Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof terminal and common shared flue ducts.
The materials used must comply with the prevailing regulations
and standards.
Please contact us to discuss using flexible flue gas outlet
material.
Tab.9
Overview of material properties
Version
Flue gas outlet
Air supply
Material
Material properties
Material
Material properties
Single-wall, rigid
Plastic
Thick-walled,
aluminium
With UKCA and/or CE mark
ing
Temperature class T120 or
higher
Condensate class W (wet)
Pressure class P1 or H1
Fire resistance class E or bet
ter
Plastic
Stainless steel
Aluminium
With UKCA and/or CE mark
ing
Pressure class P1 or H1
Fire resistance class E or bet
ter
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
4.5.3
Dimensions of flue gas outlet pipe
Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
d
1
External dimensions of flue gas outlet pipe
D
1
External dimensions of air supply pipe
L
1
Length difference between flue gas outlet pipe and air supply pipe
Tab.10 Dimensions of pipe
d
1
(min-max)
D
1
(min-max)
L
1
100/150 mm 99.3 - 100.3 mm
149 - 151 mm
0 - 15 mm
110/160 mm 109.3 - 110.3 mm 159 - 161 mm
0 - 15 mm
(1) Shorten the inner pipe if the length difference is too great.
4.5.4
Length of the flue and air supply pipes
The maximum length of the flue and air supply vary per appliance type.
Consult the relevant chapter for the correct lengths.
If a boiler is not compatible with a specific flue system or diameter, it is
indicated with "-" in the table.
When using bends, the maximum flue length (L) must be shortened
according to the reduction table.
Use approved flue reducers for adaptation to another diameter.
The boiler also supports other flue lengths and diameters than those
specified in the tables. Contact us for more information.
Fig.8
Dimensions of concentric
connection
AD-3000962-01
ød
1
L
1
øD
1
4 Preparation of installation
7701838 - v.09 - 10122021
17