Sensor calibration
SEnS
(sensor calibration display)
Stabilised temperature values must
be available for sensor calibration.
In addition, sensor calibration must be
performed at a usual room temperature
of approx. 20°C.
In order to perform correct
temperature calibration, the actual
temperature displayed on the unit and
the temperature at the sensor (to be
measured with a suitable temperature
measuring instrument) must be known.
The difference between these two values
can be set within ±3.0 K limits under
the
SEnS
menu item.
Example:
20.7°C
is shown on the unit display.
The temperature measuring instrument
shows
19.9°C
as the temperature
at the sensor.
– 0.8
must therefore be set under
the SEnS menu item.
Pre-setting
Limit
0.0 K
±3.0 K
NOTE
The accuracy of temperature
recording is dependent on the length
and cross-section of the lines
(see table on page 15).
MO
DI
MI
DO
FR
SA
SO
Key lock
Loc
(key lock)
Key lock prevents the daytime and
nighttime temperatures from being
modified with the rotary buttons.
After removing the key lock, an
interim modified daytime or nighttime
temperature is adopted. The key lock
is deactivated by pressing the PROG key
for 6 seconds.
Active key lock is indicated by the key
symbol.
Pre-setting
Alternatives
oFF
(inactive)
on
(active)