Simple Quinta Pro boiler domestic installation  

Typical ‘S’ plan, heating and hot water  

(Time and temperature control by others) 

 

Power Supply

  

•    Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected  

to the factory fitted fly lead

Boiler Control Settings

 

(see 5.7.2 in technical documentation)
•   Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
•   Boiler will recognise the control being used 
•    Use the zone valve end switches to provide the volt free switch pair on OT on the main 

control PCB to enable the boiler

•    Boiler output will vary between 18% part load set point and 100% full load set point  

to achieve the boiler flow set point (code P1)  

System Components

 

(not supplied) 
•    Simple two channel time clock providing 230v switched supplies to control  

heating and  domestic hot water

•   System pump 
•   Cylinder thermostat
•   Room thermostat
•   HTG and DHW zone valves c/w a single end switch (closes on valve fully open) 
•   Wiring centre  

Note:

 

1.   Maintain polarity on all connections 
2.   Some Neutral and Earth connections have been omitted for clarity 
3.   The schematic is for guidance only and does not constitute a design 
4.    Heating and hot water can be operated independently or simultaneously  

with this layout provided the control selected will allow it

Summary of Contents for Quinta Pro 115

Page 1: ...AM EXCELLENT RECYCLABLE MATERIALS PANTONE 2985 EC PANTONE 2985 EC HIGH EFFICIENCY 108 9 NCV T 50 30 C REMEHA QUINTA PRO RANGE SUGGESTED SCHEMATICS WITH CONTROL AND POWER WIRING DETAILS QUINTA PRO RANGE Suggested Schematics with Control and Power Wiring Details QUINTA PRO RANGE OUTPUTS QP30 8 0 31 4 kW QP45 8 0 43 0 kW QP65 12 0 65 0 kW QP90 14 1 89 5 kW QP115 16 6 114 0 kW High efficiency wall hun...

Page 2: ...m p31 and run signals Quinta Pro nominal flow rates and boiler resistances p31 Note We supply the Grundfoss 25 80 Part No S101621 as standard for the full Quinta Pro range This will alter due to changes in EU regulations The Quinta Pro 30 will operate on speed 1 the 45 and 65 will operate on speed 2 and the 90 and 115 will operate on speed 3 They are intended to act as a shunt pump In the layouts ...

Page 3: ... can be used with a combination of outside room and flow temperature sensors to vary the boiler output flow temp to suit weather conditions The iSense can be installed in a reference room and can also be mounted in a boiler when used in weather compensated mode It has a 7 day timer with multiple on off and night setback periods holiday function frost protection and manual override Celcia MC4 Multi...

Page 4: ...CB to enable the boiler Boiler output will vary between 18 part load set point and 100 full load set point to achieve the boiler flow set point code P1 System Components not supplied Simple two channel time clock providing 230v switched supplies to control heating and domestic hot water System pump Cylinder thermostat Room thermostat HTG and DHW zone valves c w a single end switch closes on valve ...

Page 5: ...heating and dome stic hot wa ter usinga simple S Pla n Shunt O QP 001S QP 001SA Quinta Pro single boiler heating and dome stic hot wa ter usinga simple S Pla n QP 001S QP 001SA Single Quinta Pro boiler heating and domestic hot water using a simple S Plan ...

Page 6: ...etails Boiler Run volt free relay on SCU X01 see boiler manual for full details Boiler Control Settings see 5 7 2 in technical documentation Connect the external controls volt free to the OT terminals on the main control PCB on off Boiler will modulate to the set point set in P1 or the 0 10v terminals on the IF 01 Control option based on temperature or output can be adjusted on the jumper on the I...

Page 7: ...7 QP 002 QP 002A Quinta Pro single boiler heating only QP 002 QP 002A Quinta Pro single boiler heating only QP 002 QP 002A Single Quinta Pro boiler heating only ...

Page 8: ...boiler manual for full details Boiler Run volt free relay on SCU X01 see boiler manual for full details Boiler Control Settings see 5 7 2 in technical documentation Boiler will recognise the type of control being used Set boiler code P1 to the required flow temp i e 80 80ºC system design requirements Connect the external controls volt free to the OT terminals on the main control PCB on off Boiler ...

Page 9: ... QP 003A Quinta Pro single boiler heating only with loss heading QP 003 QP 003A Quinta Pro single boiler heating only with loss heading QP 003 QP 003A Single Quinta Pro boiler heating only with low loss header ...

Page 10: ...ise the type of control being used Set boiler code P1 to the required flow temp i e 80 80ºC system design requirements Connect the external controls volt free to the OT terminals on the main control PCB on off Boiler will modulate to the set point set in P1 Pumps connect pump PM1 to the heating pump terminals shown on the PCB SCU S02 max 400Va 1 5 amp Connect the shunt pump SH1 to the fly lead sup...

Page 11: ...eating with priority hot water using a low loss header Three way valve DHW priority Quinta Pro 30 45 65 only Quinta Pro single boiler heating with priority hot water using a low loss header pump option DHW priority can be used on all Quinta Pro range QP 004 QP 004A Single Quinta Pro boiler heating with priority hot water using a low loss header 3 way valve DHW priority Quinta Pro 30 45 65 only Sin...

Page 12: ...valve Wiring detailof controlswhen using a Remeha Commercial Calorifier a volt free HWStime control anda 2 Port spring return valve Ifusing adifferent type of calorifier please follow manufacturer s instructions regarding control and wiring details 2 C 1 2 C 1 Factory tted supplylead to be connected to a230v fused spur forboiler permanent supply Time temp control HTG volt free TimecontrolDHW volt ...

Page 13: ... 2 Port spring return valve and an iSense or Open Therm controller If using a different type of calorifier please follow manufacturer s instructions regarding control and wiring details Set Boiler parameter P37 to 0 Note Calorifier Thermostat temperature should be set 5oC higher than the iSense control hot water setting Wiring detail of controls when using a Remeha Commercial Calorifier If using a...

Page 14: ...se the type of control setting used Fitting the Control For room compensation fit the control in a normally occupied reference room within the building being heated For room weather compensation an outside sensor can be fitted If requiring weather compensation only the iSense can be fitted into the boiler control panel In this case an outside sensor must be fitted and connected to Tout in the boil...

Page 15: ...ontroller 1 6M Suggested height in room Normal position for the iSense controller mounted in reference room within the building room compensation 100m Max 230v Supply Condensate Gas Flow Return Pump PM1 1 6M Suggested height in room Normal position for the iSense controller mounted in reference room within the building 100m Max 230v Supply Condensate Gas Flow Return Pump PM1 iSense can be fitted i...

Page 16: ...pensation Single Quinta Pro boiler heating only using the iSense controller room weather or weather compensation Single Quinta Pro boiler heating only using the iSense controller QP 005C Factory fitted supply lead to be connected to a 230v fused spur for boiler permanent supply Note Control PCBs are shown diagrammatically Earths are omitted for clarity Pump PM1 iSense controller O T Factory fitted...

Page 17: ... documentation Set boiler code P1 to the required flow temp i e 80 80ºC system design requirements Boiler will recognise the type of control setting used Fit the control in a normally occupied reference room within the building being heated Refer to the instructions supplied with the control package Set up the controller to suit the design requirements and occupancy times for heating and hot water...

Page 18: ...oom within the building room compensation 100m Max 230v Supply Condensate Gas Flow Return Pump PM1 100m Max DHW Sensor DHW Diverting valve A AB B 2 Port spring return valve Bypass valve 1 6M Suggested height in room Normal position for the iSense controller mounted in reference room within the building room compensation 100m Max 230v Supply Condensate Gas Flow Return Pump PM1 100m Max DHW Sensor 2...

Page 19: ...ted for clarity Boiler parameter P37 must be set to 0 See drawing QP004E Pump PM1 iSense controller O T 230v fused Outside Sensor 3 way valve supply for 2 portvalve 2 Port spring return valve Calorifier Sensor Factory fitted supply lead to be connected to a 230v fused spur for boiler permanent supply Note Control PCBs are shown diagrammatically Earths are omitted for clarity iSense controller O T ...

Page 20: ...in a normally occupied reference room within the building being heated if room and weather compensation is required If weather only is required the iSense can be fitted in a boiler control panel Install the MC4 controller adjacent to the boiler plant and connect as shown Install the outside sensor on a North facing wall and connect to the MC4 for weather compensation only Boiler Control Settings s...

Page 21: ...sing a low loss header outside weather room compensation with the Celcia MC4 and iSense controller QP 007A 1 6M Suggested height in room Normalpositionforthe iSense controllermounted in reference room within the building 100m Max 230v Supply 230v Supply Condensate Gas Flow Return 100m Max Outside sensor on North facing wall iSense can be mounted in boiler for weather compensation only Shunt Pump S...

