background image

[Relay] [ON/OFF]

Switches on / off

 a given 

relay

.

To activate the first relay send 

999 TERMO ON

 (

TERMO

is the default name of the relay; use its real name if you

have changed it)

Programs the first relay

 so that it works according to the measured 

temperature

.

C

 will switch on the relay when the temperature is under the lower limit. 

Z

will turn it on when the temperature is over the higher limit.

Sets the 

alarm text

 for the 

maximum

 temperature alarm. All blank spaces

contained in the desired text must be replaced by points in the command.

Enables / disables

 the control pulses for the relays and the reset switch:

1

st

 char.: 

A

 enables the control pulse for the 1

st

 relay. 

N

 disables this input.

2

nd

 char.: 

A

 enables the control pulse for the 2

nd

 relay. 

N

 disables it.

3

rd

 char.: 

A

 enables the reset button. 

N

 disables it. 

B

 sets it so that only the

siren is deactivated by the reset button.

*P[Password]

Changes the 

password

 for a new one (the default password is 1)

To change the password from the default (1) to 

999

send 

1 *P999

*I[A/N][A/N][A/N/B]

To enable the alarm reset button and the external

control pulses send 

999 *IAAA

*T[A-F][Phone number]

Sets the 

phone numbers

 that will be notified when an alarm is fired. The 2

nd

character specifies the recipient (

A

 = 1

st

 recipient, 

B

 = 2

nd

 recipient, etc.). If

the phone number is left blank the corresponding recipient is deactivated.

To  set  phone  number  635469583  as  the  first  alarm

message  recipient  send 

999  *TA635469583

*NX[Text]

If you send 

999 *NXALM.HEAT

, the text 

ALM HEAT

 will

be sent when the TMAX alarm is fired

*NM[Text]

If you send 

999 *NMTEMP.COLD

, the text 

TEMP COLD

will be sent when the TMIN alarm is fired

*NA[Name]

Sets the 

name of the first relay

, usually associated to the thermostat (

TERMO

).

To rename the first relay to 

R1

 (its default name is 

TERMO

)

send 

999 *NAR1

*NB[Name]

Sets the 

name of the second

 relay usually associated to the siren (

SIRENA

).

To rename the second relay to 

R2

 (its default name is

SIRENA

) send 

999 *NBR2

*TV[Phone number]

When the device receives an information request it sends its reply to the

sender of the request. This may not be possible if the request is sent from a

web platform or any other system that is not able to receive messages. This

command allows to specify a 

third recipient

 so that the requested data are

sent to the specified number.

If you send the command 

999 V

 the response SMS will

be sent to your number. If you use 

999 V *TV635469583

instead, the information message will be sent to the

specified number 635469583

*TM[Value/N]

Sets

 the lowest valid temperature for the 

minimum temperature

 alarm. 

N

deactivates the alarm. If a value is used it is set as the lowest temperature

limit. The temperature must be expressed in centigrade degrees and it can

also be negative (-25 to 85º C).

To disable the alarm send 

999 *TMN.

To set -5º C as the minimum temperature limit send the

command 

999 *TM-5

*TX[Value/N]

Sets

 the highest valid temperature for the 

maximum temperature

 alarm. 

N

disables the alarm. If a value is specified it is used as the highest temperature

limit. The temperature must be expressed in centigrade degrees and it can

be negative (-25 to 85º C).

To disable the alarm send 

999 *TXN.

To set 30º C as the maximum temperature limit send

the command 

999 *TX30

*SA[Value]

Sets the 

delay

 for the power supply failure and recovery alarms. The value

must be specified in seconds.

If the supply failure alarm must be fired two minutes

after the failure, send 

999 *SA120

*SB[Value]

Sets the 

hysteresis

 margin 

of the thermostat

. Every step corresponds to half

a degree.

To set a hysteresis of 2 degrees send the command 

999

*SB4

*SC[A/N]

Enables or disables the 

failure

 alarm 

of the temperature probe

A

 enables the

alarm; 

N

 disables it.

In order to deactivate the alarm send 

999 *SCN

*SD[A/B/N]

Configures the 

alarm of power supply

 failure and recovery. 

A

 enables only

the failure one. 

B

 enables both. 

N

 deactivates all power supply alarms.

To deactivate both the supply failure alarm and the

supply recovery alarm send 

999 *SDN

*SM[A/B/C/D/E/F]

Configures the 

periodical sending

 of a verification message to the first alarm

recipient. 

A

 disables it; the rest of the options enable it for a sending every

24 hours (

B

), every week (

C

), every 20 days (

D

), every 60 days (

E

) or every 120

days (

F

). Time intervals are only calculated approximately, especially the

longest ones.

If a periodical verification message is to be sent every

week  to  the  phone  number  635469583,  send 

999

*TA635469583 *SMC

*SR[A/N/Value]

Sets the reset 

mode for the temperature alarms

A

 activates the automatic

reset mode. 

N

 sets the manual mode. If a value is provided, the timed reset

mode is activated and the reset will occur after the given delay. The value

is expressed as 10-minute intervals and the minimum value is 1 (corresponds

to a 10-minute delay).

For the alarms to be reset every hour send 

999 *SR6

*SH[A/N/Value]

Configures 

how the siren works

 whenever a temperature alarm is fired. 

N

disables the siren and 

A

 enables it so that it will stay turned on until the

temperature alarm is reset. If a value is used instead, the siren will keep

switched on for that many seconds or until it is otherwise reset (either manually

or automatically).

If the siren is to keep switched on for 2 minutes when

the maximum temperature alarm is fired, send 

999

*SH120

*ST[Value]

Sets a 

delay for the temperature alarms

 before they are fired. It is especially

useful for environments where temperature fluctuates around the set limits.

The value is expressed in minutes.

To delay 10 minutes the temperature alarms send 

999

*ST10

ENVIO [ON/OFF]

Enables / disables the alarm 

message sending

.

To enable the message sending send 

999 ENVIO ON

[Relay] [Value][S/M/H]

Sets a 

timing for a

 given 

relay

. In additon to the time value a code for the

time units must be specified (

S

 for seconds, 

M

 for minutes and 

H

 for hours) and

it must be within [1 - 1440] for  minutes and seconds, or [1 - 48] for the hours.

To activate the second relay for 35 minutes send the

command 

999 SIRENA 35M

 (

SIRENA

 is the default

name of the second relay)

TERMO [Value][C/Z]

For the first relay to be activated when the temperature

is over 23º C, send 

999 TERMO 23C

Sets the 

alarm text

 for the 

minimum

 temperature alarm. All blank spaces

contained in the desired text must be replaced by points in the command.

Command

Description (programming functions)

Example (999 is used as password)

Command

Description (telecontrol functions)

Example

(*) Both upper and lower case can be used, the system is case insensitive.

(**) Several commands may be sent together separating them by a blank space

EXAMPLE

: for a warning to be sent to the phone number 666666666 when the temperature is over 20º C, send:

999  ENVIO  ON  *TA666666666  *TX20 

(the  alarm  will  fire  again  every  time  that  value  is  exceeded)

EXAMPLE

: to activate heating whenever the probe temperature is over 21º C, and also get an SMS regarding the status of the device send:

999 ENVIO ON *TERMO 21C V