9.7 GROUP G - CURRENT TRANSFORMER
90
c.t.
Current Transformer (Word modbus 2090)
Enables C.T. input and selects the net frequency
0
Disabled (
Default
)
1
50 Hz
2
60 Hz
91
c.t. v.
Current Transformer Value (Word modbus 2091)
Selects amperometric transformer full-scale
1…200
Ampere (
Default
: 50)
92
H.b.a.t.
Heater Break Alarm Threshold (Word modbus 2092)
Heater Break Alarm activation threshold
0
Alarm disabled. (
Default
)
0.1-200.0 Ampere.
93
ocu.t.
Overcurrent Alarm Threshold (Word modbus 2093)
Overcurrent alarm threshold
0
Alarm disabled. (
Default
)
0.1-200.0 Ampere
94
H.b.a.d.
Heater Break Alarm Delay (Word modbus 2094)
Delay for Heater Break Alarm and overcurrent alarm
0...3600 s. (
Default
: 60 s)
95÷99
Reserved Parameters - Group G
Reserved parameters - Group G