Quinta Ace
135
160
Operating temperature
max
°C
90
90
Pressure drop secondary circuit (ΔT=20 K)
mbar
126
170
Tab.63 Electrical data
Quinta Ace
135
160
Supply voltage
V~
230
230
Power consumption – full load
max
W
199
275
Power consumption – low load
min
W
47
47
Power consumption – standby
min
W
5.3
5.3
Electrical protection index
IP
IPX1B
IPX1B
Fuses
CB-01
CU-GH06c
A
A
6.3
1.6
6.3
1.6
Tab.64 Other data
Quinta Ace
135
160
Total weight (empty)
kg
147
147
Minimum mounting weight (without front panel)
kg
123
123
Average acoustic level at a distance of one metre from the
boiler
dB(A)
59.5
59.5
Tab.65 Technical parameters
Quinta Ace
135
160
Condensing boiler
Yes
Yes
No
No
B1 boiler
No
No
Cogeneration space heater
No
No
Combination heater
No
No
Rated heat output
Prated
kW
128
152
Useful heat output at nominal heat output and high tempera
P
4
kW
128.1
152.1
Useful heat output at 30% of rated heat output and low tem
P
1
kW
42.8
50.8
Seasonal space heating energy efficiency
ƞ
s
%
-
-
Useful efficiency at rated heat output and high temperature
ƞ
4
%
88.1
87.8
Useful efficiency at 30% of rated heat output and low tem
ƞ
1
%
98.0
97.8
Auxiliary electricity consumption
Full load
elmax
kW
0.199
0.275
Part load
elmin
kW
0.047
0.047
Standby mode
P
SB
kW
0.005
0.005
Other items
Standby heat loss
P
stby
kW
0.191
0.191
Ignition burner power consumption
P
ign
kW
-
-
Annual energy consumption
Q
HE
kWh
GJ
-
-
Sound power level, indoors
L
WA
dB
68
68
Emissions of nitrogen oxides
NO
X
mg/kWh
29
35
(1) Low temperature means 30°C for condensing boilers, 37°C for low temperature boilers and 50°C (at heater inlet) for other heating appli
ances.
(2) High temperature operation means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
12 Technical specifications