Installation and Operation Manual 

CSE MIX W6 1F PUMP STATION with mixing valve

Summary of Contents for 18317

Page 1: ...www regulus eu CSE MIX W6 1F CSE MIX W6 1F EN Installation and Operation Manual CSE MIX W6 1F PUMP STATION with mixing valve...

Page 2: ...25 6 SC pump including a power cable a 3 way mixing valve with actuator incl a power cable a ball valve and insulation Main Features Application It ensures circulation and mixing in a heating circuit...

Page 3: ...agram shows a typical connection of a solid fuel boiler thermal store and heating circuit If there is also the indicated hot water circuit install the CSE OTS ZV pump station not included in the suppl...

Page 4: ...echnical data Torque 5 Nm Angle of rotation 90 Shift time 120 s Control 3 point Auxiliary switch none Power supply 230 V AC Max power input 2 5 VA IP rating IP42 Protection class II by EN 60730 1 Cabl...

Page 5: ...in unpressurized systems can lead to its rapid destruction 5 2 Pump Description 1 Pump housing 2 Pump motor 3 Condensate drain openings 4 Pump housing bolts 5 Control module 6 Rating plate 7 Pump adju...

Page 6: ...t speed operating mode and pump performance curve III are preset as factory settings for the PARA SC pump After switching on the pump runs at the factory setting or at the last setting The settings ca...

Page 7: ...tting hold the control button for at least 4 seconds and switch off the pump by disco nnecting it from the mains SETTING THE PUMP PROFILE Briefly press the operating button for 1 second to select oper...

Page 8: ...l pump venting press and hold the operating button for 3 sec MANUAL RESTART If the pump has been inactive for a long time or is blocked activate the manual restart by holding the operating button for...

Page 9: ...hanged To unlock hold down the operating button again for 8 seconds and the LEDs will stop flashing FACTORY SETTINGS To return to the factory settings press and hold the operating button for at least...

Page 10: ...r hand is unsuitable for circuits with heat sources where the reduction of the head and flow can make these sources even inoperable By reducing the discharge as the flow decreases the pump s power con...

Page 11: ...revious mode p v could cause insufficient heating through discharge reduction By decreasing the required flow the pump maintains a constant delivery head thus the pump power consumption decrease is mo...

Page 12: ...as set by a selector switch For example this mode may be suitable for older circuit types where flow is regulated by throttling and this method required to be maintained Furthermore it may be suitable...

Page 13: ...m Pump Electric Data Power supply 230 V 50 Hz Power input min max 3 43 W Current min max 0 04 0 44 A Max speed 4300 rpm Speed control frequency converter Energy Efficiency Index 0 21 by EN 16 297 3 IP...

Page 14: ...etting if necessary set lower head Building not warming up Heat output of heating surfaces too low Set higher temperature at controller and fully open radiator valves If this does not help increase ci...

Page 15: ...and refit the actuator in the same position When needed the mixing valve can be rotated to the right hand position see Fig 2 After the valve is turned by 180 and the fittings tightened the actuator l...

Page 16: ...tic wheel properly see Fig 4 and finally fit the plastic adapter the arrow on the plastic adapter forms an angle of 45 with inlets 1 and 3 see Fig 4 The flat spot on the shaft and the arrow on the pla...

Page 17: ...divide between red and blue on the label and then fit the actuator onto the adapter already on the valve The control knob shall be able to turn freely both to left and right by 45 When turned to the r...

Page 18: ...5 and on the left hand side for right hand installations see Fig 6 Fig 5 Fig 6 In case of a horizontal installation with a solid fuel boiler the red mark on the label shall be on the right hand side f...