background image

The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model GFR VELO–ECOH
Extended Coverage
Ordinary Hazard 
Upright Sprinkler

Bulletin 165 Rev

. E

Bulletin 165 Rev. E 

Model GFR VELO–ECOH Upright
(SIN R6553) Standard Response

Features

1. Provides Extended Coverage Ordinary 

Hazard protection to 400 ft

2

 (37.2m

2

) per 

sprinkler.

2. Very Extra Large Orifice of Nominal K=14.0 

(200) results in low pressures.

3. 212°F (100°C) and 165°F (74°C) temperature 

rating.

4. Available in brass, chrome, black plated and 

polyester coated finishes.

5. Can be used for all editions of NFPA 13.

Listings & Approvals

1.  Listed by Underwriters Laboratories, and UL certified 

for Canada (cULus)

2.  NYC MEA 258-93-E

UL Listing Category

Sprinklers, Automatic and Open Extended Coverage 
Sprinklers— Ordinary Hazard Occupancy

UL Guide Number

VNIV

Product Description

The Reliable Model  VELO-ECOH Extended Coverage Sprin-

kler has a very extra large orifice, Nominal K=14.0 (200).  It can 
provide Ordinary Hazard protection to 400 ft

2

 (37.2 m

2

 ) at lower 

pressures than an XLO which has a K=11.2 (160.2). 

The Model GFR VELO-ECOH Sprinklers provide protection in 

Ordinary Hazard Group 1 and 2 Occupancies to 400 ft

(37.2m

2

per sprinkler when the system is designed to NFPA 13 hydraulic 
density requirements.

Model GFR VELO-ECOH Upright Sprinklers are to be installed 

according to the design criteria shown in this bulletin. The use 
of ECOH sprinklers can provide opportunities for lower system 
installation costs by requiring fewer sprinklers, less piping and 
reduced labor.

Model GFR VELO-ECOH Sprinklers use a levered fusible alloy 

solder link.

Model GFR VELO-ECOH Upright

Design Criteria

Reliable Model GFR VELO-ECOH sprinklers are to be used 

in systems designed and installed in accordance with NFPA 13 
and all other local codes and ordinances. The following design 
criteria also apply:
•  Minimum sprinkler spacing is 12’ (3.6 m).
•  Minimum flow requirement is shown in the Flow Re-

quirements Table on the reverse side.

•  ECOH sprinklers are only to be used in systems hy-

draulically designed per NFPA 13, and for a minimum 
area of 1,500 ft

2

 (139.4 m

2

) or 5 sprinklers, whichever 

is greater.

•  Deflector to commodity clearance shall be a minimum 

of 18” (457mm).

•  ECOH sprinklers shall be installed in unobstructed 

constructions as defined in NFPA 13.

•  Sprinklers can be installed under a sloping ceiling not 

exceeding 2” (50.8mm) of rise in 12” (305mm).

•  Maximum working pressure is 175 psi (12 bar) at the 

sprinkler.

Reviews: