background image

Maintenance

Model SWC Concealed Sprinklers should be inspected 

quarterly and the sprinkler maintained in accordance with 
NFPA 25.  Do not clean sprinklers with soap and water, 
ammonia or any other cleaning fluids.  Remove dust by using 
a soft brush or gentle vacuuming.  Remove any sprinkler cover 
plate assembly, which has been painted (other than factory 
applied) or damaged in any way.  A stock of spare sprinklers 
should be maintained to allow quick replacement of damaged 
or operated sprinklers.  Prior to installation, sprinklers should 
be maintained in their original cartons and packaging until 
used to minimize the potential for damage to sprinklers that 
would cause improper operation or non-operation.

Model SWC Concealed Quick Response
Extended Coverage Horizontal

Sidewall Sprinkler Specification

Sprinklers shall be a [quick response – cULus Listed] 

[quick response - New York City MEA Approved (258-93-E)] 
extended coverage concealed horizontal sprinkler with EC-9 
deflector and adjustable cover plate for light hazard, interior, 
non-corrosive applications.  Sprinklers to be of bronze frame 
construction with brass cover plate and copper alloy retainer 
flange assembly. Water seal assembly shall consist of a PTFE 
coated Belleville spring washer and machined brass cup 
with 3 mm glass bulb containing no plastic parts. Method of 
attaching the cover plate to the sprinkler cup shall be a push-
on and thread-off design allowing a ½” cover plate adjustment.  
Sprinklers shall have a nominal K-factor of 8.0 (115.3), and 
¾” NPT thread.  Sprinkler temperature rating shall be 135°F 
(57°C) with a cover plate temperature rating of 135°F (57°C).  
Sprinklers shall be capable of a maximum coverage area of 
16 ft. x 22 ft. (4.9 m x 6.7 m), with a minimum lateral spacing 
of 8 ft. (2.4 m).  Rated working pressure shall be 300 psi (20,7 
bar).  A plastic protective cap shall be provided and factory 
installed inside the sprinkler cup to protect the sprinkler from 
damage, which could occur during construction before the 

cover plate is installed.  Standard cover plate finish: [White] 

[Custom Color– specify]. Concealed horizontal sidewall 
sprinklers shall be Reliable Model SWC, SIN R5962 (Bulletin 
163).

UL Listing Category

Sprinklers, Automatic and Open
Quick Response Extended coverage Sprinklers

Ordering Information

Specify:

1.  Model SWC Sidewall Concealer

® 

2.  Cover Plate Finish.

Installation Wrench

Model GFR1 Sprinkler Wrench

Installation Aid

A protective plastic cap is included for use during installa-
tion. 

Cover Plate Finishes

(1)

Standard Finishes

White Paint

Special Application Finishes

Bronze
Black Paint
Flat White Paint

(1)

 Other colors and finishes are available.  Consult factory for details.

Note:

 Paint or any other coatings applied over the factory 

finish will void all approvals and warranties.

Figure 1

The Reliable Automatic Sprinkler Co., Inc.

(800) 431-1588    

Sales Offices

(800) 848-6051    

Sales Fax

(914) 829-2042    

Corporate Offices

www.reliablesprinkler.com   Internet Address

Manufactured by

Recycled

Paper

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 05/21

P/N 9999970167

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual 

Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified 

and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.