background image

3

008FG01C

Fig. 1 – Model N252 EC Pendent

FM Data Sheet 2-0, Ceiling to center of thermal element: 
Maximum 12”

Fig. 2 – Model N Wrench

FRAME ARM

LINK ASSEMBLY

MODEL N WRENCH

Technical Data

Sprinkler 

Model

Type

Temperature 

Rating

Maximum 

Ambient 

Ceiling Temp.

Nominal 

K-Factor 

gpm/psi

1

/

2

  

(l/min.bar

-0.5

)

Orifice 

Size

Thread 

Size

Sprinkler Ht. 

inch (mm)

Sprinkler 

Identification 

Number (SIN)

°F

°C

°F

°C

N252 EC

Pendent

165

74

100

38

25.2 (363)

1”

1” NPT (R1)

3.6 (91.5)

RA0842

212

100

150

66

Installation

Model N252 sprinklers are to be installed as shown. When 

handling sprinklers, hold sprinklers only on frame arms and do 
not apply any force on the link assembly. For installing Model 
N252 EC pendent sprinklers use only the Model N wrench (ref. 
Fig. 2). The N1 wrench may also be utilized in all non-recessed 
installations (Fig. 3). Use of wrenches other than that specified 
may damage these sprinklers. Sprinklers should be tightened 
between 22 to 30 ft-lb (29.8 - 40.7 N-m) torque. Sprinklers 
not tightened to recommended torque may cause leakage 
or impairment of the sprinklers. Damaged sprinklers must be 
replaced immediately.

Maintenance

The Model N252 EC Pendent Control Mode Specific 

Application Sprinklers should be inspected and the sprinkler 
system maintained in accordance with NFPA 25, and local 
jurisdictional requirements. Do not clean sprinklers with soap 
and water, ammonia, or any other cleaning fluids or solvents. 
Remove dust by using a soft brush or gentle vacuuming. Remove 
any sprinkler that has been painted (other than factory-applied) 
or otherwise altered after leaving the factory. A stock of spare 
sprinklers should be maintained to allow quick replacement of 
damaged or operated sprinklers. Prior to installation, sprinklers 
should be maintained in the original cartons and packaging 
until used to minimize the potential for damage to sprinkler that 
would cause improper operation or non-operation. 

CEILING OR UNDERSIDE OF ROOF DECK

 12”  

[304.80 mm]

1.85” [47.0 mm] 

Fig. 3 – Model N1 Wrench

Use only the Model N (Fig. 2) or N1 

(Fig. 3) wrenches for installation and 
removal of the sprinkler. Any other 
type of wrench may damage the 
sprinkler.

Summary of Contents for N252 EC Pendent

Page 1: ... Fire pump size Tank size 6 165 F 74 C and 212 F 100 C temperature ratings 7 Maximum deflector distance from ceiling is 131 2 343 mm 12 305 mm to center line of thermal element 8 This is a Quick Response CMSA sprinkler that meets the requirements of IFC 2015 for the elimination of smoke heat vents in storage occupancies 9 US Pat No 7 624 812 Other Patents Pending See Design Criteria for details Ta...

Page 2: ...sprinkler systems or pre action sprinkler systems whose sprinkler protection design can be based on the equivalent of a wet pipe system are acceptable 4 Sprinkler Spacing The minimum and maximum linear distances between sprinklers are 10 ft 3 1 m and 14 ft 4 2 m respectively for ceiling heights up to and including 30 ft 9 0 m For ceiling heights over 30 ft 9 0 m and up to 35 ft 10 7 m the maximum ...

Page 3: ...lers not tightened to recommended torque may cause leakage or impairment of the sprinklers Damaged sprinklers must be replaced immediately Maintenance The Model N252 EC Pendent Control Mode Specific Application Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 and local jurisdictional requirements Do not clean sprinklers with soap and water ammonia or an...

Page 4: ...anded Plastics Cartoned Expanded Plastics Uncartoned Unexpanded Plastics Uncartoned Expanded Plastics 10 3 0 N A N A 6 20 1 4 10 7 0 5 See Note 4 10 7 0 5 See Note 4 15 4 5 N A 6 20 1 4 6 20 1 4 12 7 0 5 See Note 4 8 20 1 4 See Note 4 20 6 0 6 20 1 4 6 20 1 4 6 20 1 4 8 20 1 4 See Note 4 8 40 2 8 See Note 4 25 7 5 6 20 1 4 6 20 1 4 6 20 1 4 8 40 2 8 See Note 4 12 40 2 8 See Note 4 30 9 0 6 25 1 7 ...

Reviews: