3.
Model F156 Vertical Sidewall Sprinkler
Installation Wrench:
Model D Sprinkler Wrench
Installation Position:
Upright or Pendent
Approval Type:
Light Hazard Occupancy
U.S. Patent No. 6,374,920
Sprinkler Type
Deflector to Ceiling Distance
(Min. - Max.)
Upright
4” (102mm) - 12” (305mm)
Pendent
4” (102mm) - 12” (305mm)
Installation Data:
Nominal
Orifice
Thread Size
Nominal K Factor
Sprinkler
Height
Approval
(1)
Organizations
Sprinkler
Identification
Numbers (SIN)
US
Metric
½” (15mm)
½” NPT (R1/2)
5.6
8.0
2.25” (57mm)
1,2,3
RA1385
(1)
(1)
LPC Approval is pendent only, 57°C through 141°C ratings.
(2)
cULus Listed corrosion resistant (Polyester coated) sprinkler.
Model F156 Horizontal Sidewall Sprinkler
Deflector:
HSW
Installation Wrench:
Model D Sprinkler Wrench
Installation Data:
Horizontal Sidewall
Nominal Orifice
Thread Size
Nominal K Factor
Sprinkler
Height
Approval Organizations
Sprinkler
Identification
Numbers (SIN)
US
Metric
Light Hazard
Ordinary
Hazard
½” (15mm)
½” NPT (R1/2)
5.6
80
2.63” (67mm)
1,2
1
RA1335
(1)
(1)
cULus Listed corrosion resistant (Polyester coated) sprinkler.
Horizontal Sidewall
Vertical Sidewall
Note:
For Recessed HSW Sprinklers use installation wrench GFR2.