background image

31

STATUS LIGHT TROUBLESHOOTING FLOWCHART

Status Light Code

LED FLASH 

SEQUENCE

CONTROL STATUS

CORRECTIVE ACTION

Short flash once every four second

IDLE (No call for heat, no fault conditions)

“Heartbeat”, alternates bright/dim

Call for Heat (No fault conditions)

One Flash, three second pause

Low Flame Signal (control continues to 

operate)

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the 
power outlet.

1. 

Check the incoming gas line pressure to ensure adequate supply to the water heater.  If incoming 
gas supply pressure is adequate proceed to step 2.

2. 

Check all wiring connections and insure all harness and wires connections are seated firmly and 
provide proper electrical contact.  If no connection problems are found proceed to step 3.  Firmly 
seat any loose connections found.  If any connections are found to be damaged consult the 
replacement parts list for the appropriate replacement.  After any connection problems are fixed 
restart the water heater by following the lighting instructions on page 19.  If the problem persists 
proceed to step 3.

3. 

Check condition of the base ring filter and flame arrestor.  If they are clogged follow the instructions 
for cleaning on pages 26-27.  If parts are not clogged proceed to step 4.  After cleaning follow 
instructions for lighting on page 19.  If problem persists proceed to step 4.

4. 

Follow the instructions on page 25 to remove the burner assembly.  Once the burner assembly has 
been removed inspect the manifold tube and burner, see figure 29, for any obstructions.  If any 
clogs or obstructions are present clear them.  Inspect the electrode/flame sense rod, see figure 43, 
for corrosion buildup, degradation, or damage.  If there is evidence of any damage to the electrode/
flame sense rod replace the igniter/pilot assembly.  Follow the directions on page 27 to re-install the 
burner assembly into the combustion chamber.  Follow the instructions for lighting on page 19.  If the 
problem persists contact a certified service representative.

Two Flash, three second pause

End Switch Failed Closed

Look at the top of water heater to see if the damper is open, see figure 12.  If the damper is open insure 
there is no obstruction that would prevent the damper from closing.  If there are any obstructions turn 
the power switch on the gas valve to the “OFF” position, remove the obstruction, if the damper closes 
turn the power switch on the gas valve to the “ON” position.  If there are no obstructions present turn the 
power switch on the gas valve to the “OFF” position.  Observe the damper to see if the damper closes.  
If the damper does not close unplug the power cord from the power outlet and proceed to step 1.  If the 
damper closes turn the power switch on the gas valve to the “ON” position.

1. 

Check all wiring connections to insure all harness and wire connections are seated firmly and 
provide proper electrical contact.  If no connection problems are found replace the damper.  
Firmly seat any loose connections found.  If any connections are found to be damaged consult 
the replacement parts list on pages 34-35 for the appropriate replacement.  After any connection 
problems are fixed restart the water heater by following the lighting instructions on page 19.  If the 
problem persists replace the damper.

Three Flash, three second pause

End Switch Failed Open or TCO Limit Lockout

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the 
power outlet.

1. 

Attempt to depress the TCO door switch button, see figure 27.  If the TCO door switch button 
depresses follow the instructions for cleaning the filter and flame arrestor on page 24.  After 
cleaning is completed follow the lighting instructions on page 19.  If the TCO door switch button 
does not depress proceed to step 2.

2. 

Follow the lighting instructions on page 19.  Observe the damper during initial startup.  If there is a 
call for heat and the damper opens allow the unit to continue to perform and monitor any change 
in status.  If there is a call for heat and the damper does not open proceed to step 3. 

3. 

Check all wiring connections to insure all harness and wire connections are seated firmly and 
provide proper electrical contact.  If no connection problems are found replace the damper.  
Firmly seat any loose connections found.  If any connections are found to be damaged consult 
the replacement parts list on page 34-35 for the appropriate replacement.  After any connection 
problems are fixed restart the water heater by following the lighting instructions on page 19.  If the 
problem persists replace the damper.

Four Flash, three second pause

ECO Limit Lockout

1. 

Turn the power switch on the gas control valve to the “OFF” position, wait 10-20 seconds then turn 
the power switch on the gas control valve to the “ON” position.  If the problem persists replace the 
gas control valve.

Five Flash, three second pause

Flame Out of Sequence

Turn the power switch on the gas control valve to the “OFF” position.  Wait 10 minutes then follow the 
lighting instructions on page 19.  If the problem persists replace the gas control valve.

Six-One Flash, three second pause

Soft Lockout* - Retry Limit - 
Failed TFI (Trial for Ignition)

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the 
power outlet.

1. 

Check the incoming gas line pressure to ensure adequate supply to the water heater.  If incoming 
gas supply pressure is adequate proceed to step 2.

2. 

Check all wiring connections and insure all harness and wires connections are seated firmly and 
provide proper electrical contact.  If no connection problems are found proceed to step 3.  Firmly 
seat any loose connections found.  If any connections are found to be damaged consult the 
replacement parts list for the appropriate replacement.  After any connection problems are fixed 
restart the water heater by following the lighting instructions on page 19.  If the problem persists 
proceed to step 3.

3. 

Check condition of the base ring filter and flame arrestor.  If they are clogged follow the 
instructions for cleaning on pages 26-27.  If parts are not clogged proceed to step 4.  After 
cleaning follow instructions for lighting on page 19.  If problem persists proceed to step 4.

4. 

Follow the instructions on page 25 to remove the burner assembly.  Once the burner assembly 
has been removed inspect the manifold tube and burner, see figure 29 , for any obstructions.  If 
any clogs or obstructions are present clear them.  Inspect the electrode/flame sense rod, see 
figure 43 , for corrosion buildup, degradation, or damage.  If there is evidence of any damage to 
the electrode/flame sense rod replace the igniter/pilot assembly.  Follow the directions on page 27 
to re-install the burner assembly into the combustion chamber.  Follow the instructions for lighting 
on page 24.  If the problem persists contact a qualified service representative.

* Soft Lockout - 20 minute wait before returning to normal mode.

Summary of Contents for 616 series

Page 1: ...ny electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call...

Page 2: ...Installation 17 Important Information About this Water Heater 18 Operating Your Water Heater 19 21 Lighting Instructions 19 Checking the Draft 20 Burner Flames 20 Emergency Shutdown 20 Water Temperat...

Page 3: ...t water heaters and have a thorough understanding of this instruction manual Service Agency A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing air sup...

Page 4: ...oid all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Kee...

Page 5: ...n Valve U Pilot and Main Burner V Flue W Metal Drain Pan X Igniter Wire Y Base Ring Filter Z FV Sensor AA Transformer BB Flue Damper ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATIO...

Page 6: ...instructions you should not proceed but have a qualified technician perform the installation of this water heater Massachusetts code requires this water heater to be installed in accordance with Mass...

Page 7: ...to clean the spill until all ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result...

Page 8: ...ctor or water shut off device used in conjunction with a piped metal drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in variou...

Page 9: ...ural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisonin...

Page 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Page 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Page 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Page 13: ...re certified by CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxid...

Page 14: ...Before connecting a vent to a chimney make sure the chimney passageway is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces...

Page 15: ...off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperatu...

Page 16: ...se excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates boile...

Page 17: ...h duct tape 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add additional sections of pipe insulation as needed T P RELIEF VALVE T P RELIEF VALVE MANUAL RELIEF LEVER T P RELIEF VALVE INSULATIO...

Page 18: ...es Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide Installation Checklist Water Heater Location Wate...

Page 19: ...ier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the...

Page 20: ...emperature range of 120 F 140 F 49 C 60 C is recommended by most dishwasher manufacturers The thermostat of this water heater has been factory set at the VAC Vacation position It is adjustable and mus...

Page 21: ...erature set by the user Vacation Setting The Vacation Setting VAC sets the controller at approximately 70 F This setting is recommended when the water heater is not in use for a long period of time Th...

Page 22: ...YL YL BN 24VAC V 24VAC BK 120VAC WH 120VAC GR BK 24VAC HOT WH 24VAC NEUTRAL BL RD BL RD YL YL BK 24VAC HOT WH 24VAC NEUTRAL YL 24VAC YL 24VAC TRANSFORMER YL 24 VAC GAS CONTROL VALVE THERMOSTAT FV SENS...

Page 23: ...ce information at 1 800 365 4054 A temperature limit switch or ECO Energy Cut Off sensor located in the gas control valve thermostat is used to shut off the water heater if the water temperature excee...

Page 24: ...ting Your Water Heater See the Repair Parts Illustration section for anode rod location TEFLON is a registered trademark of E I Du Pont De Nemours and Company Draining and Flushing It is recommended t...

Page 25: ...ush down slightly to free the manifold and pilot tube 7 Carefully remove the manifold assembly from the burner compartment NOTE Be sure not to damage internal parts Replacement Parts IMPORTANT The fol...

Page 26: ...lot before going to the next step FIRST BEND S OTHER FITTINGS NOT SHOWN FOR CLARITY PILOT TUBE SCREWS OLD PILOT IGNITER FLAME SENSOR ASSEMBLY FIGURE 30 7 Push the new pilot tube and igniter wire throu...

Page 27: ...ssembly door is tightened visually inspect the door gasket between the manifold burner assembly door and the combustion chamber for spaces or gaps that would prevent a seal IMPORTANT Do not operate th...

Page 28: ...26 NOTE L P Gas systems use reverse left hand threads on the manifold tube 6 Refer to Gas Piping section Figure 5 and disconnect the ground joint union in the gas piping Disconnect the remaining pipe...

Page 29: ...roubleshooting Table section 2 See Pilot Light Troubleshooting Flowchart section 3 Seat connector firmly in socket 4 Bleed the air from the gas line 5 Check with gas utility company 6 Check with gas u...

Page 30: ...at COMBUSTION ODORS 1 Insufficient secondary air 2 Flue clogged 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean locate source...

Page 31: ...wer switch on the gas control valve to the OFF position and unplug the power cord from the power outlet 1 Attempt to depress the TCO door switch button see figure 27 If the TCO door switch button depr...

Page 32: ...e electrode flame sense rod replace the igniter pilot assembly Follow the directions on page 27 to re install the burner assembly into the combustion chamber Follow the instructions for lighting on pa...

Page 33: ...alve Open Is Main Flame Sensed Is Demand for Heat Satisfied Pilot Main Valve De Energize Is Flame Sensed Damper Energizes and Closes Will not light 8 4 flash error code See Corrective Action Table on...

Page 34: ...List Item No Parts Description 1 DRAFT HOOD 2 FLUE DAMPER 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE L...

Page 35: ...assembly which contains the manifold tube gasket door pilot igniter flame sensor assembly manifold component block with retainer clip thermal switch and pilot tube Natural Gas Low Nox Item 14B Manifol...

Page 36: ...36 NOTES...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...ntaminated atmosphere used with factory approved anode s installed in its original installation location in the United States its territories or possessions and Canada sized in accordance with proper...

Page 40: ...OF USE OF THE UNIT INCONVENIENCE LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS...

Reviews: