Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model G6-80 K8.0 (115 metric)
Concealed Quick Response
Extended Coverage Light Hazard
Horizontal Sidewall Sprinkler
(SIN RA4762)

Bulletin 047 Rev

. A

Bulletin 047 Rev. A

Coverage to 18 ft. x  22 ft.
(5.5m x 6.7m), 16 ft. x 24 ft.
(4.9m x 7.3m). 

Features:

1.  Flat cover plate (Solid or Perforated).
2.  K-factor of 8.0 (115 metric).
3.  Listed as quick-response, extended coverage for 

Light Hazard occupancies.

4.  Sprinkler assembly and cover plate packaged 

separately.

5.  ¼” (6.3mm) cover plate adjustment.
6.  Cover plate available in in a wide variety of col-

ors and finishes.

Approval Organizations

1.  Listed for use in Light Hazard occupancies by 

Underwriters Laboratories Inc. and UL certified 
for Canada (cULus).

UL Listing Category

Sprinklers, Automatic and Open
Quick Response Extended Coverage Sprinklers

Product Description

The Reliable Model G6-80 Concealed Quick Response 

Extended Coverage Horizontal Sidewall Sprinkler is an at-
tractive, concealed sprinkler assembly that utilizes a push-
on/pull-off cover plate assembly. The sprinkler assembly is 
shipped with a protective cap.  

 The flat cover plate is attached to the skirt using 135°F 

(57°C) ordinary temperature classification solder.  The sprin-
kler is installed into the sprinkler fitting using the Model G6 
Sprinkler Wrench.  

When the ambient temperature rises, the solder holding 

the cover plate melts, allowing the release of this part and 
thus exposing the sprinkler inside to the rising ambient tem-
perature.

The Model G6-80 utilizes a Quick Response soldered link.  

Quick-response sprinklers are designed to apply water to a 
fire sooner than standard-response sprinklers of the same 
temperature rating.

 The Model G6-80 sprinkler is listed for a maximum service 

pressure of 175 psi (12,0 bar).

Application and Installation

The Model G6-80 sprinkler is intended for installation in 

light hazard occupancies in accordance with NFPA 13.  This 
sprinkler is especially well-suited for use in non-corrosive 
environments in student dormitories, hotels, hospitals and 
care facilities.

Model G6-80 Concealed Horizontal Sidewall sprinklers 

utilize a sprinkler assembly with spring loaded deployable 
deflector feature.  The assembly is  completed by the instal-
lation of the attractive, 135°F (57°C) push-on/pull-off cover 
plate assembly, which provides ¼” (6.3mm) of adjustment.

Apply a Teflon* - based thread sealant to the sprinkler 

threads.  After a 2 

5

/

8

” (66.7mm) diameter hole is cut in the 

wall, the sprinkler is installed and properly oriented with the 
Model G6 Wrench, as follows:

Do not remove factory installed plastic protective cap 

since it is sized to fit inside the G6 wrench. Note that the 
sprinkler can only mate  when the sprinkler’s deflector ori-
entation tab (Fig. 1) is aligned with wrench’s key-way. The 
G6 Wrench has a bubble level pad and TOP to assist the 
installer in properly orienting the sprinkler. Final leveling can 
be done after leak proof joint is obtained with a minimum to 
maximum torque of 14 to 20 ft-lbs (19 to 27 N.m). Do not 
attempt to compensate for improper rough in dimensions of 
fitting by over tightening the sprinkler assembly, but readjust 
the sprinkler fitting instead. Leave the protective cap on to 
assure sprinkler protection while the wall is plastered, wall-
papered or painted.

Concealed cover plate/cup assemblies are listed only for 

use with specific sprinklers.  The use of any other concealed 
cover plate/cup assembly with the Model G6-80 Horizontal 
Sidewall Sprinkler or the use of this dedicated concealed 
cover plate assembly on any sprinkler with which it is not 
specifically listed will void all guarantees, warranties, listings 
and approvals.
* DuPont Registered Trademark

Summary of Contents for G6-80 K8.0

Page 1: ... for a maximum service pressure of 175 psi 12 0 bar Application and Installation The Model G6 80 sprinkler is intended for installation in light hazard occupancies in accordance with NFPA 13 This sprinkler is especially well suited for use in non corrosive environments in student dormitories hotels hospitals and care facilities Model G6 80 Concealed Horizontal Sidewall sprinklers utilize a sprinkl...

Page 2: ...05 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 4 6 102 152 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 6 12 152 305 39 147 6 23 8 1 6 16 x 16 4 9 x 4 9 4 12 102 305 26 98 4 10 6 0 7 16 x 18 4 9 x 5 5 4 12 102 305 29 109 8 13 1 0 9 16 x 20 4 9 x 6 1 4 12 102 305 32 121 1 16 0 1 1 16 x 22 4 9 x 6 7 4 12 102 305 36 136 2 20 2 1 4 16 x 24 4 9 x 7 3 4 12 102 305 39 147 6 23 8 1 6 18 x 18 5 5 x 5 5 4 12 102 305 33 124 ...

Page 3: ...to the sprinkler cup shall be a push on and pull off design al lowing a cover plate adjustment Sprinklers shall have a nominal K factor of 8 0 115 metric Sprinkler temperature rating shall be 165 F 74 C with a cover plate temperature rating of 135 F 57 C Sprinklers shall be capable of a max imum coverage area of 16 ft x 24 ft 4 9 m x 7 4 m or 18 ft x 22 ft 5 5 m x 6 7 m with a minimum lateral spac...

Page 4: ...roughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrica...

Reviews: