background image

Maintenance

Reliable Model F1XLH and F1FRXLH series sprinklers should be 

inspected and the sprinkler system maintained in accordance 
with NFPA 25, as well as the requirements of any Authorities 

Having Jurisdiction.

Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the potential 
for damage to sprinklers that could cause improper operation or 
non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 

without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 

applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 
operation or non-operation during a fire event.

P/N 9999970608

Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify the following when ordering:

•  Sprinkler

[Model F1XLH] [Model F1FRXLH]

•  Deflector/Orientation

[Upright] [Pendent]

•  Temperature Rating

See individual sprinkler pages

•  Sprinkler Finish

See Table B

•  Sprinkler Wrench 

[Model W2] [Model W4 (Recessed)] 
[Model J (with guard installed)]

•  Guards and Shields

See individual sprinkler pages

Installation

Model F1XLH and F1FRXLH Series sprinklers must be installed 
with the Reliable sprinkler installation wrench identified in this 
Bulletin. Any other wrench may damage the sprinkler.  The 

Models W2 and W4 wrenches have two sets of jaws.  Use the 

smallest set of jaws that fit on the wrench flats of the sprinkler.  

A leak tight sprinkler joint can be obtained with a torque of 8 

to 18 lb-ft (11 to 24 N

.

m). Do not tighten sprinklers over the 

maximum recommended installation torque. Exceeding the 
maximum recommended installation torque may cause leakage 
or impairment of the sprinkler.

Glass bulb sprinklers have orange bulb protectors or protective 
caps to minimize bulb damage during shipping, handling and 

installation. Reliable sprinkler installation wrenches are designed 

to install sprinklers with bulb protectors in place. Remove the 
bulb protector at the time when the sprinkler system is placed in 
service for fire protection. Removal of the bulb protector before 
this time may leave the bulb vulnerable to damage. Remove bulb 

protectors by undoing the clasp by hand. Do not use tools to 

remove bulb protectors.

Wrenches

Figure 5

Model W2 Wrench

Model W4 Wrench

Model J Wrench

Bulletin 184
January 2022

Page 7 of 7

www.reliablesprinkler.com

Summary of Contents for F1XLH Series

Page 1: ...ire sprinklers utilizing a sensitive 3 0 mm thermal glass bulb element These sprinklers are characterized by a 4 2 60 metric K factor with a pintle on the deflector Table A provides a summary of the a...

Page 2: ...g Washer Nickel with PTFE Load Screw Copper Alloy Deflector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286...

Page 3: ...itivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C Guards and Shields F7 Guard F8 Guard with Shield Recessed Escutcheons F1 cULus F2 cULu...

Page 4: ...Sealing Washer Nickel with PTFE Load Screw Copper Alloy Deflector Brass Alloy Sprinkler Finishes See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C...

Page 5: ...See Table B Sensitivity Quick Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards and Shields F7 Guard F8 Guard with Shield Recessed Escutcheons F1 cULus F2 cUL...

Page 6: ...available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP an...

Page 7: ...er Finish See Table B Sprinkler Wrench Model W2 Model W4 Recessed Model J with guard installed Guards and Shields See individual sprinkler pages Installation Model F1XLH and F1FRXLH Series sprinklers...

Reviews: