
│
22
REGULUS - STDC E Controller - www.regulus.eu
F 5.11 - Tset
(Thermostat1)
„Thermostat“
has 2 functions:
Backup (heating) - if the parameter value of
„Tset on“
is lower than that of
„Tset off“
.
If the temperature at sensor S1 falls below
„Tset on“
and the
„Thermostat“
function is on, the backup
heating relay switches on and stays on until the temperature reaches
„Tset off“
.
Example:
The storage tank shall be heated from a backup source to keep its temperature above 50 °C. A heat
source pump shall be wired to relay R.
Set Tset On = 50 °C, Tset Off = 58 °C. When the temperature in the tank falls below 50 °C, relay R will switch
on and remain switched until the tank heats up to 58 °C.
Heat exchange (tank recooling) - if the parameter value of
„Tset on“
is higher than that of
„Tset off“
.
If the temperature at sensor S1 falls below
„Tset on“
and the
„Thermostat“
function is on, the recooling relay
switches on and stays on until the temperature reaches
„Tset off“
.
Example:
When the tank temperature exceeds 60 °C, the surplus heat shall be conveyed into the heating
system. A heat source pump shall be wired to relay R.
Set Tset On = 60 °C, Tset Off = 52 °C. When the temperature in the tank exceeds 60 °C, relay R will switch on
and remain switched until the tank cools down to 52 °C.
Setting range:
Tset on: 10-90 °C / Default setting: 50 °C
Tset off: 0-99 °C / Default setting: 60 °C
If a S2 sensor is installed, then S1 sensor shall be used for switching on (Tset On) and S2 for
switching off (Tset Off).
F 5.20 - Tmax S1
If this value is exceeded at sensor S1, then the controller switches the associated pump and/or valve on. If the
temperature at sensor S1 drops below this value by 5 °C, then the pump and/or the valve are switched off again.
Setting range: 0-99 °C (for hydraulic variants
„Thermostat“
and
„Universal
Δ
T“
this value may be set to Off)
Default setting: 60 °C (for hydraulic variant
„Solar system with pool“
the default setting is off)
Temperature values which are set too high will allow higher solar heat accumulation but it shall be
checked that all system components are resistant to high temperature and scalding protection is
provided. Regulus solar systems are safe for heating water up to 95 °C.
F 5.21 - Thermostat periods
Set the desired periods of time when the thermostat should be active. 2 periods can be set per day, settings
can also be copied to other days. Outside the set times the thermostat is switched off.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
F 5.22 - Tmax S3
Switch-off temperature at S3 sensor
If this value is exceeded at sensor S3, the controller switches the relay off. If the temperature falls below this
value again, the controller switches the relay on again. For switching on and off further conditions shall be met
as well.
Setting range: from 0 °C to 99 °C / default setting: 60 °C
(if the selected variant does not use S3, the default setting is Off).
Temperature values which are set too high will allow higher solar heat accumulation but it shall be
checked that all system components are resistant to high temperature and scalding protection is
provided. Regulus solar systems are safe for heating water up to 95 °C.
Party function (for Thermostat function only)
With the party function the storage tank is heated up once to the set temperature (TsetS1), disregarding the
set thermostat times.
The party mode is enabled by pressing the
„esc“
key for 3 seconds in the main menu. While this mode is
active, the system heats up to the set value Tset Off unattached to preset thermostat times. The mode is
ended once the required temperature is reached.
Caution
Danger
Danger
Summary of Contents for STDC E
Page 1: ...EN v 1 5 STDC E Controller Instruction Manual...
Page 35: ......