Reliable F1FR40 Bulletin Download Page 4

Standard Finishes

Special Application Finishes

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Bronze

Brass

Electroless Nickel PTFE

Bright Brass

Chrome Plated

Chrome Plated

Bright Brass

(4)

Black Plated

White Polyester

White Polyester

Black Plated

Black Paint

Black Paint

Off White

Off White

Chrome Dull

Chrome Dull

Notes:

1.  Other finishes and colors are available on special order. Consult your Reliable sales representative for details.
2.  Paint or any other coating applied over the factory finish will void all approvals and warranties.
3.  The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring.
4.  For 200°F (93°C) maximum temperature rated sprinklers only.

Sprinkler and Escutcheon Finishes

(1)(2)

Table B

Maintenance

Reliable Model F1FR series sprinklers should be inspected 
and the sprinkler system maintained in accordance with NFPA 
25, as well as the requirements of any Authorities Having 
Jurisdiction.
Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the 
potential for damage to sprinklers that could cause improper 
operation or non-operation.
Do not clean sprinklers with soap and water, ammonia 
liquid or any other cleaning fluids. Remove dust by gentle 
vacuuming without touching the sprinkler.
Replace any sprinkler which has been painted (other than 
factory applied). A stock of spare sprinklers should be 
maintained to allow quick replacement of damaged or 
operated sprinklers.  Failure to properly maintain sprinklers 
may result in inadvertent operation or non-operation during a 
fire event.

Guarantee

For the guarantee, terms, and conditions, visit www.
reliablesprinkler.com.

Ordering Information

F1FR40 Ordering Information 

Specify the following when ordering:

• Deflector/Orientation

Pendent

      Pendent - FP

• Temperature Rating

• Sprinkler Finish

See Table B

• Recessed Escutcheon*

   F1
   F2
   FP

• Escutcheon Finish

See Table B

• Sprinkler Wrench 

Model W-2 (pendent)
Model W-4 (recessed pendent)

*Note:

 286°F (141°C) sprinklers are not listed to be used 

recessed.

P/N 9999970607 

Bulletin 183
October 2020

Page 4 of 4

www.reliablesprinkler.com

Reviews: