Sensor calibration

SEnS

 (sensor calibration display)

Stabilised temperature values must 
be available for sensor calibration. 
In addition, sensor calibration must be 
performed at a usual room temperature 
of approx. 20°C.
In order to perform correct 
temperature calibration, the actual 
temperature displayed on the unit and 
the temperature at the sensor (to be 
measured with a suitable temperature 
measuring instrument) must be known. 
The difference between these two values 
can be set within ±3.0 K limits under 
the 

SEnS

 menu item.

Example:

 

20.7°C

 is shown on the unit display.

The temperature measuring instrument 
shows 

19.9°C

 as the temperature 

at the sensor.

– 0.8

 must therefore be set under 

the SEnS menu item.

Pre-setting

Limit

0.0 K

±3.0 K

NOTE

The accuracy of temperature 
recording is dependent on the length 
and cross-section of the lines 
(see table on page 15).

     

  

MO

  

DI

   

MI

 

 

DO

 

FR

 

SA

 

SO 

     

 

 

 

 

Key lock

Loc 

 (key lock)

Key lock prevents the daytime and 
nighttime temperatures from being 
modified with the rotary buttons.  
After removing the key lock, an 
interim modified daytime or nighttime 
temperature is adopted. The key lock 
is deactivated by pressing the PROG key 
for 6 seconds.  
Active key lock is indicated by the key 
symbol.

Pre-setting

Alternatives

oFF

(inactive)

on

(active)

     

  

MO

  

DI

   

MI

 

 

DO

 

FR

 

SA

 

SO 

     

 

 

 

 

Summary of Contents for ATR 10

Page 1: ...Operating and installation instructions Edition GB N12 Read the instructions prior to performing any task ATR 10 REMKO ATR Electronic temperature regulation...

Page 2: ......

Page 3: ...tion 14 Customer data 15 Circuit diagram 16 18 Technical data 19 Carefully read this Installation manual prior to commis sioning using the units This operating manual is a translation of the German or...

Page 4: ...ns including any regional regulations Modification of the units and components supplied by REMKO is not permitted and can cause malfunctions Units may not be used in areas where there is an increased...

Page 5: ...the indicators 5 In hourly operation a second indicator is used to display the respective temperature level In Off operating mode no indicator is displayed Display in hourly operation daytime operati...

Page 6: ...unit continues to record the actual temperature however the switch relay for temperature regulation is no longer activated Frost protection is no longer available Depending on the selected units Heati...

Page 7: ...t of the relay The relay is activated for as long as the key combination is pressed Any previously entered individual time program and parameter settings will be lost NOTE Malfunction code In the even...

Page 8: ...with the SET key the clock is started with to the second accuracy After confirming the day the unit returns to the operating mode from which the Set time menu was called MO DI MI DO FR SA SO MO DI MI...

Page 9: ...ed temperature settings for daytime and nighttime are confirmed with the adjustment buttons 1 and 2 After pressing the PROG key with flashing program point number the unit returns to the operating mod...

Page 10: ...right hand half of the display Pressing the PROG key for 3 seconds opens a menu in which the different regulation parameters can be set The parameter is displayed in the left hand half of the display...

Page 11: ...C is shown on the unit display The temperature measuring instrument shows 19 9 C as the temperature at the sensor 0 8 must therefore be set under the SEnS menu item Pre setting Limit 0 0 K 3 0 K NOTE...

Page 12: ...t screen Nighttime temperature Time program diFF control parameter SEns default setting Loc key lock Set time program SET SET SET SET SET PROG 1 sec PROG 3 sec PROG 6 sec PROG SET SET Set time 3 sec S...

Page 13: ...xternal temperature probe must be installed such that it can record the average room temperature Draught and proximity to windows doors and heat sources etc must be avoided NOTE Probe not fitted immed...

Page 14: ...function as expected begin by verifying that it is correctly connected and that there is a power supply Use probe lines in accordance with the requirements and note the maximum line lengths and requi...

Page 15: ...P10 P11 P12 P13 P14 P15 P16 The following tables have been compiled for entering the individual customer data Time program We reserve the right to modify the dimensions and design as part of the ongoi...

Page 16: ...A mains voltage must be permanently available at terminals L and N for the unit to function CAUTION T2 P1 1 S1 PE L N Heat Ventilate release Heat Ventilate selection P2 2 S2 P3 3 S3 N L PE Fault ackn...

Page 17: ...diagram for one GPS unit 363534333231 T2 P1 S1 1 P2 S2 2P3 S3 3 N PE L ATR 10 N PE L A1A2 Wahlschalter auf NC stellen NC NO 1 2 3 4 5 6 1 2 3 4 5 6 3 Set selection switch to NC GPS board 1 GPS Tempera...

Page 18: ...14 11 12 14 11 12 14 11 A2 A1 R2 R3 R4 R1 31 32 33 34 35 36 S3 S2 S1 A2 N PE 31 32 33 34 35 36 X1 X2 PE 12 A1 A2 A1 A2 A1 A2 11 14 12 12 14 11 12 14 11 12 14 11 A2 A1 R2 R3 R4 R1 31 32 33 34 35 36 GPS...

Page 19: ...1 Max permissible load relay switching current 10 4 A 230 V AC Max permissible signal relay switching current 4 2 A 230 V AC the minimum switching current of 10 mA must be met Electrical service life...

Page 20: ...EMKO GmbH Co KG Air conditioning and heating technology Im Seelenkamp 12 D 32791 Lage Postfach 1827 D 32777 Lage Telephone 49 5232 606 0 Fax 49 5232 606 260 E mail info remko de Website www remko de W...

Reviews: