background image

3.

Model F1FR-300 Quick Response Extended Coverage Recessed Horizontal Sidewall Sprinkler

Deflector: 

QREC-9

Installation Wrench: 

Model W4 Sprinkler Wrench

Approval Type: 

Quick Response Extended Coverage – Light Hazard Occupancy

Installation Data:

Nominal

Orifice

Size

Thread

Size

“K” Factor

Sprinkler 

Length

Approval

(2)

Organizations

Sprinkler

Identification

Number (SIN)

US

Metric

17

/

32

(20mm)

¾” NPT

(R¾)

8.0

115.3

2.95”

(75mm)

1, 2

R5962

(2)

Refer to Escutcheon Data Table for approvals and dimensions.

Installation Data:

COVERAGE AREA

Flow Rate

gpm (L/min)

Pressure

psi (bar)

Maximum

Coverage Area 
Width x Length

ft. x ft. (m x m)

Temperature

Rating

(1)

Deflector to Ceiling

Dimension
Min. - Max.

Inches (mm)

UL

UL

26     (98.4)

29   (109.8)
29   (109.8)
32   (121.1)
36   (136.3)
39   (147.6)

10.6   (0,7) 
13.1   (0,9)
13.1   (0,9)
16.0   (1,1)
20.2   (1,4)
23.8   (1,6)

16 x 16   (4.9 x 4.9) 
16 x 16   (4.9 x 4.9)
16 x 18   (4.9 x 5.5)
16 x 20   (4.9 x 6.0)
16 x 22   (4.9 x 6.7)
16 x 24   (4.9 x 7.3)

135°F   (57°C)

155°F   (68°C)

175°F   (78°C)

6 - 12   (153 - 305)
4 - 12   (102 - 305)
4 - 12   (102 - 305)
4 - 12   (102 - 305)
4 - 12   (102 - 305)
4 - 12   (102 - 305)

33 (124.9)
39 (147.6)
40 (151.4)
46 (174.1)
33 (124.9)
40 (151.4)
46 (174.1)

17.0 (1,2)
23.8 (1,6)
25.0 (1,7)

33.1 (2,25)

17.0 (1,2)
25.0 (1,7)

33.1 (2,25)

18 x 18 (5.5 x 5.5)
14 x 26 (4.3 x 7.9)
18 x 22 (5.5 x 6.7)
14 x 26 (4.3 x 7.9)
18 x 18 (5.5 x 5.5)
18 x 22 (5.5 x 6.7)
14 x 26 (4.3 x 7.9)

135°F   (57°C)
135°F   (57°C)
135°F   (57°C)
135°F   (57°C)
155°F   (68°C)
155°F   (68°C)
155°F   (68°C)

4 - 12 (102 -305)

4 - 6 (102 - 153)

4 - 12 (102 - 305)
6 - 12 (153 - 305)

4 -12 (102 - 305)

4 - 12 (102 - 305)
6 - 12 (153 - 305)

Reviews: