31
C
B
S Syst
BF
AF
0 - 10v
- +
O T
C
C
B
E N L C S
E N L C S N E N L E N L N L
AUV
N
CDI
C
CDI CDR
B
Bus Cable
Shunt pump SH3
Boiler No.3
Shunt pump SH2
Boiler No.2
2 to 8 boilers
OT
OT
On/off
Shunt pump SH1
Boiler No.1
On/off
On/off
OT
Bus Cable
Interface AD287 fitted into
each boiler (not required
for No.1 boiler)
External BMS
Controller
(not supplied)
Some earths omitted for clarity
Flow Sensor
Flow Sensor AD199
Switch Fused Supply
Boiler No. 1
Boiler No. 2
Boiler No. 3
Boiler No. 1
Boiler No. 2
Boiler No. 3
On/off
On/off
On/off
Connect boilers in parallel. Ensure polarity is maintained on each boiler
External
interlock
Supply voltage (max 230v 1amp)
Supply voltage (max 230v 1amp)
Connect boilers in parallel. Ensure polarity is maintained on each boiler
Diagram shows run signal connected to X3 on SCU - X01
X3 potentiometer will be set to 2.
Alarm signal is connected to X4 the X4 potentiometer will be set to 0.
There are various options. Please refer to the Quinta Pro installation booklet.
Run Signal
Alarm Signal
N
N
X3
X4
Nc C No
Nc C No
Nc C No
Nc C No
Nc C No
Nc C No
X3
X4
X3
X4
Status
Status
Status
Status
Status
Status
QP 010
Connecting multiple boilers with external control interlocks and
alarm and run signals.
QP 010
QP 009F
Connecting multiple boilers with external control interlocks and
alarm and run signals
Quinta Pro multiple boilers, HTG only using a 0-10v input from a
remote BMS control
Quinta Pro 30 output
29.3kW @ 80/60ºC
Quinta Pro 45 output
40kW @ 80/60ºC
Quinta Pro 65 output
61kW @ 80/60ºC
Quinta Pro 90 output
84.2kW @ 80/60ºC
Quinta Pro 115 output
107kW @ 80/60ºC
System ∆t
Nom flow
l/s
Boiler
resistance
mbar
Nom flow
l/s
Boiler
resistance
mbar
Nom flow
l/s
Boiler
resistance
mbar
Nom flow
l/s
Boiler
resistance
mbar
Nom flow
l/s
Boiler
resistance
mbar
20
0.35
70.00
0.48
90.00
0.73
130
1.00
140
1.28
250
19
0.37
77.56
0.50
99.72
0.77
144
1.06
155
1.35
277
18
0.39
86.42
0.53
111.1
0.81
160
1.12
173
1.42
309
17
0.41
96.89
0.56
124.5
0.86
180
1.18
194
1.51
346
16
0.44
109.38
0.60
140.6
0.91
203
1.26
219
1.60
391
15
0.47
124.44
0.64
160.0
0.97
231
1.34
249
1.71
444
14
0.50
142.86
0.68
183.6
1.04
265
1.44
286
1.83
510
13
0.54
165.68
0.74
213.0
1.12
308
1.55
331
1.97
592
12
0.58
194.44
0.80
250.0
1.22
361
1.68
389
2.13
694
11
0.64
231.40
0.87
297.5
1.33
430
1.83
463
2.33
826
10
0.70
280.00
0.96
360.0
1.46
520
2.01
560
2.56
1000
Quinta Pro Nominal flow rates and boiler resistances