background image

Models F1FR-FS56 and F1FR-FS42 Quick Response Pendent Sprinklers

Installation Wrench: 

Model W2 Sprinkler Wrench

Installation Data:

Sprinkler Type

Standard–Pendent (SSP)

Deflectors Marked to Indicate Position

K Factor 

Sprinkler

Height

Approval

Organizations

US

Metric

1/2” (15mm) Standard Orifice with 1/2” NPT Thread

5.6 

80

2.25” (57mm) 

VdS 

1/2” (15mm) Standard Orifice with R1/2 Thread

5.6 

80

2.25” (57mm) 

VdS 

3/8” (10mm) Standard Orifice with R1/2 Thread

4.2 

57

2.25” (57mm) 

VdS 

Pendent

Model F1FR-FS56 with shield

Models F1FR-FS56 and F1FR-FS42 Quick Response Pendent Sprinklers with shield

Installation Wrench: 

Model W4 Sprinkler Wrench

Installation Data:

Nominal

Orifice

Thread

Size

K Factor 

Sprinkler 

Height

Approval

Organizations

US 

Metric

1/2” (15mm) 

1/2” NPT 

5.6 

80 

2.25” (57mm) 

VdS 

1/2” (15mm) 

R1/2” BSPT 

5.6 

80 

2.25” (57mm) 

VdS 

3/8” (10mm) 

R1/2” BSPT 

4.2

57

2.25 (57mm)

VdS

Shield Data

Part No.

Approvals

“A”

Dimension

“B”

Dimension

“C”

Dimension

6999995574 

VdS

17

/

32

” 

(115mm)

15

/

16

” 

(49mm)

9

/

16

(14mm)

2.

Reviews: