6.  REGULATION AND SAFETY EQUIPEMENT

6.1  General

The Remeha Gas 350 is supplied with electronic control 
and safety equipment with ionisation fl ame detection.

6.2  Instrument panel

The Remeha Gas 350 is supplied with an instrument 
panel that is fi tted in the front of the boiler. The standard 
instrument panel can be extended with the fi tting of 
the following options: hour run meters, water pressure 
switch, down draught thermostat, no volt contacts and/or 

rematic

®

 control.

All connections are pre-wired and fi tted with plugs. The 
capillaries from the control panel should be fi tted in the 
pocket of the boiler, which is fi tted in the fl ow connection 
of the boiler.

6.3.2  Specifi cation

1  Gas Multi-Bloc contains A.B.C.
  A  

2 Safety shut off valves

  B  

1 Gas governor 

  C  

1 Gas fi lter

1  Pilot gas valve
1  Pilot burner with ionisation probe
  and ignition probe.

6.3.3  Control panel behind front panel

1  Control box Satronic
1  Ignition transformer 16 kV.

6.4  Functions

6.4.1  Flame protection

Flame protection by means of ionisation fl ame detection.

6.4.2  Down draught thermostat

Optional the boiler can be fi tted with a down draught 
thermostat. When there is down draught of the fl ue gases 
this thermostat will switch off the boiler. 
Fixed setpoint is 70°C.

6.4.3  Thermostats

Control thermostat On/Off 35°-95°C.
Control thermostat High/Low 35°-95°C.
High-Limit thermostat locks out at 110°C.

6.3  Standard electronic gas train High/Low

6.3.1  Schematic

Fig. 05  Gastrain

Legend

A  

Gas cock

AB  

Pilot burner

DR  

Gas governor

F   

Gas fi lter

HB  

Main gas burners

MB  

Gas multibloc

OT  

Ignition transformer

MK 

Pilot gas valve

MP  

Measuring point

VA  

Safety shut off valve

VB 

Ionisation probe 

- - - -    Not supplied.

6. Analogue thermometer for water temperature
7. High - Limit thermostat 110°C (pre set)
8. Warning light (lock out)

9. Option for 

rematic

®

 weather compensator

8

7

5

4

9

1

2

3

6

Fig. 04  Layout of the instrument panel, extended with hour counters

1. Operating switch (On/Off)
2. Control thermostat On/Off. Setting between 35 - 95°C
3. Control thermostat high/low. Setting between 35 - 95°C
4. Hour run meter total running hours (not standard)
5. Hour run meter full load hours (not standard)

Summary of Contents for Gas 350 L

Page 1: ...Remeha Gas 350 Atmospheric gas boiler with reduced NOx emission 64 174 kW Technical information R e m e h a G a s 3 5 0...

Page 2: ...6 3 1 Schematic 7 6 3 2 Specification 7 6 3 3 Control panel behind front panel 7 6 4 Functions 7 6 4 1 Flame protection 7 6 4 2 Down draught thermostat 7 6 4 3 Thermostats 7 7 Assembly and installati...

Page 3: ...II 2H3B P The Remeha Gas 350 central heating boiler is approved according to the following European directives Gas appliance directive no 90 396 EEC Ef ciency directive no 92 42 EEC E M C directive no...

Page 4: ...09 130 152 174 mbar mbar A mm B mm E mm F mm t 10 C l 640 740 840 940 1040 1140 280 330 380 430 480 530 905 905 905 930 930 930 200 200 200 200 250 250 1030 1030 1030 1080 1080 1080 165 165 165 215 21...

Page 5: ...imum water ow through the boiler is Output boiler in kW m3 h 93 This minimum ow must be maintained for 5 minutes after the burners stops ring to avoid high temperature shut down due to residuel heat g...

Page 6: ...00 200 250 250 905 905 905 930 930 930 1030 1030 1030 1080 1080 1080 Number of sections 280 330 380 430 480 530 V min length 0 5 m before elbow thus avoiding down draught W min 150 mm with vertical fl...

Page 7: ...ction Flame protection by means of ionisation ame detection 6 4 2 Down draught thermostat Optional the boiler can be tted with a down draught thermostat When there is down draught of the ue gases this...

Page 8: ...a Main supply 230 V 50Hz L N Running current 110 W Installed fuse 6 3 Amp slow acting 7 3 Water connections The boiler water connections 2 male thread are tted at the rear of the boiler right hand con...

Page 9: ...9 9 5 Wiring diagram boiler Fig 06 Wiring diagram...

Page 10: ...r 1 Check gas connections 2 Check electrical supply L N and earth 3 Check water connections and if installation is lled 4 Switch on circulation pump and check rotation direction 5 Open main gas cock r...

Page 11: ...the boiler room and the oor underneath the boiler 5 Clean the burners internally and externally and check the kanthal bars 11 MAINTENANCE 6 Clean the boiler casings 7 Clean the gas train ignition pil...

Page 12: ...t or whole without our prior consent in writing ISO 9001 since 1988 Subject to alterations 51247 1 500 02 01 Ho Broag Ltd Head office Remeha house Molly Millars Lane Wokingham Berkshire RG41 2QP Tel 0...

Reviews: