Connection of EP8102 with the EIB option X9017 on Port 3.

Pin no Signal

Detailed function

Group function

1

EMI ground

This terminal is connected internally to the PIFA’s 
frame and to internal protective circuits. It should be 
connected to the ground rail with a separate, heavy 
gauge.

 

2

+12 V DC

+12 V DC output

3

Gnd3

Signal Ground

4

B2

EXOline connection, Port 2 
Galvanically insulated from all other 
circuits. 

5

A2

6

N2

The 0 V reference. This should be connected to the 
screen of the communication cable, which in turn 
should be grounded at one point at least.

7

E2

8

B3

EXOline connection, Port 3 
Galvanically insulated from all other 
circuits. 

9

A3

10

N3

The 0 V reference. This should be connected to the 
screen of the communication cable, which in turn 
should be grounded at one point at least.

11

E3

12

DTR

  

Option X9017

13

Gnd

Signal Ground

14

EMI ground

This terminal is connected internally to the PIFA’s 
frame and to internal protective circuits. It should be 
connected to the ground rail with a separate, heavy 
gauge.

15

TxD

Transmit Data (Out)

16

RxD

Receive Data (In)

17

RTS

Request To Send (Out)

18

CTS

Clear To Send (In)

19

+24 V DC

Inputs for +24 V DC power supply

20

0 V

Power supply 0 V. The 0 V-connection is normally 
grounded at the supply source, so as to define the 
potential to earth reference and to compensate for 
disturbances and transients from I/O signals.

21

TxD2

See “The RS232 Port” on page 2.

RS232 connection, Port 2

This connection is galvanically 
insulated from the internal circuits. 
GND2 is the signal zero. Use screened 
cable and earth it at one point.

22

RxD2

23

RTS2

24

CTS2

25

GND2

26

SEL2

27

TxD3

See “The RS232 Port” on page 2.

RS232 connection, Port 3

This connection is galvanically 
insulated from the internal circuits. 
GND3 is the signal zero. Use screened 
cable and earth it at one point.

28

RxD3

29

RTS3

30

CTS3

31

GND3

32

SEL3

33

DTR3

34

DSR3

35

DCD3

36

RI3