Page 22: ...room and weather compensation is required If weather only is required the iSense can be fitted in a boiler control panel Install the MC4 controller adjacent to the boiler plant and connect as shown Install the outside sensor on a North facing wall in a sheltered position and connect to the MC4 Boiler Control Settings see 5 7 2 in technical documentation Set boiler code P1 to the required flow temp...

Page 23: ...iSense controller Hot water produce by single boiler only pump option All of the Quinta range 1 6M Suggested height in room Normalpositionforthe iSense controllermounted in reference room within the building 100m Max 230v Supply 230v Supply Condensate Gas Flow Return 100m Max Outside sensor on North facing wall Shunt Pump Shunt Pump Celcia MC4 Pump PM1 Htg Flow sensor T w o t o f o u r b o il e r ...

Page 24: ...iagrammatically Earths are omitted for clarity Shunt pump Shunt pump Shunt pump Shunt pump Boiler Parameter P37 must be set to 0 Boiler No 4 Boiler No 3 Boiler No 2 On off OT On off OT On off OT X81 X81 X81 System Pump PM1 Max 1amp Switch spur 230v Rated at 3amps Flow Sensor Mount on flow pipework to register a common flow temperature L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14 MC4 Outside s...

Page 25: ...iSense Pro complete with wall box Part No 100018256 1 x AD278 Room Sensor Control temperature control Part No 100017732 1 x AD287 Open Therm Interface not required in first boiler Part No 100018921 1 x AD134 Bus Cable 12m iSense controller to second boiler Part No 88017851 1 x AD199 Flow Sensor Part No 88017017 1 x AF60 Outside Sensor Part No 95362450 1 x KVT60 DHW Sensor Part No 95362448 Basic Tw...

Page 26: ... Note The OT cable between the iSense controller and the first boiler is not supplied Cable should be 2 core 7mm screened when running with higher voltage cables iSense Pro Component Details iSense Pro controller complete with wall box AD283 Part No 100018256 Room Sensor Basic AD244 Part No 100012044 Room Sensor Temperature Control AD278 Part No 100017732 Digtal Remote Room Control AD Part No 1000...

Page 27: ...ense Pro controller in conjunction with the iSense Pro installation and service manual and to suit the installation and building heat loss response time It will provide timed weather compensated heating with an optimum start facility uses inside and outside sensors to delay the on time as dictated by weather conditions Heating all boilers available during the timed on periods the heating will be d...

Page 28: ...ng a low loss header outside weather room compensation with iSense Pro controller QP 009A Multiple Quinta Pro boilers heating and HTG and DHW using a low loss header outside weather room compensation with iSense Pro controller DHW via multiple boilers 6 1 6M Suggested height in room 1 6M Suggested height in room Normal position for the iSense Pro remote controllers or room sensors mounted in refer...

Page 29: ...il e r s OT On off On off On off Note When using single zone control B flow sensor is connected to S Syst HWS Sensor Some earths omitted for clarity Thermostat Interface AD287 fitted into each boiler not required for No 1 boiler C B S Syst BF AF 0 10v O T C C B E N L C S E N L C S N E N L E N L N L AUV N CDI C CDI CDR B Room Sensor Room Sensor Flow Sensor Flow Sensor Flow Sensor O Side Sensor HWS ...

Page 30: ...ase follow manufacturers instructions 230v fused supply for 2 port valve from boiler supply 2 Port spring return valve Calorifier Thermostat Shunt pump SH1 Pump PM2 Time Control DHW volt free Boiler No 1 in cascade QP 009D Quinta Pro multiple boiler HTG and DHW using a low loss header outside weather room compensation with the iSense Pro controller DHW from single boiler QP 009E Quinta Pro multipl...

Page 31: ...tus Status Status QP 010 Connecting multiple boilers with external control interlocks and alarm and run signals QP 010 QP 009F Connecting multiple boilers with external control interlocks and alarm and run signals Quinta Pro multiple boilers HTG only using a 0 10v input from a remote BMS control Quinta Pro 30 output 29 3kW 80 60ºC Quinta Pro 45 output 40kW 80 60ºC Quinta Pro 65 output 61kW 80 60ºC...

Page 32: ...remeha co uk Lightly Tread O N T H E P L A N E T Thedatapublishedinthistechnicalsalesleafletisbasedonthelatestinformation atdateofpublication and may be subject to revisions It should be read in conjunction with our full technical brochure available on request We reserve the right to continuous development in both design and manufacture therefore any changes to the technology employed may not be r...

Reviews: