background image

Technical Data: 

Nominal 

K-Factor

Thread 

Size

Temperature

Rating

Maximum

Ambient

Temperature

Sprinkler

Identification

Number

(SIN)

US

Met-

ric

Sprinkler

SWC

Cover

8.0

115

1” NPT

or

ISO 

7-1R1

155°F   

(68°C)

135°F   

(57°C)

100°F

(38°C)

RA5532

175°F   

(79°C)

165°F 

(74°C)

150°F

(66°C)

200°F   

(93°C)

165°F 

(74°C)

150°F

(66°C)

Required Minimum Flow Rate and Pressure

Maximum Coverage 

Area Width x Length

ft x ft (m x m)

Flow Rate

gpm (L/min)

Pressure

psi (bar)

28 x 14 (8.5 x 4.3)

40 (151)

25 (1.7)

Installation Instructions

Model DH80 Dry sprinklers must only be installed in the 

following fittings:

(1.) the side outlet of an ANSI B 16.3 class 150 malleable iron 

pipe tee

(2.) the side outlet of an ANSI B 16.4 class 125 cast iron pipe 

tee

(3.) the side outlet of a Spears Manufacturing Company Model 

4202-010 or Model 4202-010SR Listed CPVC sprinkler tee

(4.) the side outlet of any Listed CPVC sprinkler tee only in 

accordance with Fig. 9 and upon verification that the CPVC 

sprinkler tee does not interfere with the sprinkler’s inlet.

Model DH80 Dry sprinklers shall not be installed into elbows, 

welded outlets, or gasket sealed outlets. In all installations, 
including into CPVC piping, the dry sprinkler shall be installed 

with protrusion into the fitting in accordance with the installation 

diagrams in this Bulletin. 

Installation of the Model DH80 Dry sprinkler is not recommend 

in copper pipe systems, as this may reduce the life expectancy 
of the sprinkler. Do not install Model DH80 Dry sprinklers with 

the standard (long) inlet fitting into CPVC fittings that have an 

internal obstruction (see Fig. 9); this will damage the sprinkler, 

the  fitting,  or  both.  Model  DH80  Dry  sprinklers  are  available 
with a short “PL” inlet fitting for installation on CPVC fittings of 

wet pipe sprinkler systems only. Model DH80 Dry sprinklers 
connected to wet-pipe systems must be installed with the 

Exposed Minimum Barrel Length required by Fig. 8 located in 

a Heated Area.

A clip is provided to protect the glass bulb thermal element 

from damage. The clip is factory installed on the sprinkler. The 
clip should remain in place during installation of the sprinkler 
and be removed when the sprinkler system is placed in service. 
Model DH80 Dry sprinklers with the Model FP recessed 
escutcheon or the Model SWC cover plate are also supplied 
with a cap that can be used to provide additional protection 

for  the  sprinkler  during  painting  or  finishing.  The  cap  can 

be installed without removing the clip. Both the cap and the 
clip must be removed when the sprinkler system is placed in 
service.

Use the following steps for installation:

1.   The centerline of the Model DH80 Dry sprinkler must be 

installed between 4-5/8” (118 mm) and 12-5/8” (321 mm) 

vertically below the finished ceiling so that the top of the 

deflector is not less than 4“ (102 mm) or more than 12” 

(305 mm) from the finished ceiling. A hole must be cut in 

the wall directly in-line with the outlet of the tee. See the 
Installation Data table for the recommended hole diameter 
based on the escutcheon or cover plate option selected.

2.   

Apply pipe joint compound or Polytetrafluoroethylene 

(PTFE) tape to the threads of the sprinkler’s inlet fitting.

3.   Install the sprinkler in the tee using the installation wrench 

specified  in  the  Installation  Data  table.  The  Model  F3R 

wrench is designed to be inserted into the groves in the 
sprinkler’s wrench boss as shown in Fig. 3. The Model 

XLO2 wrench is designed to fit into the cup and engage the 

wrench boss as shown in Fig. 2. Do NOT wrench any part of 
the sprinkler assembly other than the wrench boss. When 
inserting or removing the wrench from the sprinkler, care 
should be taken to prevent damage to the sprinkler. The 

sprinkler  is  then  tightened  into  the  pipe  fitting  to  achieve 

a leak free connection. The recommended minimum to 

maximum installation torque is 22-30 lb-ft (30 – 40 N-m).

3a. Alternatively, where access to the outer tube of the 

sprinkler is available, the Model DH80 Dry sprinkler may be 
installed using a pipe wrench. The pipe wrench shall only 
be permitted to interface with the steel outer tube portion 
of the sprinkler (Item #8 in Fig. 10). Do NOT wrench any 
other portion of the sprinkler assembly. A pipe wrench can 

install  the  sprinkler  into  the  fitting  with  a  large  amount  of 
torque; consideration should be given to the need for future 
removal of the sprinkler because the installation torque will 

have to be matched or exceeded to remove the sprinkler. 
The recommended minimum to maximum installation 

torque is 22-30 lb-ft (30 – 40 N-m).

4.   Standard and Model HB escutcheons can be installed by 

slipping the escutcheon over the can until the escutcheon 
is seated against the wall. The Model FP escutcheon is 
installed by pressing or threading the escutcheon into the 
cup by hand; the escutcheon can be tightened against the 
wall by turning the escutcheon in a clockwise direction and 
removed by turning the escutcheon in a counter-clockwise 

direction. To install the Model SWC cover plate, first remove 

the protective cap, if installed, and clip. Install the Model 
SWC cover plate on the sprinkler by pressing or threading 
the cover plate into the cup by hand; the cover plate can 
be tightened against the wall by turning the cover plate in a 
clockwise direction and removed by turning the cover plate 
in a counter-clockwise direction. The Model FP recessed 
escutcheon and Model SWC cover plate are the only 
recessed escutcheon and cover plate, respectively, listed 
for use with the Model DH80 Dry sprinkler; the use of any 
other recessed escutcheon or cover plate with the Model 
DH80 Dry sprinkler will void all guarantees, warranties, 
listings and approvals.

5.   Remove the protective cap, if installed, and clip when 

placing the sprinkler system in service.

4.

Summary of Contents for DH80 Dry

Page 1: ...Light Hazard occupancies Patents US Patent No 7 841 418 Products Description The Model DH80 Dry sprinkler is a quick response extended coverage horizontal sidewall sprinkler for use in Light Hazard ap...

Page 2: ...ate occurs when the solder melts due to an increase in the surrounding temperature allowing the cover plate to fall away and exposing the Model DH80 Dry sprinkler Model SWC cover plates are available...

Page 3: ...al throw Sprinklers shall have standard escutcheons extended escutcheons recessed escutcheons conical concealed cover plates produced by the manufacturer of the sprinklers and cULus Listed for use wit...

Page 4: ...ot less than 4 102 mm or more than 12 305 mm from the finished ceiling A hole must be cut in the wall directly in line with the outlet of the tee See the Installation Data table for the recommended ho...

Page 5: ...Stainless Steel Bronze Laquered Brass Chrome Polished Stainless Steel White Polyester 1 White Polyester 4 Black Polyester 1 Black Polyester 4 Custom Color Polyester 1 Custom Color Polyester 4 Electrol...

Page 6: ...Sprinkler Escutcheon 2 3 Bronze Chrome Chrome Chrome White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Stain...

Page 7: ...ite Polyester 2 White Polyester Black Polyester 2 Black Polyester Custom Color Polyester 2 Custom Color Polyester Electroless Nickel PTFE 2 Stainless Steel Notes 1 Cup for FP Recessed is unfinished ga...

Page 8: ...r 1 connections Finish Combinations SWC Concealed Cover Plate Sprinkler 1 Cover Plate 2 Bronze White Polyester Chrome Bright Chrome Dull Bright Brass Unfinished Bronze Black Plate Custom Color Notes 1...

Page 9: ...Fig 8 9...

Page 10: ...10 Fig 9...

Page 11: ...11 Fig 11...

Page 12: ...property for almost 100 years Ordering Information Specify 1 Sprinkler Model DH80 Dry 2 Escutcheon Cover Plate Model Standard escutcheon Model HB extended escutcheon Model FP recessed escutcheon Model...

Reviews: