Parameterization
TR-Electronic GmbH 2013, All Rights Reserved
Printed in the Federal Republic of Germany
Page 128 of 175
TR - ECE - BA - DGB - 0102 - 09
01/17/2019
7.4.3.5 Attribute 12, Direction Counting Toggle
Direction Counting Toggle
sets the counting direction of the measuring
system.
BOOL
Access Value Description
Default
Set/Get
0
Position increasing clockwise (view onto the shaft)
X
1
Position decreasing clockwise (view onto the shaft)
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x0C
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #12
This attribute only takes effect after executing service code 0x16
save
or attribute 112
Accept Parameter
.
7.4.3.6 Attribute 15, Position Format
Position Format
sets the output format of the position value (attribute
) it is
permanently set to
„steps“.
ENGUNIT
Value
Unit
0x1001
steps [stp]
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x0F
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #15
This attribute only takes effect after executing service code 0x16
save
or attribute 112
Accept Parameter
.