background image

2.

Model F1FR Quick Response Extended Coverage Pendent Sprinkler 

Deflector: 

EC

Installation Wrench: 

Model D Sprinkler Wrench

Approval Type: 

Quick Response Extended Coverage-Light Hazard Occupancy

Installation Data:

Nominal 

Orifice

Thread 

Size

“K” Factor

Sprinkler 

Length

Temperature 

Rating

Approval

Organizations

Sprinkler 

Identification 

Number (SIN)

US

Metric

17

/

32

”   

(20mm)

¾” NPT  

(R¾)

8.0

115

2.2” 

(56.1mm)

135°F (57°C)
155°F (68°C)

1,2,3,4

R4842

Model F1FR Recessed Quick Response Extended Coverage Pendent Sprinkler 

Deflector: 

EC

Installation Wrench: 

Model GFR2 Sprinkler Wrench

Approval Type: 

Quick Response Extended Coverage-Light Hazard Occupancy

Installation Data:

Nominal 

Orifice

Thread 

Size

“K” Factor

Sprinkler 

Length

Temperature 

Rating

Approval

(1)

Organizations

Sprinkler 

Identification 

Number (SIN)

US

Metric

17

/

32

(20mm)

¾” NPT

(R¾)

8.0

115

2.2” 

(56.1mm)

135°F (57°C)
155°F (68°C)

1, 2, 3, 4

R4842

(1)

 Refer to escutcheon data table for dimensions.

COVERAGE AREA

Flow Rate

gpm (L/min)

Pressure, psi (bar)

Maximum

Coverage Area

Width x Length

ft. x ft. (m x m)

K = 8.0 (115)

26      (98.4)

10.6 (0,7)

16 x 16   (4.9 x 4.9)

33    (125.0)

17.0 (1,2)

18 x 18   (5.5 x 5.5)

40    (151.4)

25.0 (1,7)

20 x 20   (6.0 x 6.0) 

(2)

(2)

 UL/ULC Listed for both Pendent and Recessed Pendent at

   135°F (57°C) only.

Reviews: