[Relay] [ON/OFF]
Switches on / off
a given
relay
.
To activate the first relay send
999 TERMO ON
(
TERMO
is the default name of the relay; use its real name if you
have changed it)
Programs the first relay
so that it works according to the measured
temperature
.
C
will switch on the relay when the temperature is under the lower limit.
Z
will turn it on when the temperature is over the higher limit.
Sets the
alarm text
for the
maximum
temperature alarm. All blank spaces
contained in the desired text must be replaced by points in the command.
Enables / disables
the control pulses for the relays and the reset switch:
1
st
char.:
A
enables the control pulse for the 1
st
relay.
N
disables this input.
2
nd
char.:
A
enables the control pulse for the 2
nd
relay.
N
disables it.
3
rd
char.:
A
enables the reset button.
N
disables it.
B
sets it so that only the
siren is deactivated by the reset button.
*P[Password]
Changes the
password
for a new one (the default password is 1)
To change the password from the default (1) to
999
send
1 *P999
*I[A/N][A/N][A/N/B]
To enable the alarm reset button and the external
control pulses send
999 *IAAA
*T[A-F][Phone number]
Sets the
phone numbers
that will be notified when an alarm is fired. The 2
nd
character specifies the recipient (
A
= 1
st
recipient,
B
= 2
nd
recipient, etc.). If
the phone number is left blank the corresponding recipient is deactivated.
To set phone number 635469583 as the first alarm
message recipient send
999 *TA635469583
*NX[Text]
If you send
999 *NXALM.HEAT
, the text
ALM HEAT
will
be sent when the TMAX alarm is fired
*NM[Text]
If you send
999 *NMTEMP.COLD
, the text
TEMP COLD
will be sent when the TMIN alarm is fired
*NA[Name]
Sets the
name of the first relay
, usually associated to the thermostat (
TERMO
).
To rename the first relay to
R1
(its default name is
TERMO
)
send
999 *NAR1
*NB[Name]
Sets the
name of the second
relay usually associated to the siren (
SIRENA
).
To rename the second relay to
R2
(its default name is
SIRENA
) send
999 *NBR2
*TV[Phone number]
When the device receives an information request it sends its reply to the
sender of the request. This may not be possible if the request is sent from a
web platform or any other system that is not able to receive messages. This
command allows to specify a
third recipient
so that the requested data are
sent to the specified number.
If you send the command
999 V
the response SMS will
be sent to your number. If you use
999 V *TV635469583
instead, the information message will be sent to the
specified number 635469583
*TM[Value/N]
Sets
the lowest valid temperature for the
minimum temperature
alarm.
N
deactivates the alarm. If a value is used it is set as the lowest temperature
limit. The temperature must be expressed in centigrade degrees and it can
also be negative (-25 to 85º C).
To disable the alarm send
999 *TMN.
To set -5º C as the minimum temperature limit send the
command
999 *TM-5
*TX[Value/N]
Sets
the highest valid temperature for the
maximum temperature
alarm.
N
disables the alarm. If a value is specified it is used as the highest temperature
limit. The temperature must be expressed in centigrade degrees and it can
be negative (-25 to 85º C).
To disable the alarm send
999 *TXN.
To set 30º C as the maximum temperature limit send
the command
999 *TX30
*SA[Value]
Sets the
delay
for the power supply failure and recovery alarms. The value
must be specified in seconds.
If the supply failure alarm must be fired two minutes
after the failure, send
999 *SA120
*SB[Value]
Sets the
hysteresis
margin
of the thermostat
. Every step corresponds to half
a degree.
To set a hysteresis of 2 degrees send the command
999
*SB4
*SC[A/N]
Enables or disables the
failure
alarm
of the temperature probe
.
A
enables the
alarm;
N
disables it.
In order to deactivate the alarm send
999 *SCN
*SD[A/B/N]
Configures the
alarm of power supply
failure and recovery.
A
enables only
the failure one.
B
enables both.
N
deactivates all power supply alarms.
To deactivate both the supply failure alarm and the
supply recovery alarm send
999 *SDN
*SM[A/B/C/D/E/F]
Configures the
periodical sending
of a verification message to the first alarm
recipient.
A
disables it; the rest of the options enable it for a sending every
24 hours (
B
), every week (
C
), every 20 days (
D
), every 60 days (
E
) or every 120
days (
F
). Time intervals are only calculated approximately, especially the
longest ones.
If a periodical verification message is to be sent every
week to the phone number 635469583, send
999
*TA635469583 *SMC
*SR[A/N/Value]
Sets the reset
mode for the temperature alarms
.
A
activates the automatic
reset mode.
N
sets the manual mode. If a value is provided, the timed reset
mode is activated and the reset will occur after the given delay. The value
is expressed as 10-minute intervals and the minimum value is 1 (corresponds
to a 10-minute delay).
For the alarms to be reset every hour send
999 *SR6
*SH[A/N/Value]
Configures
how the siren works
whenever a temperature alarm is fired.
N
disables the siren and
A
enables it so that it will stay turned on until the
temperature alarm is reset. If a value is used instead, the siren will keep
switched on for that many seconds or until it is otherwise reset (either manually
or automatically).
If the siren is to keep switched on for 2 minutes when
the maximum temperature alarm is fired, send
999
*SH120
*ST[Value]
Sets a
delay for the temperature alarms
before they are fired. It is especially
useful for environments where temperature fluctuates around the set limits.
The value is expressed in minutes.
To delay 10 minutes the temperature alarms send
999
*ST10
ENVIO [ON/OFF]
Enables / disables the alarm
message sending
.
To enable the message sending send
999 ENVIO ON
[Relay] [Value][S/M/H]
Sets a
timing for a
given
relay
. In additon to the time value a code for the
time units must be specified (
S
for seconds,
M
for minutes and
H
for hours) and
it must be within [1 - 1440] for minutes and seconds, or [1 - 48] for the hours.
To activate the second relay for 35 minutes send the
command
999 SIRENA 35M
(
SIRENA
is the default
name of the second relay)
TERMO [Value][C/Z]
For the first relay to be activated when the temperature
is over 23º C, send
999 TERMO 23C
Sets the
alarm text
for the
minimum
temperature alarm. All blank spaces
contained in the desired text must be replaced by points in the command.
Command
Description (programming functions)
Example (999 is used as password)
Command
Description (telecontrol functions)
Example
(*) Both upper and lower case can be used, the system is case insensitive.
(**) Several commands may be sent together separating them by a blank space
EXAMPLE
: for a warning to be sent to the phone number 666666666 when the temperature is over 20º C, send:
999 ENVIO ON *TA666666666 *TX20
(the alarm will fire again every time that value is exceeded)
EXAMPLE
: to activate heating whenever the probe temperature is over 21º C, and also get an SMS regarding the status of the device send:
999 ENVIO ON *TERMO 21C V
Temperature controller SMX-T80 - User manual