Remeha Selecta
42
III
7
DHW temperature 45 °C
With this option you can
set the maximum DHW
temperature.
8
DHW temperature 55 °C
9
*
DHW temperature according to
parameter 3/3
Work setting 3/3 = 50 °C
1
)
IV
A
CH flow temperature 60 °C
In the less cold periods of the
year the radiators need not
be heated to the same extent.
With these parameters you
can lower the flow tempera-
ture. This is not necessary if
you have a modulating con-
troller or outside sensor con-
nected.
B
CH flow temperature 75 °C
C
*
CH flow temperature according to
parameter 1/1
Factory setting 1/1 = 80 °C
V
D
*
Pump overrun according to param-
eter 2/2
Factory setting 2/2 = 3 minutes
If there is danger of your heat-
ing system freezing, continu-
ous water circulation is advis-
able. Setting ‘E’ recognises
this.
E
Pump continuous circulation
VI
F
*
Pump position during CH-
operation. Parameter F selected
(red dot is flashing) means: pump
is circulating at high speed
With this parameter you can
choose whether the pump
circulates at high speed or
at low (manual adjustable)
speed during CH operation.
To change this parameter,
keep the ‘
prog
’- key pressed
in for more than 1 sec.
Table 06 Overview and meaning of parameters
*
These values have factory default settings which can only be changed using a PC/
PDA and the Recom software with the
interface
kit.
1
)
When a calorfier sensor or thermostat is installed, this temperature setting must be
used.