its diameter must 
not be smaller than the outlet 
nozzle of the unit

Example 1 

Operation with 
extended exhaust 
gas ducting

Condensate trap 
required

Example 2 

Operation without 
extended exhaust 
gas ducting

Max. 1 metre

Example 3 

Impermissible 
layout

Notes for implementing the 1st. 
BImSchV

Units that are not expected to 
be operated for longer than 
3 months in the same location 
are not subject to any approvals 
or monitoring as per the 
1st. BImSchV.

NOTE

After installing an exhaust 
gas system the settings on the 
burner should be adapted to 
suit the new conditions.

CAUTION

There must be no counter 
pressure arising from incorrect 
installation of the exhaust 
gas ducting under any 
circumstances.

!

Summary of Contents for CLK 120

Page 1: ...Operating and installation instructions Edition GB Q04 Read the instructions prior to performing any task CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 REMKO CLK series Automatic oil gas heaters...

Page 2: ......

Page 3: ...prints Safety notes 4 Unit description 5 Specifications for fan assisted heaters 6 Installation instructions 7 Safety device 8 Exhaust gas ducting 9 Before commissioning 10 Commissioning 11 Shutdown 1...

Page 4: ...ces Personnel must not remain in the installation area Appropriate prohibition signs must be displayed at the entrances Portable fuel containers must only be set up and used in observance of the techn...

Page 5: ...ining the temperature of frost sensitive goods Heating ventilating or frost protection of lightweight structures Heating ventilating or frost protection of tents Heating or frost protection in garden...

Page 6: ...he unit or the power supply Precipitation such as rain or snow can be sucked in through the supply air fan For this reason suitable weather protection should be provided When using the units the respe...

Page 7: ...lled in well ventilated spaces and not in living areas or similar recreational areas NOTE The electrical connection for the units must be made at a separate feed point with a residual current device i...

Page 8: ...damaged as well as if an overtemperature of ca 220 C is reached the filling medium will be emptied and the safety device is permanently triggered Resetting is no longer possible The controller is no...

Page 9: ...order to exclude the ingress of rainwater and dirt If the units are used for room heating then the combustion gases must be routed away to the outside if necessary The exhaust gas ducting must be des...

Page 10: ...pieces that may be being used Only suitable air distributors or air distributors approved by ourselves should be used for the air distribution The units should be checked for visible defects on the op...

Page 11: ...t spots forming Membrane hoses must not be twisted Enclosed spaces being heated via hoses must not present any overpressure The forced air burner can be switched off briefly during operation by the te...

Page 12: ...ct the plug 3 of the room thermostat 4 with the thermostat socket 1 on the unit 3 Place the room thermostat 4 at a suitable location in the room The thermostat sensor must not be located directly in t...

Page 13: ...eplace contaminated filter if necessary Check the units for mechanical damage and have defective parts properly replaced Check the fan blades and combustion chamber with heat exchanger for contaminati...

Page 14: ...screw the fuel filter 3 including the fuel lines and take the plug 4 off the burner 5 4 Loosen the 2 lower fastening screws on the burner flange 6 4 Loosen the clamping screw 7 on the burner flange 6...

Page 15: ...then reset the automatic burner 9 Move the operating switch to the II Ventilate position If the supply air fan now starts up the fault may well be in the burner area Forced air burner and power suppl...

Page 16: ...s are processed the majority of which are recyclable You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner Therefore...

Page 17: ...green H2 External burner fault lamp red KL Terminal block M Fan motor RT Thermostat socket S1 Operating switch S2 Reset button burner STB Safety temperature limiter TR Temperature controller TW Temper...

Page 18: ...66 67 68 69 70 71 72 4 11 25 63 27 REMKO oil filter standard up to CLK 70 with oil burner fitted ex works Available as option for all types REMKO Multiflex oil preheating Standard with CLK 120 150 wi...

Page 19: ...Burner housing 1104724 1104724 1104759 1104789 1104789 35 Support foot 1104725 1104725 1104725 1104790 1104790 36 Axle 1104726 1104726 1104760 1104791 1104791 37 Wheel 1101621 1101621 1101621 1108369...

Page 20: ...ta for the required oil nozzle size Air inlet nozzle The required blower pressure can be adjusted with the adjustable air inlet nozzle A in accordance with the combustion chamber resistance and chimne...

Page 21: ...e off sooty smoke or break away with a fully opened air flap reduce the pressure behind the baffle plate with the help of the secondary air setting It may also be necessary to open the air inlet nozzl...

Page 22: ...y by authorised specialists and in accordance with the legal provisions 1st BImSchV A corresponding measurement log should be generated Unit to be maintained only by authorised specialists in accordan...

Page 23: ...0 000 0 000 0 000 0 000 0 000 in Stand By mode elSB kW 0 000 0 000 0 000 0 000 0 000 Pilot flame power requirement Ppilot kW N A N A N A N A N A Thermal efficiency at nominal heating capacity th nom...

Page 24: ...400 500 500 Flue gas connection mm 150 150 150 200 200 Dimensions Length mm 1 450 1 450 1 610 2 100 2 100 Width mm 660 660 730 920 920 Height mm 1 000 1 000 1 120 1 350 1 350 Weight without blower oi...

Page 25: ...25 Notes...

Page 26: ...26 REMKO CLK SERIES...

Page 27: ...27...

Page 28: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews: