Recessed Installation: Pendent Sprinklers

Figure 2

 Wrenches

Model W2 (pendent)

Model W4 (recessed pendent)

Installation

Model F1FR Series sprinklers must be installed with the 
W2 (pendent) or W4 (recessed pendent) Reliable sprinkler 
installation wrench as identified in this Bulletin. Any other wrench 
may damage the sprinkler.  The Models W2 and W4 wrenches 
have two sets of jaws.  Use the smallest set of jaws that fit the 
wrench flats of the sprinkler.  A leak tight sprinkler joint can be 
obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not 
tighten sprinklers over the maximum recommended installation 
torque. Exceeding the maximum recommended installation 
torque may cause leakage or impairment of the sprinkler.

Both the Model W2 and W4 wrench have two sets of jaws. 
Use the smallest set of jaws that fit on the wrench flats of the 
sprinkler. The Model W4 wrench is used in conjunction with 
a nominal 1/2” square drive ratchet with a nominal 5” long 
extension (not provided). 

Glass bulb sprinklers have orange bulb protectors or protective 
caps to minimize bulb damage during shipping, handling 
and installation. Reliable sprinkler installation wrenches are 
designed to install sprinklers with bulb protectors in place. 
Remove the bulb protector at the time when the sprinkler 
system is placed in service for fire protection. Removal of the 
bulb protector before this time may leave the bulb vulnerable 
to damage. Remove bulb protectors by undoing the clasp by 
hand. Do not use tools to remove bulb protectors.

Bulletin 183
October 2020

Page 3 of 4

www.reliablesprinkler.com