Printed in the Federal Republic of Germany
TR-Electronic GmbH 2013, All Rights Reserved
01/17/2019
TR - ECE - BA - DGB - 0102 - 09
Page 129 of 175
7.4.3.7
Standard scaling parameter (≤ 32 bit)
To use “Attribute 16, Measuring Units per Span” and “Attribute 17, Total Measuring
Range in Measuring Units
” the “Attribute 105, TR-Parameter in use (scaling)” must be
set to “0”.
Danger of personal injury and damage to property exists if the measuring
system is restarted after positioning in the de-energized state by shifting
of the zero point!
If the number of revolutions is not an exponent of 2 or is >4096, it can occur, if
more than 512 revolutions are made in the de-energized state, that the zero
point of the multi-turn measuring system is lost!
Ensure that the
Number of Revolutions
for a multi-turn measuring system is
an exponent of 2 of the group 2
0
, 2
1
, 2
2
…2
12
(1, 2, 4…4096).
or…
Ensure that every positioning in the de-energized state for a multi-turn
measuring system is within 512 revolutions.
7.4.3.7.1 Attribute 16, Measuring Units per Span
Measuring Units per Span
sets the number of steps per revolution.
UDINT
Steps per revolution
Byte 0
Byte 1
Byte 2
Byte 3
2
7
up to 2
0
2
15
up to 2
8
2
23
up to 2
16
2
31
up to 2
24
Access
Set / Get
Lower limit
1 step per revolution
Upper limit
CE_: 32768 steps per revolution (see max. value on the nameplate)
CO_: 262144 steps per revolution (see max. value on the nameplate)
Default
4096
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x10
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #16
This attribute only takes effect after executing service code 0x16
save
or attribute 112
Accept Parameter
.