8 Settings
8.1
List of parameters
The code of the parameters always contain two letters and three numbers.
The letters stand for:
AP
Appliance related parameters
CP
Zone related parameters
DP
Domestic hot water related parameters
EP
Smart Solutions related parameters
GP
Gas-fired heat engine related parameters
PP
Central heating related parameters
Important
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
8.1.1
Description of the parameters - SCB-01
Tab.10
> SCB–01 - Factory settings at user level
Code
Description
Adjustment range
Factory setting
EP018
Status relay function
0 = No Action
1 = Alarm
2 = Alarm Inverted
3 = Burning
4 = Not burning
5 = Reserved
6 = Reserved
7 = Service request
8 = Boiler on CH
9 = Boiler on DHW
10 = CH pump on
11 = Locking or Blocking
0
EP019
Status relay function
0 = No Action
1 = Alarm
2 = Alarm Inverted
3 = Burning
4 = Not burning
5 = Reserved
6 = Reserved
7 = Service request
8 = Boiler on CH
9 = Boiler on DHW
10 = CH pump on
11 = Locking or Blocking
0
EP028
Selects the function of the 0-10 Volt output
0 = 0-10V 1 (Wilo)
1 = 0-10V 2 (Gr. GENI)
2 = PWM signal (Solar)
3 = 0-10V 1 limited
4 = 0-10V 2 limited
5 = PWM signal limited
6 = PWM signal (UPMXL)
0
EP029
Selects the source signal for the 0-10 Volt
output
0 = PWM
1 = Requested power
2 = Actual power
0
8 Settings
7698983 - v.02 - 17102018
27