9
Régul’ Electronique
1- Connect the power cable of device in the
filtration cabinet.
- Phase=brown wire=on terminal 3 of the
circuit breaker.
- Neutral=blue wire=on the neutral strip.
2-Plug the cable into the device on the power
supply terminal block.
Connecting the device
Wiring terminals of the electronic board of The Bulleur
Warning : risk of electric shock.
Before working on the device, disconnect the circuit breaker.
Filtration cabinet
neutral strip
pump
The appliance must be wired so that it is always on (not connected to filtration).
The power cable must be plugged into the filter cabinet as shown below.
Connecting the « filtering force »
Connecting the « filtration stop »
Wired by a 2 x 1mm2 cable in serie on the clock contact.
Disconnect the wire connected to the filter clock contact.
Connect one of the wires to this contact and then the other by a
quick connection on the left wire-In contrast to the filtration force,
for safety reasons, it is necessary to be able to stop the filtration,
in particular when the level is too low.
M
horloge
Horloge de Filtration
M
horloge
Horloge de Filtration
Connecting the « electro valve »
The Bulleur provides on the solenoid valve connector the
24 V required to supply the valve in option (1" RAINBIRD DV100FF).
Connecting the « drain pump »
It is possible to drive a drain pump in the event of an overflow caused by rain,
connect to the connector a drain pump by a contactor or a power relay.
P N
Wired by a cable 2 x1 mm2 in parallel with the contact of the
clock.
In order for the device to be able to force the filtration when the
water level rises to level 3, closing the relay force filtration will
make it