Product Description

The Model N252 EC Pendent are Control Mode Specific 

Application Extended Coverage Sprinklers for Storage 
Applications. This includes protection of the storage and 
display of Class I through IV commodities encapsulated or 
unencapsulated, cartoned unexpanded plastics. The Model 
N252 EC sprinklers offer maximum coverage areas up to 14 ft 
by 14 ft (196 ft

2

) as compared to ESFR or Standard Coverage 

Control Mode or Control Mode Specific Application sprinklers 
with maximum coverage of 100 ft

2

  (9 m

2

). This offers the 

advantage of decreasing the number of required sprinklers, 
reducing labor and material costs. The Model N252 EC Pendent 
Control Mode Specific Application Sprinklers is designed for 
use in ceiling only sprinkler systems with no in-rack sprinklers 
required. 

Operation

The Reliable Model N252 Extended Coverage Pendent 

Control Mode Specific Application Storage Sprinklers utilize a 
levered fusible alloy solder link. When the rated temperature 
is reached, the solder melts and the two link halves separate 
allowing sprinkler to operate and water to flow.
FM Approved for the following:

1. Application:

 These FM Approved extended coverage 

CMSA automatic sprinklers may be used to protect Class 
1 through 4, cartoned unexpanded plastic commodities 
under ceilings up to and including 35 ft (10.7 m) high. They 
may be used to protect any storage arrangement outlined 
in Data Sheet 8-9, however portable racks must meet the 
guidelines required to be considered open-frame racks. 
Maintain a minimum clearance of 3 ft (0.9 m) between the 
top of storage and the sprinkler deflector.

Temperature Rating:

 The Reliable Model N252 EC 

sprinkler is available in nominal temperature ratings of either 
165 °F (70 °C) or 212 °F (100 °C). Use the nominally rated 
165 °F (70 °C) sprinkler for all acceptable applications 
unless the ambient temperature of the protected occupancy 
requires the temperature rating to be 212 °F (100 °C).

2.  Hydraulic Design:

 Base the design for these automatic 

sprinklers as follows:

Solid-Piled, Palletized, Shelf or Bin-Box and Open-
Frame Racks:

 See table 1.

Storage Racks Equipped With Solid Shelves:

 Base the 

design of the ceiling sprinkler system as outlined above 
for open-frame racks, however base the need for, as well 
as the design of, in-rack sprinkler protection the same 
as what is required for K16.8 (K240) CMSA sprinklers. 

Shape of Operating Area:

 

Base the shape of the operating 

area on a 1.2 shape factor for ceiling slopes up to 5° or a 
1.4 shape factor for ceilings having a higher slope (up to 
10° maximum).

3.  System Type: 

Wet-pipe sprinkler systems or pre-action 

sprinkler systems, whose sprinkler protection design can 
be based on the equivalent of a wet-pipe system, are 
acceptable.

4.  Sprinkler Spacing: 

The minimum and maximum linear 

distances between sprinklers are 10 ft (3.1 m) and 14 ft 
(4.2 m) respectively for ceiling heights up to and including 
30 ft (9.0 m). For ceiling heights over 30 ft (9.0 m) and up to 
35 ft (10.7 m) the maximum linear spacing of the sprinkler 
is reduced to 12 ft (3.6 m). The minimum and maximum 
area of coverage per sprinkler is 100 ft

2

 (9 m

2

) and 196 ft

2

 

(18 m

2

) respectively for ceiling heights up to and including 

30 ft (9.0 m). For ceiling heights over 30 ft (9.0 m) and up to 
35 ft (10.7 m) the maximum area spacing of the sprinkler is 
reduced to 144 ft

2

 (13.5 m

2

).

5. Sprinkler Location from Walls:

 Locate the 

automatic sprinklers with respect to walls, 
measured perpendicular to the wall, as follows: 
Minimum Horizontal Distance: 4” (100 mm). 
Maximum Horizontal Distance unless indicated otherwise 
in either the occupancy-specific data sheet or the Approval 
Guide:

a.  Wall Angle Greater Than 90°: 7 ft (2.1 m) for 

ceilings up to 30 ft (9.0 m) high or 6 ft (1.8 m) for 
ceilings over 30 ft (9.0 m) and up to 35 ft (10.7 m) 
high.

b.  Wall Angle Equal to or Less Than 90°: 10 ft (3.0 m) 

for ceilings up to 30 ft (9.0 m) high or 8 ft (2.4 m) 
for ceilings over 30 ft (9.0 m) and up to 35 ft 
(10.7 m) high.

6.

 

Sprinkler Location from Ceilings:

 Locate the automatic 

sprinklers with respect to ceilings in accordance with Data 
Sheet 2-0. However, the minimum vertical distance below a 
ceiling can be reduced to 2” (50 mm) for smooth ceilings or 
4” (100 mm) for non smooth ceilings.

7.

 

Obstructions:

 Use the obstruction guidelines outlined 

in D.S. 2-0 for extended coverage automatic sprinklers 
in regards to the umbrella pattern. In addition, use the 
obstruction guidelines outlined in D.S. 2-0 for pendent 
automatic sprinklers in regards to obstructions located 
below the automatic sprinkler, except that an individual 
object up to a maximum width of 1.25 in; (31 mm) can be 
tolerated less than 12” (300 mm) horizontally away from 
the sprinkler as long as the object is located at least16” 
(400 mm) vertically below the sprinkler. All other design 
details should be in accordance with Data Sheet 8-9. All 
other installation details should be in accordance with Data 
Sheet 2-0.

8.

  FM Global considers this a “Quick Response” Extended 

Coverage Sprinkler for use in Data Sheet 8-9.

9.

 

For installations governed by NFPA #13 (2013)

, the 

N252EC fire sprinkler meets the definition of Control Mode 
Specific Application (CMSA) Sprinklers and is approved 
for installation under chapter 21. Section 3.6.4.1. Section 
8.11.1.1 states that CMSA sprinklers shall be installed 
in accordance with Section 8.5 and the manufacturer’s 
installation instructions. 

.

Summary of Contents for N252 EC Pendent

Page 1: ... Fire pump size Tank size 6 165 F 74 C and 212 F 100 C temperature ratings 7 Maximum deflector distance from ceiling is 131 2 343 mm 12 305 mm to center line of thermal element 8 This is a Quick Response CMSA sprinkler that meets the requirements of IFC 2015 for the elimination of smoke heat vents in storage occupancies 9 US Pat No 7 624 812 Other Patents Pending See Design Criteria for details Ta...

Page 2: ...sprinkler systems or pre action sprinkler systems whose sprinkler protection design can be based on the equivalent of a wet pipe system are acceptable 4 Sprinkler Spacing The minimum and maximum linear distances between sprinklers are 10 ft 3 1 m and 14 ft 4 2 m respectively for ceiling heights up to and including 30 ft 9 0 m For ceiling heights over 30 ft 9 0 m and up to 35 ft 10 7 m the maximum ...

Page 3: ...lers not tightened to recommended torque may cause leakage or impairment of the sprinklers Damaged sprinklers must be replaced immediately Maintenance The Model N252 EC Pendent Control Mode Specific Application Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 and local jurisdictional requirements Do not clean sprinklers with soap and water ammonia or an...

Page 4: ...anded Plastics Cartoned Expanded Plastics Uncartoned Unexpanded Plastics Uncartoned Expanded Plastics 10 3 0 N A N A 6 20 1 4 10 7 0 5 See Note 4 10 7 0 5 See Note 4 15 4 5 N A 6 20 1 4 6 20 1 4 12 7 0 5 See Note 4 8 20 1 4 See Note 4 20 6 0 6 20 1 4 6 20 1 4 6 20 1 4 8 20 1 4 See Note 4 8 40 2 8 See Note 4 25 7 5 6 20 1 4 6 20 1 4 6 20 1 4 8 40 2 8 See Note 4 12 40 2 8 See Note 4 30 9 0 6 25 1 7 ...

Reviews: