The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 11/13
P/N 9999970181
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Technical Data
Sprinkler Model
Thread
Size
Ori
fi
ce
Size
Temperature
Rating
Max.
Ambient
Temp.
Maximum
Sprinkler
Spacing
Maximum
Coverage
Area
Approvals
Sprinkler
Identi
fi
cation
Number
(SIN)
°F
°C
°F
°C
GFR VELO–ECOH
Upright
(1)
¾” NPT
(R¾)
0.70”
(18mm)
165
74
100
38
20 ft.
(6.1 m)
400 ft.
2
(37.2 m
2
)
1,2
R6553
212
100
150
66
(1)
Minimum Spacing Between GFR VELO-ECOH Upright Sprinklers is 12 feet (3.6m).
Minimum Flow Requirements
Spacing
(1)
Coverage
Area
NFPA 13 - 1991 & Later
NFPA 13 - 1989 & Earlier
Nominal
K
Factor
Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 3
0.15 gpm/ft
2
(6.1L/min/m
2
)
Density
0.20 gpm/ft
2
(8.1 L/min/m
2
)
Density
0.16 gpm/ft
2
(6.5 L/min/m
2
)
Density
0.19 gpm/ft
2
(7.7 L/min/m
2
)
Density
0.21 gpm/ft
2
(8.25 L/min/m
2
)
Density
Flow
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pressure
US Metric
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
20 ft. x 20 ft.
(6.1m x 6.1m)
400 ft.
2
(37.2m
2
)
60.0
(227)
18.4
(1,3)
80.0
(302)
32.7
(2,3)
64.0
(242)
20.9
(1,5)
76.0
(287)
29.5
(2,1)
84.0
(318)
36.0
(2,5)
14
200
(1)
For spacing and coverage areas less than 20 ft. x 20 ft. (6.1m x 6.1m) and 400 ft
2
, the flows and
pressures for the 20 ft. x 20 ft. (6.1m x 6.1m) spacing and 400 ft
2
(37.2m
2
) area must be used.
Ordering Information
Specify:
1. Sprinkler Model
2. Temperature Rating
3. Sprinkler Finish
Finishes
Standard Finishes
Bronze
Chrome Plated
(1)
Other colors and finishes are available
on special order. Consult factory for
details.
Model H Sprinkler Wrench
Use Model H Wrench for Model GFR VELO–ECOH
Upright Sprinkler removal and installation.
Maintenance
Model GFR VELO-ECOH Upright Extended Coverage
Sprinklers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle vac-
uuming. Remove any sprinkler that has been painted (other
than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non-operation.
Patents: U.S. Patent No. 6,446,732