REMKO CLK SERIES

Specifications for fan-
assisted heaters

Installation instructions

   The units must not be used 

below ground level, e.g. in 
basements, without suitable gas 
monitoring equipment

   The fuel supply must be 

installed in accordance with 
DIN 4755 for oil-fired fan-
assisted heaters, DVGW Code 
of Practice G 600 for gas-fired 
warm air heaters and TRF for 
liquid gas

   The gas connection/unit 

operation must take place 
exclusively on the basis of the 
accident prevention regulation 
DGUV 79, “Use of liquid gas”, 
as well as the respective local 
construction and fire prevention 
regulations.

The safety regulations of the 
accident prevention and insurance 
associations, the respective 
regional building regulations 
and the combustion appliances 
regulations apply to the operation 
of the units.

   Make sure that there is an 

adequate fresh air supply 
appropriate to the respective 
forced-air burner capacity 
(see name plate)

Outdoor installation

   Operation of the units must 

not present a hazard or 
unreasonable discomfort

   The unit operator must 

ensure that it is impossible 
for unauthorised persons to 
manipulate either the unit or 
the power supply

   Precipitation such as rain or 

snow can be sucked in through 
the supply air fan.  
For this reason suitable weather 
protection should be provided

When using the units the 
respective applicable guidelines 
must always be observed.

   Combustion plant order 

(FeuVo) for the individual 
federal states

   Workplace directives ASR 5

   Workplace regulations 

§§ 5 and 14

   Ordinance for implementation 

of Federal Emissions Control 
Regulations (BImSchG) and the 
subsequently issued legislation 
(ENEG)

Combustion air supply

There is good natural ventilation 
and aeration for example if: 

1. the room volume in m³ is at 
least 30 times the nominal heating 
capacity in kW of all of the units 
operating in the space and if the 
natural change of air is provided 
by windows and doors, or

2. constantly open ventilation 
openings are present for incoming 
and exhaust air in the vicinity of 
the ceiling and floor, whose size 
in m² is at least 0.003 times the 
nominal heating capacity in kW 
of all of the units operating in the 
space.

NOTE

Overpressure and 
underpressure in the 
installation area should be 
avoided as this will inevitably 
lead to combustion-related 
faults.

NOTE

The burner setting must be 
checked after every change of 
location and adapted to the 
new environmental conditions 
and atmospheric conditions if 
necessary.

Summary of Contents for CLK 120

Page 1: ...Operating and installation instructions Edition GB Q04 Read the instructions prior to performing any task CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 REMKO CLK series Automatic oil gas heaters...

Page 2: ......

Page 3: ...prints Safety notes 4 Unit description 5 Specifications for fan assisted heaters 6 Installation instructions 7 Safety device 8 Exhaust gas ducting 9 Before commissioning 10 Commissioning 11 Shutdown 1...

Page 4: ...ces Personnel must not remain in the installation area Appropriate prohibition signs must be displayed at the entrances Portable fuel containers must only be set up and used in observance of the techn...

Page 5: ...ining the temperature of frost sensitive goods Heating ventilating or frost protection of lightweight structures Heating ventilating or frost protection of tents Heating or frost protection in garden...

Page 6: ...he unit or the power supply Precipitation such as rain or snow can be sucked in through the supply air fan For this reason suitable weather protection should be provided When using the units the respe...

Page 7: ...lled in well ventilated spaces and not in living areas or similar recreational areas NOTE The electrical connection for the units must be made at a separate feed point with a residual current device i...

Page 8: ...damaged as well as if an overtemperature of ca 220 C is reached the filling medium will be emptied and the safety device is permanently triggered Resetting is no longer possible The controller is no...

Page 9: ...order to exclude the ingress of rainwater and dirt If the units are used for room heating then the combustion gases must be routed away to the outside if necessary The exhaust gas ducting must be des...

Page 10: ...pieces that may be being used Only suitable air distributors or air distributors approved by ourselves should be used for the air distribution The units should be checked for visible defects on the op...

Page 11: ...t spots forming Membrane hoses must not be twisted Enclosed spaces being heated via hoses must not present any overpressure The forced air burner can be switched off briefly during operation by the te...

Page 12: ...ct the plug 3 of the room thermostat 4 with the thermostat socket 1 on the unit 3 Place the room thermostat 4 at a suitable location in the room The thermostat sensor must not be located directly in t...

Page 13: ...eplace contaminated filter if necessary Check the units for mechanical damage and have defective parts properly replaced Check the fan blades and combustion chamber with heat exchanger for contaminati...

Page 14: ...screw the fuel filter 3 including the fuel lines and take the plug 4 off the burner 5 4 Loosen the 2 lower fastening screws on the burner flange 6 4 Loosen the clamping screw 7 on the burner flange 6...

Page 15: ...then reset the automatic burner 9 Move the operating switch to the II Ventilate position If the supply air fan now starts up the fault may well be in the burner area Forced air burner and power suppl...

Page 16: ...s are processed the majority of which are recyclable You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner Therefore...

Page 17: ...green H2 External burner fault lamp red KL Terminal block M Fan motor RT Thermostat socket S1 Operating switch S2 Reset button burner STB Safety temperature limiter TR Temperature controller TW Temper...

Page 18: ...66 67 68 69 70 71 72 4 11 25 63 27 REMKO oil filter standard up to CLK 70 with oil burner fitted ex works Available as option for all types REMKO Multiflex oil preheating Standard with CLK 120 150 wi...

Page 19: ...Burner housing 1104724 1104724 1104759 1104789 1104789 35 Support foot 1104725 1104725 1104725 1104790 1104790 36 Axle 1104726 1104726 1104760 1104791 1104791 37 Wheel 1101621 1101621 1101621 1108369...

Page 20: ...ta for the required oil nozzle size Air inlet nozzle The required blower pressure can be adjusted with the adjustable air inlet nozzle A in accordance with the combustion chamber resistance and chimne...

Page 21: ...e off sooty smoke or break away with a fully opened air flap reduce the pressure behind the baffle plate with the help of the secondary air setting It may also be necessary to open the air inlet nozzl...

Page 22: ...y by authorised specialists and in accordance with the legal provisions 1st BImSchV A corresponding measurement log should be generated Unit to be maintained only by authorised specialists in accordan...

Page 23: ...0 000 0 000 0 000 0 000 0 000 in Stand By mode elSB kW 0 000 0 000 0 000 0 000 0 000 Pilot flame power requirement Ppilot kW N A N A N A N A N A Thermal efficiency at nominal heating capacity th nom...

Page 24: ...400 500 500 Flue gas connection mm 150 150 150 200 200 Dimensions Length mm 1 450 1 450 1 610 2 100 2 100 Width mm 660 660 730 920 920 Height mm 1 000 1 000 1 120 1 350 1 350 Weight without blower oi...

Page 25: ...25 Notes...

Page 26: ...26 REMKO CLK SERIES...

Page 27: ...27...

Page 28: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews: