INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

Valve actuator for 3-position control

RVAZ4L1-24 is intended to be used together with Regin’s MVFL 
valves.

Technical data

Supply voltage 

 

24 V AC ±15 % 

 

Control signal 

 

3-position (increase - decrease) 

Power consumption  

Max. 0.6 W

Stroke 

 

5.5 mm

Stroke time  

 

150 s

Force  

 

400 N

Ambient temperature, operation   0…50°C
Media  temperature  

1...110°C

Storage temperature  

-10…+80°C

Ambient humidity    

Max 95 % RH

Measurements (W x H x L) 

60 x 75.5 x 92 mm 

Protection class   

IP44

Mounting

The valve should be mounted so that the drive rod on the actuator is 
within 90° from the vertical line and the motor housing is on top. The valve 
actuator’s drive rod should be in its highest/innermost position when it is 
mounted on the valve. 
Fix the actuator to the valve using the connection nut, manual power is 

sufficient.

90º

90º

Wiring

The actuator has a connection cable with a connector which is intended 
for connection to the bottom of the actuator. There is only one way to plug 
in the contact. Be careful not to damage the cable if the connector needs 
to be removed from the actuator.
Red, black is connected to the controller’s increase and decrease signals 
respectively, blue to the common.

Red = spindle out (opening valve)
Black = spindle in (closing valve)
Blue = common 

Controller, 3-point output

24 V AC opening
24 V AC closing
24 V AC common

RED

BLACK

BLUE

RVAZ4L1- 

24

Manual manoeuvring

Before the actuator is set manually, the supply voltage must first be cut. 

To set the valve position manually, hold down the disengagement button 
(A in the picture below) and then turn the knob for manual manoeuvring 
(B in the picture below) to the desired position. When the knob is turned 
clockwise, the drive rod is pushed outwards and when the knob is turned 
anti-clockwise, the drive rod is pulled inwards.

A

B

Position indication

RVAZ4L1-24 has a clear position indication which is shown on the 
knob for manual manoeuvring. There are markings for 0, 25, 50, 75 
and 100 % open position. 

 

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regin.se, [email protected]

RVAZ4L1-24

10008C

 

FEB 14

EN

1