REMKO AT 25 Manual Download Page 7

Starting 

 
Prior to starting, the unit is to be checked to make sure 
that there are no visible defects on the control and 
safety devices, that the unit has been installed correctly 
and that it has been properly connected to the mains. 

A properly trained person is to be charged with the op-
eration and control of the unit. 

Install unit in a stable position. 

Make sure that combustion air is supplied. 

Make sure that the air can be sucked in and be ex-
hausted freely. 

Avoid overpressure and underpressure in the room 
where the unit has been installed. 

Make sure that enough fuel is supplied. 

Fill fuel tank with clean fuel oil EL or diesel with the 
unit switched off. 

Use only appropriate and clean tanks to fill with fuel. 

Fuel filter

 

Prior to commissioning the unit and before 
the tank is filled each time, the main filter (F) 
must be checked for the presence of grime 
or the accumulation of paraffin. 

The main filter is positioning beside the filler. 

Make sure to fill the fuel tank only with the 
tank filter inserted into the filler neck. 

Paraffin accumulation by low outside temperatures 

The supply of sufficient liquid fuel is to be ensured, even 
with low outside temperatures. 

G

 

Paraffin accumulation can occur even at tempera-
tures as low as 5 °C. Appropriate measures must 
be taken to avoid this. 

The built-in tank heating is only active as long as the 
mains plug is connected with a functioning mains 
socket. 

It is not possible to get rid of paraffin discharge 
which is already present using the tank heating.   

The requirement for this is the cleaning of the entire 
fuel system.

 

G

 

The unit is to be installed only in well aerated 
rooms, but not in living rooms or similar recreation 
rooms! 

1.  Put operating switch 

1

 into “0” 

position (OFF). 

2.  Connect unit plug to a suitable 

mains socket. 

230V/1~  50 Hz.

 

Connect the unit with the current supply 

Attention, important hints to the after-cooling phase 

The air supply fan continues running to cool down the 
combustion chamber and then stops later. 

The fan can start several times before final switching off.

 

Unit Shut Down

 

Heating with room thermostat (accessories) 

The unit runs fully automatically and depending on tem-
peratures. 

1.   Remove the bridge circuit plug 

3

2.   Connect the thermostat plug 

5

 of the 

room thermostat (accessories) into 
the thermostat socket 

4

3.   Install room thermostat 

6

 in a suit-

able place. 

The thermostat sensor may not be 
exposed directly to the hot air cur-
rent and not fixed directly on a cold 
surface.

 

4.   Pre-select desired room tempera-

ture on the room thermostat 

5.   Put the operating switch into position 

“1” (on). 

1.   Put operating switch into position 

“0” (OFF). 

Heating without room thermostat 

The unit runs in continuous operation. 

2.  Put the operating switch into position 

“1” (on). 

1.  Connect the supplied bridge circuit 

plug 

3

 to the thermostat socket 

4

 of 

the unit 

G

 

Never interrupt (except in emergency situations) 
the connection to the mains before the end of the 
whole after-cooling phase. 

Our guarantee does not cover damages caused 
to the unit by overheating. 

Summary of Contents for AT 25

Page 1: ...REMKO powerful like a bear Edition GB M04 Operation Technology Spare Parts REMKO AT 25 Automatic oil heater ...

Page 2: ......

Page 3: ...10 Wiring diagram 10 Troubleshooting 11 Exploded view 12 Spare part list 13 Maintenance log 14 Automatic oil heater REMKO AT 25 Make sure to read these instructions carefully before starting using the unit Our guarantee will become void when the unit supplied by us is used and installed for inadequate purposes or maintained incorrectly etc or if it is changed without our prior consent Subject to a...

Page 4: ...rner with optical flame monitoring a low mainte nance axial ventilator a connection cable with plug a room thermostat socket and a fivefold filter system The unit complies with the basic safety and health re quirements of the relevant EU stipulations and is reli able and simple to operate The unit can be used e g in the following areas for drying new buildings for point heating of outdoor workplac...

Page 5: ...nd doors or openings which are not lockable are present in the region of ceiling and floor for the air supply and for out going air and the size of these openings in m corresponds with at least 0 003 times the nominal heat output in kW of all units operating in the room 2 6 The unit must not be installed or operated in rooms and areas where the danger of fire or explosion ex ists 3 Room drying 3 1...

Page 6: ...he units are generally to be operated in accordance with the safety rules the building code of the land con cerned and the fire protection code Avoid under or overpressure in the room where the unit is installed as this would result in combustion troubles Suction and blow out cross sections may not be re duced It is prohibited to connect conduits or hoses to the unit blow out opening Make sure tha...

Page 7: ...It is not possible to get rid of paraffin discharge which is already present using the tank heating The requirement for this is the cleaning of the entire fuel system G The unit is to be installed only in well aerated rooms but not in living rooms or similar recreation rooms 1 Put operating switch 1 into 0 position OFF 2 Connect unit plug to a suitable mains socket 230V 1 50 Hz Connect the unit wi...

Page 8: ...e a long service life and trouble free operation After each heating period or even earlier depending on the deployment conditions the entire unit including combustion chamber and burner head must be cleaned of soot sediments dust and dirt The oil filters must also be cleaned replaced at least once a year or depending on the degree of contamina tion of the fuel frequently G Setting and maintenance ...

Page 9: ...ustment of air slide plate Fine adjustment of air slide plate by means of CO2 indi cator and soot pump CO2 value approx 10 13 Soot figure 0 1 by Bacharach 4 When maintenance has been carried out re assemble all parts carefully in reverse order 5 Pre set air flow plate air slide plate and the ignition electrode distance according to the approximate indi cations 4 2 3 4 8 air slide plate air flow pl...

Page 10: ...re counter clockwise reduce the pressure The required pump pressure is determined according to the heating capacity please refer to unit type plate and to the nozzle size The pressure setting screw A is to be secured with the counter nut B after having set the pressure Fuel Pump The standard type of the pump runs in a system of 1 pipe The required fuel is sucked in through the suction line S For t...

Page 11: ...f ignition electrodes or damaged insulation Adjust correctly resp replace it 13 Air flow plate of the burner head is misadjusted resp dirty Adjust correctly by means of CO2 indicator and soot pump CO2 10 13 and soot figure by Bacharach 0 1 14 Solenoid valve does not open Check solenoid valve resp replace if necessary A click should be heard during switching on off The safety temperature limiter ha...

Page 12: ...12 Exploded View We reserve the right to make modifications in dimensions and construction in the interests of technical progress See fig A See fig B Fig A Fig B 74 ...

Page 13: ...ition cable kit 1102159 40 ignition electrode 1102132 41 traction relief 1108325 No Description Ref No 42 thermostat socket 1101018 43 bridge circuit plug 1101019 44 protective socket big 1101615 45 capacitor 1102907 46 connection cable solenoid valve 1102825 47 hose connection fitting 1102109 48 fuel pump with solenoid valve 1103717 49 copper pipe 4 mm cpl 1102315 50 angle clutch 1 8 x 4 1102112 ...

Page 14: ...ing screws Electric safety inspections Test run Maintenance Log Model Model No Setting and maintenance work is to be carried out only by authorised specialists Remarks 1 Date 2 Date 3 Date 4 Date 5 Date Signature Signature Signature Signature Signature 6 Date 7 Date 8 Date 9 Date 10 Date Signature Signature Signature Signature Signature 11 Date 12 Date 13 Date 14 Date 15 Date Signature Signature S...

Page 15: ......

Page 16: ...REMKO GmbH Co KG Klima und Wärmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 ...

Reviews: