Ordering Information

Specify:
1.  Sprinkler: [Model F3-80 Dry Pendent SIN RA6012] 

[Model F3-80 Dry Horizontal Sidewall SIN RA6032]

2.  Escutcheon/Cover Plate: [None][Standard escutch-

eon][Model HB extended escutcheon][Model FP re-
cessed escutcheon][Model CCP cover plate – pen-
dent only]

3.  Inlet Threads: [1” NPT][ISO7-1R1]
4.  Inlet Fitting: [Long – Standard Inlet Fitting][Short “PL” 

– Wet Pipe Systems only]

5.  Sprinkler Temperature Rating: See Temperature Rat-

ings table

6.  Sprinkler Finish: See Finishes Table
7.  Escutcheon/Cover Plate Finish: See Finishes Table
8.  Length: “A” Dimension (face of tee to face of ceiling 

or wall) in ¼” (6 mm) increments – See Fig. 1 through 
Fig. 7

Note:

The “A” dimension is based on a nominally gauged pipe 
thread “make-up” of .600” (15mm) per ANSI B2.1 [approxi-
mately 7 ½ threads].

Installation Wrench

Model F3R Sprinkler Wrench (Standard and HB escutcheons)
Model XLO2 Sprinkler Wrench (FP Recessed and CCP 
Concealed)

Installation Data

Sprinkler Model

Escutcheon or Cover Plate

Suggested Hole Diameter in Wall or Ceiling

Installation Wrench

F3-80 Dry

Standard Escutcheon

2-1/8” (54 mm)

F3R

HB Extended Escutcheon

2-1/2” (64 mm)

FP Recessed Escutcheon

2-1/2” (64 mm)

XLO2

CCP Cover Plate (Pendent Only)

Maintenance

The Model F3-80 Dry Sprinklers should be inspected and the 
sprinkler system maintained in accordance with NFPA 25. 
Do not remove the factory applied thermally sensitive wax 
fillet between the bulb supporting cup and the wrenching 
boss. Do not replace this wax with a substitute substance.
An Alternate substance may interfere with proper operation 
of the sprinkler. Do not clean sprinklers with soap and water, 
ammonia or any other cleaning fluids. Remove dust by us-
ing a soft brush or gently vacuuming. Replace any sprin-
kler which has been painted (other than factory applied) or 
damaged in any way. A stock of spare sprinklers should be 
maintained to allow quick replacement of damaged or op-
erated sprinklers. Prior to installation, sprinklers should be 
maintained in the original cartons and packaging until used 
to minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Reliable Automatic Sprinkler Co., Inc.

(800) 431-1588    

Sales Offices

(800) 848-6051    

Sales Fax

(914) 829-2042    

Corporate Offices

www.reliablesprinkler.com   Internet Address

Manufactured by

Recycled

Paper

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 03/22

P/N 9999970500

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 100 years.

Summary of Contents for F3-80 Dry Pendent

Page 1: ...able in this Bulletin for available temperature rat ings Model F3 80 Dry sprinklers are intended for installa tion on wet pipe dry pipe or preaction sprinkler systems in accordance with NFPA 13 Model...

Page 2: ...Listing per Local Law 33 2007 NYC Technical Data Maximum Listed and Approved Working Pressure 175 psi 12 bar Nominal K Factor 8 0 gpm psi1 2 115 L min bar1 2 Temperature Classification Glass Bulb Col...

Page 3: ...nations Standard Escutcheon Sprinkler Escutcheon 3 4 Bronze Polished Stainless Bronze Laquered Brass Chrome Polished Stainless White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custo...

Page 4: ...White Polyester Black Polyester 1 Black Polyester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Stainless Steel Wax 1 2 Chrome Lead 1 Stainless Steel Wax over Lead 1 2 Stai...

Page 5: ...Recessed Sprinkler 1 Escutcheon 3 4 Bronze Brass Chrome Chrome White Polyester 2 White Polyester Black Polyester 2 Black Polyester Custom Color Polyester 2 Custom Color Polyester Electroless Nickel P...

Page 6: ...inkler with the Model CCP cover plate in ceilings which have positive pressure in the space above Fig 4 6 Finish Combinations CCP Concealed Sprinkler 1 Cover Plate 2 Bronze White Polyester Chrome Brig...

Page 7: ...mm in 1 4 6mm increments for 3 4 connections Finish Combinations Standard Escutcheon Sprinkler Escutcheon 3 4 Bronze Polished Stainless Bronze Laquered Brass Chrome Polished Stainless White Polyester...

Page 8: ...Bronze Chrome Chrome Chrome White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Stainless Steel Wax 1 2 Chrome...

Page 9: ...mension adjustment range Fig 7 Finish Combinations FP Recessed Sprinkler 1 Escutcheon 3 4 Bronze Brass Chrome Chrome White Polyester 2 White Polyester Black Polyester 2 Black Polyester Custom Color Po...

Page 10: ...10 Fig 8...

Page 11: ...Fig 9 11...

Page 12: ...Fig 11 Model XLO2 Wrench Fig 10 Model F3R Wrench 12...

Page 13: ...Fig 12 13...

Page 14: ...rench specified in the Installation Data table The Model F3R wrenches are designed to be inserted into the groves in the sprinkler s wrench boss as shown in Fig 10 The Model XLO2 wrench is designed to...

Page 15: ...o not remove the factory applied thermally sensitive wax fillet between the bulb supporting cup and the wrenching boss Do not replace this wax with a substitute substance An Alternate substance may in...

Reviews: